OR Fire Alarm Installer study materials
OR Fire Alarm Installer study resources

OR Fire Alarm Installer key terms

OR Fire Alarm Installer · Get comfortable with the vocabulary.

Addressable device

A field device that has its own unique digital identifier on the signaling line circuit, so the control unit can report and test it individually rather than reporting only a zone.

Related: Signaling line circuit (SLC), Zone
Conventional zone

A group of initiating devices wired on a single pair of conductors so the panel sees the group as one alarm location, not individual devices.

Related: Addressable device, Zone
Zone

A defined area or group of devices used to locate a fire or trouble condition and to organize annunciation, output logic, and response planning.

Related: Conventional zone, Annunciator
Initiating device circuit (IDC)

The wiring path connecting automatic detectors and manual stations to the control unit, monitored for alarm, open, and short conditions.

Related: Conventional zone, End-of-line resistor
Signaling line circuit (SLC)

The addressable data loop or spur that carries power and digital communication between the control unit and addressable devices such as detectors, modules, and isolators.

Related: Addressable device, Isolator module
Notification appliance circuit (NAC)

The power circuit that operates horns, strobes, speakers, and other alerting devices, typically supervised and arranged so a single fault does not disable all notification.

Related: End-of-line resistor, Synchronization
End-of-line resistor

A resistor installed at the far end of a supervised conventional circuit so the panel can detect opens, and detect shorts by the drop in normal current.

Related: Initiating device circuit (IDC), Supervision
Supervision

Continuous electrical monitoring of circuit integrity and component power so that a break, short, or loss of operating power produces a trouble signal at the control unit.

Related: End-of-line resistor, Trouble signal
Class A circuit

A supervised circuit that continues to function past a single open or ground fault because the outgoing and return paths are separate, allowing devices beyond the fault to still operate.

Related: Class B circuit, Supervision
Class B circuit

A supervised circuit that loses operation beyond a single open fault; the panel still detects the fault but devices past the break no longer function.

Related: Class A circuit, End-of-line resistor
Smoke detector spacing

The maximum listed spacing between detectors, commonly 30 feet on smooth ceilings, adjusted downward for ceiling height, beams, and airflow conditions.

Related: Spot-type smoke detector, Detector coverage area
Spot-type smoke detector

A detector that samples air at a localized point, using photoelectric light scatter or ionization sensing, as opposed to projecting a beam across a space.

Related: Smoke detector spacing, Projected beam detector
Projected beam detector

A smoke detector that spans a long distance with a transmitter and receiver, responding to smoke obscuration along the beam path; typically used in large open spaces.

Related: Spot-type smoke detector, Air-sampling detection
Air-sampling detection

A system that draws air from a protected area through a pipe network to a remote detector, used where point detectors are impractical or early warning is needed.

Related: Projected beam detector, Smoke detector spacing
Heat detector

A device that responds to fixed temperature, rate of temperature rise, or both; it is slower than smoke detection and used where smoke detectors are unsuitable.

Related: Spot-type smoke detector, Detector coverage area
Detector coverage area

The floor area assigned to one detector, derived from listed spacing and ceiling geometry, used to lay out detector locations on a plan.

Related: Smoke detector spacing, Heat detector
Manual fire alarm box

A manually operated initiating device, usually pull-station type, mounted along the means of egress at accessible height so occupants can trigger the alarm.

Related: Initiating device circuit (IDC), Zone
Waterflow switch

A device on a sprinkler system pipe that senses sustained water movement and sends an alarm signal, distinguishing real flow from pressure surges.

Related: Supervisory signal, Alarm signal
Supervisory signal

A signal indicating an off-normal condition in a suppression or control system, such as a closed valve or low air pressure, that does not yet indicate fire.

Related: Trouble signal, Alarm signal
Alarm signal

A signal produced by an initiating device or system indicating a fire or other emergency condition requiring response.

Related: Supervisory signal, Trouble signal
Trouble signal

A distinctive indication of a fault in system wiring, power, or components that could impair operation, annunciated audibly and visibly at the control unit.

Related: Supervision, Alarm signal
Annunciator

A remote or local display unit that identifies alarm, supervisory, and trouble conditions by zone or device label so responders can locate the event.

Related: Zone, Addressable device
Synchronization

Coordination of flash timing among strobes on the same circuit or system so simultaneous flashes do not create an unsafe composite flash rate.

Related: Notification appliance circuit (NAC), Candela rating
Candela rating

The measure of strobe light intensity; required rating increases with room size and mounting height to maintain effective warning visibility.

Related: Synchronization, Audible/visible appliance
Audible/visible appliance

A notification device combining a sounder and a strobe in one unit, mounted so both the sound level and the light output meet the applicable requirements.

Related: Candela rating, Synchronization
Voice evacuation system

An emergency communication arrangement using speakers and intelligible voice messages instead of, or in addition to, tone signals to direct occupants.

Related: Notification appliance circuit (NAC), Audible/visible appliance
Primary power supply

The normal commercial or on-site source feeding the control unit, required to be dedicated and connected ahead of other loads so it is not casually switched off.

Related: Secondary power supply, Battery calculation
Secondary power supply

The standby source, usually rechargeable batteries, that keeps the system operating for a specified time when primary power fails.

Related: Primary power supply, Battery calculation
Battery calculation

The computation of standby and alarm current draws multiplied by required time durations, plus a recharge margin, to select an adequate battery capacity.

Related: Secondary power supply, Voltage drop
Voltage drop

The loss of voltage along conductors caused by current flowing through wire resistance, which must be checked so devices at the end of a circuit still receive their listed minimum voltage.

Related: Battery calculation, Notification appliance circuit (NAC)
Surge protective device

A component that limits transient overvoltages on power or signal lines to protect control equipment, often required where the system interfaces with outside wiring.

Related: Primary power supply, Supervision
Ground fault

An unintended connection between a circuit conductor and ground, detected by the panel and annunciated as a trouble condition.

Related: Trouble signal, Supervision
Acceptance test

The documented verification, performed after installation and before the system is placed in service, that all devices, circuits, and functions operate as designed.

Related: Inspection and testing, Record of completion
Inspection and testing

The recurring program of visual checks and functional tests at required intervals to confirm the system remains operational and code compliant.

Related: Acceptance test, Record of completion
Record of completion

The form documenting the installed system, its components, and test results, provided to the owner and kept available for the authority having jurisdiction.

Related: Acceptance test, Authority having jurisdiction (AHJ)
Authority having jurisdiction (AHJ)

The organization or official responsible for approving plans, issuing permits, and enforcing the applicable fire and electrical codes for a project.

Related: Permit, Record of completion
Permit

The written authorization required before installing or altering a fire alarm system, issued after plan review and subject to inspection before final approval.

Related: Authority having jurisdiction (AHJ), Plan review
Plan review

The AHJ's examination of submitted drawings and calculations to confirm the design meets adopted codes before installation begins.

Related: Permit, Authority having jurisdiction (AHJ)
NEC Article 760

The National Electrical Code article governing fire alarm system wiring methods, conductor types, and installation requirements for power-limited and non-power-limited circuits.

Related: Class A circuit, Supervision
Oregon Fire Code

The fire code adopted in Oregon that incorporates national model fire code provisions with state amendments and governs fire alarm installation and maintenance requirements.

Related: Authority having jurisdiction (AHJ), Permit