OR Fire Alarm Installer flashcards
OR Fire Alarm Installer · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- NFPA 72
- National Fire Alarm and Signaling Code; sets requirements for design, installation, testing, and maintenance of fire alarm systems in the United States.
- NEC Article 760
- Covers fire alarm system wiring, including power-limited and non-power-limited circuits, and requires listed cable and proper separation.
- Smoke detector spacing
- 30 ft (9.1 m) on smooth ceilings, with the first detector within 15 ft (4.6 m) of any wall or ceiling projection.
- Manual pull station height
- Must be mounted 3.5 ft to 4.5 ft (1.07 m to 1.37 m) above finished floor and within 5 ft (1.5 m) of an exit door.
- Photoelectric smoke detector
- Uses a light source and sensor to detect scattered light from smoke particles; responds best to smoldering fires with larger particles.
- Ionization smoke detector
- Uses an ionization chamber to detect changes in current caused by smoke particles; responds best to flaming fires with smaller particles.
- Rate-of-rise heat detector
- Activates when temperature increases rapidly, typically at 15°F (8.3°C) per minute, regardless of the absolute temperature.
- Duct smoke detector
- Required in HVAC systems over 2,000 cfm (0.94 m³/s); detects smoke in the air stream and requires remote test stations.
- Class A circuit
- Initiating or notification circuit that continues to operate with a single open fault by providing a redundant return path.
- Class B circuit
- Circuit that does not survive a single open fault; a break in the wiring causes loss of devices beyond the break.
- Notification appliance circuit
- Supervised circuit that powers horns, strobes, speakers, and other notification appliances; must be designed for voltage drop.
- Audible signal level
- At least 15 dBA above ambient or 5 dBA above maximum ambient (whichever is greater) and at least 75 dBA at 10 ft (3 m).
- Strobe synchronization
- Required when multiple strobes are visible from a single location; prevents seizures and confusion by flashing simultaneously.
- Strobe candela rating
- 15 cd for rooms up to 20 ft x 20 ft; higher candela required for larger rooms per NFPA 72 Table 18.5.5.4.1(a).
- Voltage drop formula
- VD = (2 x L x R x I) / 1000, where L is one-way length in feet, R is resistance in ohms per 1000 ft, and I is current in amperes.
- Copper wire resistance
- Approximate values: 14 AWG = 3.07 ohms/1000 ft; 12 AWG = 1.93 ohms/1000 ft; 10 AWG = 1.21 ohms/1000 ft; 16 AWG = 4.89 ohms/1000 ft.
- Maximum NAC voltage drop
- Typically 10% of rated voltage (2.4 V for 24 V systems) to ensure the last appliance operates properly.
- Battery calculation formula
- Standby current (A) x 24 h + alarm current (A) x 0.083 h (5 min) = Ah; add 20% derating for aging and temperature.
- Voice system battery calculation
- Use 24 hours standby plus 15 minutes (0.25 h) alarm, instead of 5 minutes, for voice evacuation systems.
- Battery charger requirement
- Must recharge batteries within 48 hours after full discharge; 24 hours for voice systems.
- Primary power requirement
- 120 VAC dedicated branch circuit labeled "FIRE ALARM CIRCUIT CONTROL," protected against accidental disconnection.
- Secondary power requirement
- Must operate system for 24 hours standby plus 5 minutes alarm (or 15 minutes for voice) using batteries or approved source.
- FPLR cable
- Fire alarm cable rated for riser use; suitable for vertical runs between floors in non-plenum spaces.
- FPLP cable
- Fire alarm cable rated for plenum use; required in environmental air spaces such as above suspended ceilings.
- Power-limited circuit separation
- Must be separated from non-power-limited circuits by separate conduits or barriers; label circuits appropriately.
- Record of Completion
- NFPA 72 Form 1 documenting that the system has been installed and tested per design; required for acceptance.
- Record of Inspection and Testing
- NFPA 72 Form 2 documenting periodic inspection and testing results; must be maintained and available to the AHJ.
- Smoke detector sensitivity testing
- Required within one year of installation and every two years thereafter; use calibrated equipment per manufacturer instructions.
- Annual inspection
- All initiating devices and notification appliances must be inspected and tested annually per NFPA 72.
- Oregon fire alarm contractor license
- Required by the Oregon State Fire Marshal for contractors installing or servicing fire alarm systems; individuals must hold installer certificate.
- Permit requirement
- Must obtain permit from local AHJ before installing or modifying a fire alarm system; submit plans for review.
- AHJ
- Authority Having Jurisdiction; the organization or individual responsible for enforcing code requirements and approving installations.