OR Plumber study materials
OR Plumber study resources

OR Plumber flashcards

OR Plumber · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Water column pressure
One psi equals 2.31 feet of water head. This conversion lets a plumber convert static pressure to the height of water it can support in a system.
Fixture unit
A unitless measure of the probable drainage load a fixture imposes on a drainage system, roughly equivalent to one gallon per minute of flow.
Drainage pipe slope
Horizontal drainage pipe 3 inches and smaller must slope at least 1/4 inch per foot. Pipe 4 inches and larger may slope 1/8 inch per foot.
Type L copper
Standard-weight copper tube commonly used for above-ground water distribution. Type K is heavier and used underground; Type M is lighter and limited.
Trap seal depth
The water depth in a fixture trap must be at least 2 inches and no more than 4 inches to prevent sewer gas while allowing flow.
Air gap backflow protection
An unobstructed vertical distance between the water outlet and the flood level rim of the receiving fixture, providing the highest level of backflow protection.
Lavatory drain size
A lavatory requires a minimum 1-1/4 inch drain. A bathtub requires 1-1/2 inch, and a water closet requires 3 inch.
Pressure-balancing shower valve
A shower valve that maintains a stable outlet temperature by adjusting hot and cold flow when supply pressure changes, reducing scalding risk.
Minimum fixture pressure
Flush-tank water closets need about 8 psi static pressure at the fixture; flushometer valves typically need 15 psi or more.
Pressure-reducing valve
A device installed on a water service when static pressure exceeds 80 psi, reducing downstream pressure to a safe level for fixtures and piping.
RPZ assembly
A reduced-pressure-zone backflow preventer used for high-hazard cross-connections such as irrigation and boiler feed, providing the highest protection level.
Maximum water velocity
Cold water piping should not exceed about 8 feet per second and hot water about 5 feet per second to limit noise, erosion, and pressure loss.
Building drain
The lowest pipe of a drainage system that receives soil and waste inside the building, extending to the building sewer at or outside the foundation.
Wet vent
A vent that also serves as a drain for fixtures on the same floor, sized per code and connected to a dry vent above the highest fixture.
Trap arm length
The distance from a fixture trap weir to its vent connection, limited by code, commonly 5 feet for 1-1/4 inch and 6 feet for 1-1/2 inch traps.
Backwater valve
A device installed on a drainage line to prevent sewage from flowing backward into a building when the public sewer surcharges or floods.
Vent terminal height
A vent stack must extend at least 6 inches above the roof surface and be located at least 10 feet from operable windows or air intakes.
Cleanout spacing
Horizontal drainage lines require cleanouts at intervals not exceeding 100 feet and at each change of direction greater than 45 degrees.
Oregon Plumbing Specialty Code
The Oregon code governing plumbing installation, based on the Uniform Plumbing Code and administered by the Oregon Building Codes Division.
Plumber licensing
Oregon requires individual plumber licenses (apprentice, journeyman, master) and a separate plumbing contractor license for business operation.
Plumbing permit
Authorization from the local jurisdiction or state required before starting most plumbing work, including fixture replacement and water heater installation.
Concealed work inspection
An inspection that must be requested and passed before plumbing is covered by walls, floors, or ceilings, allowing verification of installation.
T&P relief discharge
The temperature-and-pressure relief valve on a water heater must discharge to within 6 inches of the floor or to a safe, visible location.
Water heater seismic strapping
Oregon requires water heaters to be secured with two straps, one in the upper third and one in the lower third, plus base anchoring.
Backflow tester certification
Oregon requires backflow assembly testers to hold current certification, and certain assemblies must be tested annually by a certified tester.
Building sewer definition
The pipe that carries sewage from the building drain to the public sewer or private disposal system, beginning outside the building foundation.
Flushometer valve pressure
A flushometer valve typically requires at least 15 psi flowing pressure at the fixture to operate correctly and reset the diaphragm.
Expansion tank
A closed tank installed on a water heating system to absorb the volume increase from thermal expansion and protect piping and relief valves.
Water closet clearance
A water closet must have at least 15 inches from its centerline to a side wall and at least 21 inches of clear space in front.
Trap primer
A device that automatically adds water to a floor drain trap to maintain the trap seal and prevent sewer gas from entering the building.
Developed length
The total equivalent pipe length including straight run plus fitting allowances, used to size water supply piping for allowable pressure loss.
Stack vent
The extension of a soil or waste stack above the highest fixture branch, serving as a vent to the outdoors.