OR Fire Alarm Installer key terms
OR Fire Alarm Installer · Get comfortable with the vocabulary.
- Addressable device
- Related: Signaling line circuit (SLC), Zone
A field device that has its own unique digital identifier on the signaling line circuit, so the control unit can report and test it individually rather than reporting only a zone.
- Conventional zone
- Related: Addressable device, Zone
A group of initiating devices wired on a single pair of conductors so the panel sees the group as one alarm location, not individual devices.
- Zone
- Related: Conventional zone, Annunciator
A defined area or group of devices used to locate a fire or trouble condition and to organize annunciation, output logic, and response planning.
- Initiating device circuit (IDC)
- Related: Conventional zone, End-of-line resistor
The wiring path connecting automatic detectors and manual stations to the control unit, monitored for alarm, open, and short conditions.
- Signaling line circuit (SLC)
- Related: Addressable device, Isolator module
The addressable data loop or spur that carries power and digital communication between the control unit and addressable devices such as detectors, modules, and isolators.
- Notification appliance circuit (NAC)
- Related: End-of-line resistor, Synchronization
The power circuit that operates horns, strobes, speakers, and other alerting devices, typically supervised and arranged so a single fault does not disable all notification.
- End-of-line resistor
- Related: Initiating device circuit (IDC), Supervision
A resistor installed at the far end of a supervised conventional circuit so the panel can detect opens, and detect shorts by the drop in normal current.
- Supervision
- Related: End-of-line resistor, Trouble signal
Continuous electrical monitoring of circuit integrity and component power so that a break, short, or loss of operating power produces a trouble signal at the control unit.
- Class A circuit
- Related: Class B circuit, Supervision
A supervised circuit that continues to function past a single open or ground fault because the outgoing and return paths are separate, allowing devices beyond the fault to still operate.
- Class B circuit
- Related: Class A circuit, End-of-line resistor
A supervised circuit that loses operation beyond a single open fault; the panel still detects the fault but devices past the break no longer function.
- Smoke detector spacing
- Related: Spot-type smoke detector, Detector coverage area
The maximum listed spacing between detectors, commonly 30 feet on smooth ceilings, adjusted downward for ceiling height, beams, and airflow conditions.
- Spot-type smoke detector
- Related: Smoke detector spacing, Projected beam detector
A detector that samples air at a localized point, using photoelectric light scatter or ionization sensing, as opposed to projecting a beam across a space.
- Projected beam detector
- Related: Spot-type smoke detector, Air-sampling detection
A smoke detector that spans a long distance with a transmitter and receiver, responding to smoke obscuration along the beam path; typically used in large open spaces.
- Air-sampling detection
- Related: Projected beam detector, Smoke detector spacing
A system that draws air from a protected area through a pipe network to a remote detector, used where point detectors are impractical or early warning is needed.
- Heat detector
- Related: Spot-type smoke detector, Detector coverage area
A device that responds to fixed temperature, rate of temperature rise, or both; it is slower than smoke detection and used where smoke detectors are unsuitable.
- Detector coverage area
- Related: Smoke detector spacing, Heat detector
The floor area assigned to one detector, derived from listed spacing and ceiling geometry, used to lay out detector locations on a plan.
- Manual fire alarm box
- Related: Initiating device circuit (IDC), Zone
A manually operated initiating device, usually pull-station type, mounted along the means of egress at accessible height so occupants can trigger the alarm.
- Waterflow switch
- Related: Supervisory signal, Alarm signal
A device on a sprinkler system pipe that senses sustained water movement and sends an alarm signal, distinguishing real flow from pressure surges.
- Supervisory signal
- Related: Trouble signal, Alarm signal
A signal indicating an off-normal condition in a suppression or control system, such as a closed valve or low air pressure, that does not yet indicate fire.
- Alarm signal
- Related: Supervisory signal, Trouble signal
A signal produced by an initiating device or system indicating a fire or other emergency condition requiring response.
- Trouble signal
- Related: Supervision, Alarm signal
A distinctive indication of a fault in system wiring, power, or components that could impair operation, annunciated audibly and visibly at the control unit.
- Annunciator
- Related: Zone, Addressable device
A remote or local display unit that identifies alarm, supervisory, and trouble conditions by zone or device label so responders can locate the event.
- Synchronization
- Related: Notification appliance circuit (NAC), Candela rating
Coordination of flash timing among strobes on the same circuit or system so simultaneous flashes do not create an unsafe composite flash rate.
- Candela rating
- Related: Synchronization, Audible/visible appliance
The measure of strobe light intensity; required rating increases with room size and mounting height to maintain effective warning visibility.
- Audible/visible appliance
- Related: Candela rating, Synchronization
A notification device combining a sounder and a strobe in one unit, mounted so both the sound level and the light output meet the applicable requirements.
- Voice evacuation system
- Related: Notification appliance circuit (NAC), Audible/visible appliance
An emergency communication arrangement using speakers and intelligible voice messages instead of, or in addition to, tone signals to direct occupants.
- Primary power supply
- Related: Secondary power supply, Battery calculation
The normal commercial or on-site source feeding the control unit, required to be dedicated and connected ahead of other loads so it is not casually switched off.
- Secondary power supply
- Related: Primary power supply, Battery calculation
The standby source, usually rechargeable batteries, that keeps the system operating for a specified time when primary power fails.
- Battery calculation
- Related: Secondary power supply, Voltage drop
The computation of standby and alarm current draws multiplied by required time durations, plus a recharge margin, to select an adequate battery capacity.
- Voltage drop
- Related: Battery calculation, Notification appliance circuit (NAC)
The loss of voltage along conductors caused by current flowing through wire resistance, which must be checked so devices at the end of a circuit still receive their listed minimum voltage.
- Surge protective device
- Related: Primary power supply, Supervision
A component that limits transient overvoltages on power or signal lines to protect control equipment, often required where the system interfaces with outside wiring.
- Ground fault
- Related: Trouble signal, Supervision
An unintended connection between a circuit conductor and ground, detected by the panel and annunciated as a trouble condition.
- Acceptance test
- Related: Inspection and testing, Record of completion
The documented verification, performed after installation and before the system is placed in service, that all devices, circuits, and functions operate as designed.
- Inspection and testing
- Related: Acceptance test, Record of completion
The recurring program of visual checks and functional tests at required intervals to confirm the system remains operational and code compliant.
- Record of completion
- Related: Acceptance test, Authority having jurisdiction (AHJ)
The form documenting the installed system, its components, and test results, provided to the owner and kept available for the authority having jurisdiction.
- Authority having jurisdiction (AHJ)
- Related: Permit, Record of completion
The organization or official responsible for approving plans, issuing permits, and enforcing the applicable fire and electrical codes for a project.
- Permit
- Related: Authority having jurisdiction (AHJ), Plan review
The written authorization required before installing or altering a fire alarm system, issued after plan review and subject to inspection before final approval.
- Plan review
- Related: Permit, Authority having jurisdiction (AHJ)
The AHJ's examination of submitted drawings and calculations to confirm the design meets adopted codes before installation begins.
- NEC Article 760
- Related: Class A circuit, Supervision
The National Electrical Code article governing fire alarm system wiring methods, conductor types, and installation requirements for power-limited and non-power-limited circuits.
- Oregon Fire Code
- Related: Authority having jurisdiction (AHJ), Permit
The fire code adopted in Oregon that incorporates national model fire code provisions with state amendments and governs fire alarm installation and maintenance requirements.