PEI Class 7 Test study materials
PEI Class 7 Test study resources

PEI Class 7 Test: Tanks and Tank Appurtenances

PEI Class 7 Test · Work through your exam, one topic at a time.

All guide sections

Tanks and Tank Appurtenances

What this domain covers

This domain covers the tank itself and the fittings that make it work: fill, vent, gauge, monitor, pump, overfill prevention, and corrosion protection.

Core rules and concepts

  • Tank construction: fiberglass, coated or clad steel, or steel with cathodic protection (galvanic or impressed current). New and replaced tanks are secondarily contained with interstitial monitoring.
  • Cathodic protection must be tested within six months of installation and at least every three years; impressed-current rectifiers are checked on a short cycle, commonly every 60 days, and the readings recorded.
  • Overfill prevention must alert at 90% of capacity and stop flow at 95%. Automatic tank gauging, flappers, and ball float valves are the familiar devices; confirm which are acceptable locally before installing one.
  • A fill pipe needs a spill bucket, a striker plate protects the tank bottom if a gauging stick is dropped, and the vent must be sized and piped per NFPA 30 or 30A and the manufacturer's instructions.

Worked example

A 10,000-gallon tank has its ATG high-level alarm set at 9,200 gallons. That is 92% - too late. The correct setting warns at 90% (9,000 gallons) and the 95% (9,500 gallons) device stops the delivery. Setting only one point means either no warning or no shutdown.

Traps that cost marks

  • Setting overfill at a single point instead of 90% and 95%.
  • Treating cathodic protection as maintenance-free.
  • Forgetting buoyancy and anchoring where groundwater is high.
  • Recording rectifier readings without acting on an out-of-range value.