PE Control Systems key terms
PE Control Systems · Get comfortable with the vocabulary.
- Accuracy
- Related: Repeatability, Calibration
How close a measured value is to the true value of the variable, usually stated as a percentage of span or of reading over a stated range.
- Repeatability
- Related: Accuracy, Hysteresis
How closely an instrument gives the same output when the same input is applied again and again under identical conditions, approached the same way each time.
- Hysteresis
- Related: Repeatability, Calibration
The difference in an instrument's output when the same input value is reached from increasing versus decreasing directions, caused by friction, backlash, or elastic effects in the movement.
- Span
- Related: Calibration, Accuracy
The algebraic difference between the upper and lower range values of an instrument; it is the width of measurement range that the output signal represents.
- 4-20 mA current loop
- Related: Span
An analog signaling standard where 4 mA represents the zero or live-zero value and 20 mA represents full scale; current signaling resists voltage loss in long wires.
- Orifice plate
- Related: 4-20 mA current loop, Span
A differential-pressure flow element made of a flat plate with a machined bore clamped between pipe flanges; measured pressure drop relates to flow by a square-root relationship.
- RTD
- Related: Calibration, Accuracy
A resistance temperature detector, usually platinum, whose electrical resistance rises predictably as temperature increases, giving accurate and stable measurement over a wide span.
- Calibration
- Related: Span, Hysteresis
Comparing an instrument's indication with a traceable reference standard and adjusting its zero and span so the output correctly matches known input values, with results documented.
- PID controller
- Related: Proportional band, Integral windup
A feedback algorithm whose output combines proportional action on current error, integral action on accumulated error, and derivative action on the rate of error change.
- Proportional band
- Related: PID controller, Ultimate gain
The error, expressed as a percentage of measurement span, required to drive the controller output through its full range; it is the reciprocal of proportional gain.
- Integral windup
- Related: PID controller, Proportional band
The unwanted buildup of the integral term while a controller output sits saturated at a limit, which causes overshoot and slow recovery once the process returns to range.
- Derivative kick
- Related: PID controller, Dead time
A sharp controller output spike produced by derivative action when the setpoint is stepped; it is normally avoided by taking the derivative on measurement rather than error.
- Dead time
- Related: Ultimate gain, PID controller
The interval between a change in controller output and the first detectable response of the process variable, caused by transport delays or slow analysis.
- Cascade control
- Related: PID controller, Feedforward control
A structure in which the output of a primary controller becomes the setpoint of a faster secondary controller, so disturbances inside the inner loop are corrected before they upset the main variable.
- Feedforward control
- Related: Cascade control, Dead time
Control action taken on a measured disturbance before the controlled variable moves, using a process model; it is usually combined with feedback to correct the remaining error.
- Split-range control
- Related: PID controller, Air-to-open valve
Dividing a single controller output between two or more final elements so each strokes over its own portion of the signal range, such as separate heating and cooling valves.
- Ultimate gain
- Related: Proportional band, Dead time
The controller gain at which a closed loop cycles continuously with integral and derivative action removed; paired with the ultimate period, it sets Ziegler-Nichols tuning constants.
- Control valve
- Related: Valve positioner, Valve flow coefficient
The final control element that throttles fluid flow in response to a controller output signal, regulating the process variable by changing the open area of the flow path.
- Valve flow coefficient
- Related: Control valve, Equal percentage characteristic
A capacity number equal to the gallons per minute of water at 60 degrees Fahrenheit that a valve passes with a one psi pressure drop across it.
- Equal percentage characteristic
- Related: Installed characteristic, Control valve
A trim characteristic in which equal increments of stem travel produce equal percentage changes in flow, which compensates for pressure drop that falls as flow increases.
- Installed characteristic
- Related: Equal percentage characteristic, Control valve
The actual flow-versus-travel relationship a valve shows in service, differing from the inherent curve because of piping losses, fittings, and changing pressure drop across the valve.
- Valve positioner
- Related: Control valve, Air-to-open valve
A device that senses stem position and adjusts air to the actuator so the valve follows the controller signal, overcoming friction and improving response on large or high-pressure valves.
- Air-to-open valve
- Related: Valve positioner, Control valve
A valve that strokes open as air pressure rises and springs closed when air fails, also called fail-closed; its failure direction is chosen to protect the process.
- Cavitation
- Related: Control valve, Valve flow coefficient
Formation and collapse of vapor bubbles in liquid passing through a valve's narrowest point, producing noise, erosion, and reduced capacity as pressure recovers downstream.
- Safety instrumented function
- Related: Safety integrity level, Cause and effect matrix
An independent protective action performed by a safety instrumented system that moves the process to a safe state when a defined hazardous condition is detected.
- Safety integrity level
- Related: Safety instrumented function, LOPA
A discrete rating from one to four assigned to a safety function according to its required risk reduction and allowable probability of failure on demand.
- Three-element drum level control
- Related: Cascade control, Feedforward control
Boiler feedwater control that combines drum level, steam flow, and feedwater flow signals, letting level be held steady while the loop responds quickly to load changes.
- Compressor surge control
- Related: Split-range control, PID controller
Protection that recycles or vents flow to keep a compressor's throughput above its surge limit, preventing flow reversal and damage during low demand or high pressure ratio.
- Distributed control system
- Related: SCADA, Piping and instrumentation diagram
A networked plant platform of controllers and operator stations that share data while keeping individual control loops running locally, even if higher levels fail.
- SCADA
- Related: Distributed control system, Piping and instrumentation diagram
Supervisory control and data acquisition: a system that collects field data and issues supervisory commands over a wide area, often through remote terminal units and telemetry.
- Alarm rationalization
- Related: Distributed control system, HAZOP
A structured review that sets each alarm's limit, priority, and operator response and removes nuisance or duplicate alarms so the board highlights what truly needs action.
- Piping and instrumentation diagram
- Related: Cause and effect matrix, HAZOP
A drawing that shows process equipment, piping, instruments, and control loops using standardized symbols and tag numbers, serving design, construction, and maintenance work.
- HAZOP
- Related: LOPA, Management of change
Hazard and operability study: a team review that applies guide words to process parameters at defined nodes to find deviations, their causes, and their consequences.
- LOPA
- Related: HAZOP, Safety integrity level
Layer of protection analysis: a semi-quantitative method comparing the frequency of an initiating event with credited independent protection layers against a tolerable risk target.
- Intrinsic safety
- Related: Area classification
A protection method that limits voltage and current in hazardous-area circuits using barriers or galvanic isolators, so sparks and surface temperatures cannot ignite the atmosphere.
- Area classification
- Related: Intrinsic safety
The division of plant areas into zones or divisions by how often and how long flammable gas or dust may be present, which controls the equipment approvals allowed there.
- Management of change
- Related: HAZOP, Piping and instrumentation diagram
A formal process that reviews and approves modifications to equipment, chemicals, or procedures before they are made, confirming hazards and documents stay current.
- Cause and effect matrix
- Related: Safety instrumented function, Piping and instrumentation diagram
A chart with trip causes listed as rows and output actions as columns, documenting exactly how the safety system responds to each initiating event.