PGDB Certifying Plumber · Put your knowledge to work in context.

All case studies

Café water supply, shared pressure and high-hazard backflow

You are asked to assess water supply and backflow prevention for a 60-seat café being fitted out in the ground floor of a two-storey 1920s building. The existing 20 mm lead-in comes from the council main. Static pressure is 280 kPa at the ground-floor meter and 120 kPa at the first-floor apartment; the café shares the supply with the two apartments above. The café will have two espresso machines, a carbonated drink dispenser using a CO2 cylinder, a 200 L hot water cylinder, and a six-station garden irrigation system supplied through a hose tap. The only existing backflow protection is a single non-return valve at the meter. The council's cross-connection policy requires testable protection for high hazards. The upstairs tenant complains that the shower pressure drops when the café dishwasher runs. The owner wants the cheapest solution that will pass inspection.

1. Identify the backflow hazards and specify the protection required at each point. Would a single non-return valve satisfy the council?

Read the worked answer

The single non-return valve is not acceptable. It is not testable, its condition is unknown, and it provides no protection against backpressure from the carbonator or irrigation system.

The carbonated drink dispenser is a high hazard because CO2 can be forced back into the potable supply and is not detectable by taste or smell. It requires a testable reduced pressure zone (RPZ) device or an air gap, located so that the whole carbonator branch is protected. The irrigation system is also a cross-connection: if it is a simple hose tap, a hose connection vacuum breaker may protect that outlet, but a fixed six-station system normally needs a testable device appropriate to the council's hazard rating, often an RPZ or dual-check valve. Because the café shares a supply with residential units, I would also consider zone protection at the property boundary to protect the apartments from café hazards.

I would map each hazard, select the device, confirm the council's classification, and ensure the devices are accessible for testing and not buried or concealed.

2. The first-floor pressure is 120 kPa and drops when the café uses water. What hydraulic checks and options should you present?

Read the worked answer

A 20 mm lead-in serving a café, two apartments and a 200 L cylinder is likely to be marginal even before backflow protection is added. The static pressure at the first floor is already 120 kPa; an RPZ will add pressure loss, and peak simultaneous demand from the dishwasher, espresso machines and cylinder will reduce it further. I would carry out a hydraulic calculation using the measured static and residual pressures, the developed length, fittings, elevation and fixture demand. I would also measure residual pressure at the first-floor shower while the café is running, not just static pressure.

Options to present are:

  • upgrade the lead-in and internal pipework to reduce friction loss;
  • install a booster set with a break tank or accumulator, subject to council approval and backflow protection;
  • manage demand by staggering high-flow appliances;
  • locate the RPZ to minimise pressure loss and protect it from frost and damage.

A pressure-reducing valve is not the answer to low pressure. The owner needs a measured, designed solution, not the cheapest device that appears to pass inspection.

3. What commissioning and ongoing compliance steps apply to the selected backflow devices?

Read the worked answer

The devices must be commissioned by a competent person and tested with calibrated equipment. I would record the device type, size, serial number, location, hazard served and test results. The test should confirm the pressure differential or check-valve performance required for that device type, not merely that water flows.

The council should receive the cross-connection application and test certificate, and the device should be tagged with the test date and tester. Annual testing is normally required for testable devices, with immediate retesting after repair or relocation. The owner should have a maintenance schedule and know that removal, bypassing or alteration of the device is not permitted without approval.

I would also confirm that the irrigation system has a suitable backflow device and that hose taps are protected. At handover, provide as-built drawings showing the backflow devices and a simple logbook for test records.