PE Control Systems flashcards
PE Control Systems · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- 4-20 mA live zero
- In a 4-20 mA loop, 4 mA represents 0 % of span and 20 mA represents 100 %; a 0 mA reading indicates a broken wire or lost loop power.
- Orifice flow equation
- For a differential-pressure flow element, volumetric flow is proportional to the square root of differential pressure, so the transmitter or control system applies square-root extraction to linearize the signal.
- Pt100 RTD
- A platinum resistance thermometer with 100 ohms at 0 degC and a temperature coefficient near 0.00385 ohm/ohm/degC, chosen where accuracy and long-term stability exceed thermocouple capability.
- Cold junction compensation
- Thermocouples measure only the difference between hot and reference junction voltages, so the reference junction temperature must be measured and compensated to obtain an accurate absolute temperature.
- Coriolis mass flowmeter
- A Coriolis meter measures mass flow directly from the phase shift of vibrating tubes and also reports fluid density, typically with 0.1 to 0.2 percent of rate accuracy.
- Magnetic flowmeter limitation
- Magnetic flowmeters require a conductive liquid, generally above 5 microsiemens per centimeter, and a full pipe; they cannot measure hydrocarbons, gases, or other non-conductive fluids.
- Gauge versus absolute pressure
- Gauge pressure is referenced to local atmospheric pressure while absolute pressure is referenced to perfect vacuum; psia equals psig plus atmospheric pressure, about 14.7 psi at sea level.
- Ideal PID equation
- Controller output equals Kc times the sum of error, the integral of error divided by Ti, and derivative time Td times the derivative of error.
- Ziegler-Nichols ultimate gain tuning
- From the ultimate gain Ku and ultimate period Pu at which the loop cycles continuously, PID settings are Kc = 0.6 Ku, Ti = Pu/2, and Td = Pu/8.
- Damping ratio and overshoot
- For a second-order loop, fractional overshoot equals exp(-pi zeta / sqrt(1 - zeta squared)); a damping ratio of 0.5 gives roughly 16 percent overshoot.
- IMC lambda tuning
- For a first-order-plus-dead-time process, internal model control sets controller gain Kc = tau / (K (lambda + theta)) and integral time Ti = tau, where lambda is the chosen closed-loop time constant.
- Gain margin
- Gain margin is the amount in decibels by which loop gain may increase at the 180 degree phase crossover before instability; a minimum of about 6 dB is commonly targeted.
- Cascade secondary loop speed
- In cascade control the inner secondary loop should be at least three to five times faster than the outer primary loop so the primary controller sees nearly instantaneous correction.
- Integral windup
- When controller output saturates while error persists, the integral term keeps accumulating; anti-windup logic stops or limits integration to prevent large overshoot when the loop recovers.
- Valve flow coefficient Cv
- Cv is the number of gallons per minute of 60 degF water that flows through a wide-open valve with a pressure drop of one psi across it.
- Equal percentage valve characteristic
- With equal-percentage trim, each equal increment of stem travel changes flow by a constant percentage of current flow, producing a nearly linear installed characteristic when valve pressure drop falls with increasing flow.
- Air-to-open actuator
- An air-to-open actuator with spring return closes the valve when air supply is lost, so it is specified wherever the process safe state requires the valve to be shut.
- Cavitation in control valves
- Cavitation occurs when vena contracta pressure falls below vapor pressure and bubbles then collapse downstream, causing noise, vibration and trim damage; flashing occurs when downstream pressure stays below vapor pressure.
- Valve positioner
- A positioner compares the controller signal with actual stem position and adjusts actuator air accordingly, overcoming packing friction and unbalanced forces to reduce hysteresis and improve accuracy.
- Valve rangeability
- Rangeability is the ratio of maximum to minimum controllable flow through a valve, typically about 30:1 to 50:1 for globe valves before installed performance degrades.
- Three-element drum level control
- Boiler drum level control that trims feedwater using drum level feedback, steam flow feedforward, and a feedwater flow inner loop, compensating for shrink and swell during load changes.
- Compressor anti-surge control
- Anti-surge control opens a recycle valve when compressor flow approaches the surge line, maintaining flow above the minimum needed to prevent damaging flow reversal.
- pH control nonlinearity
- The pH titration curve is extremely steep near neutrality, so a fixed PID gain becomes unstable; gain scheduling or adaptive control based on the measured slope is used instead.
- Fuel-air cross-limiting
- In fired heater control, cross-limiting increases air flow before fuel on load increases and cuts fuel before air on load decreases, keeping the mixture below flammable limits during upsets.
- Column tray temperature control
- Distillation composition is often inferred from a tray temperature and controlled by manipulating reflux flow or reboiler steam, because online analyzers are slow and expensive to maintain.
- Selective auctioneering control
- A selector passes the highest or lowest of several controller outputs, for example overriding on compressor suction pressure or protecting a pump near the end of its curve.
- ISA instrument tag letters
- On a P&ID the first letter gives the measured variable, such as F flow, T temperature, P pressure or L level, and later letters give the function, such as transmitter, controller or valve.
- SIL 2 PFD range
- Safety integrity level 2 corresponds to an average probability of failure on demand between 10^-3 and 10^-2 for a low-demand safety instrumented function.
- 1oo1 PFDavg formula
- For a single one-out-of-one channel, average probability of failure on demand is approximately lambda_DU times TI divided by 2, where lambda_DU is undetected dangerous failure rate and TI the proof-test interval.
- Class I Division 1
- A hazardous location classification for areas where flammable gases or vapors are present during normal operation, requiring explosion-proof or intrinsically safe equipment and wiring methods.
- Intrinsic safety barrier
- An intrinsic safety barrier uses zener diodes and current-limiting resistors to limit energy entering a hazardous area so no spark or hot surface can ignite the atmosphere, even under fault conditions.
- SIS independence from BPCS
- A safety instrumented system must be functionally separate from the basic process control system, with its own sensors, logic solver and final elements, to satisfy IEC 61511 requirements.