PEI Class 7 Test: Containment Sumps and Spill Buckets

PEI Class 7 Test · Work through your exam, one topic at a time.

All guide sections

Containment Sumps and Spill Buckets

What this domain covers

Sumps and spill buckets are the small containers that catch what drips and drains. The exam tests whether you can tell a liquid-tight container from a wet one, and whether you know the testing clock.

Core rules and concepts

  • Sumps appear at the tank top (containing fill, vent, gauge, and pump fittings), at piping transitions, and under dispensers. They must be liquid-tight, structurally sound, and kept free of liquid and debris.
  • Containment sumps used for interstitial monitoring of piping must be tested for integrity at least every three years under 40 CFR 280.35; PEI RP1200 describes accepted test methods. Double-wall sumps with interstitial monitoring may follow the 30-day monitoring alternative.
  • Spill buckets sit at the fill connection and are sized to hold the volume that drains from the delivery hose, commonly about 5 gallons. They either drain back to the tank through a fitting or must be emptied by hand after delivery.
  • Water is the enemy: it hides a leak, corrodes fittings, and can freeze and crack boots. Never use a sump as a floor drain or a disposal point.

Worked example

A spill bucket is filled with water to a marked level for its integrity test. After the RP1200 or manufacturer-specified observation period the level has dropped noticeably and water is seeping at the fill-pipe boot. Result: the bucket fails. The correct response is to repair or replace the boot or bucket and retest - not to pump the water out and record a pass.

Traps that cost marks

  • Pumping a wet sump dry and calling it repaired.
  • Letting the three-year test date slide because no one tracks it.
  • Testing a bucket packed with debris that masks a seam leak.
  • Discharging sump water to a storm drain without treatment.