- Spill bucket capacity
- A spill bucket must be liquid-tight and hold at least 5 gallons at the fill pipe. It catches product spilled during delivery and must be tested for tightness at installation and on the state-required schedule.
- Overfill ball-float valve
- A drop-tube overfill device that floats and closes the fill path when product reaches about 90% of tank capacity. It must be inspected and tested per the manufacturer's instructions.
- 0.1 gph leak rate
- The standard leak detection threshold for USTs and piping. ATG and tightness tests must detect a 0.1 gallon-per-hour leak with 95% probability of detection and 5% false alarm rate.
- 3.0 gph line test
- An annual line leak detector test that verifies the detector can identify a 3.0 gallon-per-hour leak. It is one of the accepted line leak detection methods under 40 CFR 280.43.
- Interstitial monitoring
- Monitoring the space between the primary and secondary containment of a tank or pipe. A liquid sensor or vacuum/pressure monitor detects product in the annular space and triggers an alarm.
- Inventory variance rule
- Manual inventory control compares stick readings with dispensed volume. A variance greater than 1% of throughput plus 130 gallons triggers an investigation for a possible release.
- SIR leak detection
- Statistical Inventory Reconciliation analyzes inventory and dispensing data to detect a 0.1 gph leak. The method must be site-specific and validated by the vendor or state.
- ATG quiet period
- Automatic tank gauging tests must run when no product is being dispensed, so tank level changes reflect only leaks. Dispensing during a test invalidates the result.
- Sump hydrostatic test
- Fill the sump with water above the highest expected liquid level, mark the level, and observe for the specified hold time. A drop or visible leak indicates a failed sump.
- Sump sensor placement
- The liquid sensor must sit at the lowest point of the sump so it detects small accumulations. A sensor set too high misses leaks and defeats secondary containment monitoring.
- Sump penetration boot
- A flexible seal where piping or conduit enters a sump wall. It must be sealed liquid-tight; an unsealed boot lets product escape secondary containment and is a common finding.
- Piping bend radius
- The minimum radius a flexible pipe can bend without kinking. Exceeding it causes permeability failures and is a common inspection reject. Always follow the manufacturer's limit.
- Line slope to tank
- Pressurized supply lines should slope back to the tank or sump so product drains and line leak detection works. Vapor recovery lines slope toward the tank or riser.
- Fusion pipe joint
- A heat-fused joint for HDPE or FRP piping that is stronger than the pipe itself. Fusion requires the correct temperature, pressure, and cooling time per the manufacturer's spec.
- Secondary-contained piping
- Double-wall piping with an interstitial space that must be monitored. A liquid sensor in the sump or vacuum/pressure monitoring detects a leak in the primary pipe.
- Cathodic protection reading
- A structure-to-soil potential of at least -850 mV (Cu/CuSO4) indicates adequate cathodic protection for steel tanks and piping. Record readings at each test station.
- Tank bedding and backfill
- Place specified bedding and backfill in lifts, keep heavy equipment off the tank, and use hold-down straps in high-water areas. Backfill per the drawings and manufacturer's instructions.
- Piping pressure test
- Test piping at the manufacturer's pressure and hold time before backfill. Record gauge readings, ambient temperature, and duration; a failed test means repair and retest.
- Tank tightness test
- A test that detects a 0.1 gph leak, conducted after installation and before product is introduced. Results are recorded and retained for at least 3 years.
- As-built records
- Documentation of tank and piping locations, depths, materials, and test results. Keep as-builts for the life of the system plus the required retention period.
- Confined space entry
- Sump and tank entry requires a permit, atmospheric testing, an attendant, and a rescue plan under OSHA 29 CFR 1910.146. Fuel vapors are heavier than air and collect at the bottom.
- Gasoline LEL
- The lower explosive limit for gasoline vapor is about 1.4% by volume in air. Meter the atmosphere before entry and bond/ground equipment before any transfer.
- Release reporting timeline
- A suspected release must be reported within 24 hours under 40 CFR 280.50. Spills and overfills with no free product and no contamination may be logged and investigated per 280.53.
- Corrosion protection options
- Coated-and-cathodically-protected steel, STI-P3 type tanks, fiberglass-reinforced plastic, or cathodic protection with sacrificial anodes or impressed current. Required on new and replaced USTs.
- Vent line requirements
- Vent lines must be unobstructed, slope back to the tank, and have a pressure/vacuum vent or vent cap. A blocked vent causes tank pressure and dispenser shutdowns.
- Drop tube depth
- The drop tube should reach within about 6 inches of the tank bottom. A short drop tube causes turbulence and static during delivery and can damage the tank.
- Manway torque spec
- Manway, gasket, and bung bolts must be torqued to the manufacturer's specification. Over-torquing cracks composite tanks; under-torquing causes leaks at the fitting.
- Working tank capacity
- Working capacity is about 90% of tank volume, the level at which overfill protection stops flow. Some systems set the overfill alarm at 95% of capacity.
- STI-P3 tank
- A steel tank with a dielectric coating, sacrificial anodes, and a test station. Anode readings and coating condition must be checked at each inspection to confirm protection.
- Spill bucket drain valve
- The valve that drains the spill bucket into the tank. It must be closed during delivery and opened only after the bucket is emptied; a stuck-open valve bypasses containment.
- Sensor alarm response
- A sensor alarm must be investigated and logged. Verify the alarm and normal conditions with the manufacturer's test method and record the date, tester, and result.
- Stage II vapor recovery
- A system that captures displaced vapors at the dispenser and returns them to the tank. Lines must be liquid-tight and tested; a liquid trap causes tank pressure and shutdowns.