Pump Circuit: Calculated vs. Measured Voltage Drop

RME Board Exam · Put your knowledge to work in context.

All case studies

Pump Circuit: Calculated vs. Measured Voltage Drop

A 1.5 kW, 230 V single-phase centrifugal pump serves a hillside reservoir. Its controller sits at the end of a 75 m cable run from the service panel, fed with 3.5 mm² THHN copper in PVC conduit. Nameplate current is 7.7 A. With the pump running, the technician measures 232 V line-to-neutral at the panel and 208 V at the controller terminals. The pump runs hot, starts sluggishly, and the owner has already replaced two start capacitors in eight months. The motor itself was megger-tested and is sound. The conduit contains only the two circuit conductors and the equipment grounding conductor, and no other loads are connected to the circuit.

1. Is the 24 V drop explained by the conductor length and size? Show the calculation.

Read the worked answer

No - the conductor accounts for only about a quarter of it.

Take 3.5 mm² copper at roughly 5.3 Ω/km at operating temperature:

  • V_drop = 2 × I × L × R (factor 2 for the outgoing and return path)
  • V_drop = 2 × 7.7 A × 0.075 km × 5.3 Ω/km ≈ 6.1 V (about 2.6 % of 230 V)

So the cable run should cost you ~6 V, and the measured drop is 24 V. Roughly 18 V of the drop is unaccounted for by conductor resistance, which means it is being dropped somewhere that is not a 75 m length of 3.5 mm² copper.

2. What does the discrepancy indicate physically, and what is the immediate risk?

Read the worked answer

Convert the drop into loop resistance and compare:

  • Measured: 24 V ÷ 7.7 A ≈ 3.1 Ω of loop resistance
  • Expected from the cable: 2 × 0.075 × 5.3 ≈ 0.8 Ω
  • Excess: about 2.3 Ω concentrated at one or more points

That much resistance in a joint dissipates P = I²R ≈ (7.7)² × 2.3 ≈ 135 W in a spot the size of a thumb. A loose terminal screw, a corroded splice, an oxidized aluminium-to-copper connection, or a back-stabbed device will do this. The joint heats, carbonizes, resistance climbs further, and the failure accelerates - a classic fire initiator inside a controller or junction box. Note also that a low-voltage megger or continuity test will usually pass, because the defect only shows up under load.

The sluggish starting is a separate symptom of the same resistance: at roughly 6× FLA inrush (≈46 A) the same 2.3 Ω would collapse the terminal voltage far below the ~195 V the cable alone would give, which is why capacitors keep failing.

3. What sequence of checks and what repair would you specify?

Read the worked answer
  1. Load the circuit and measure successively - panel terminals, any junction boxes, the controller line terminals, the disconnect. The point where the voltage takes a big step is the defect.
  2. Thermograph or feel every termination immediately after a loaded run; the hot joint identifies itself.
  3. Re-terminate with correct torque, replace back-stabbed or wire-nut splices with listed connectors, and separate dissimilar metals with listed connectors.
  4. Re-measure after repair and confirm the loaded drop is back near the calculated ~6 V.
  5. Revisit the design. At 7.7 A running the 3.5 mm² is adequate, but on starting the drop is marginal at 75 m. If the pump is critical, upsize the run (5.5 mm² roughly halves the drop) rather than accept repeated capacitor failures. Do not simply increase the breaker - that addresses none of the above.