  • Ohm's law: V = I × R. Power: P = V × I = I²R = V²/R. Any two known quantities determine the other two.

  • Series circuit: same current through all elements; RT = R1 + R2 + R3 + …; source voltage divides in proportion to resistance.

  • Parallel circuit: same voltage across all branches; 1/RT = 1/R1 + 1/R2 + …; for two resistors RT = R1R2/(R1 + R2), always less than the smallest branch.

  • Two-branch current divider: I1 = IT × R2/(R1 + R2); series voltage divider: Vx = VT × Rx/RT.

  • DC resistance from dimensions: R = ρL/A. Copper resistivity ≈ 1.72 × 10⁻⁸ Ω·m at 20 °C; resistance rises with temperature for metals.

  • AC quantities: Z = √(R² + (XL − XC)²); XL = 2πfL; XC = 1/(2πfC); sine-wave RMS = 0.707 × peak; series resonance at f = 1/(2π√(LC)).

  • Power forms: single-phase P = V × I × cos θ; balanced three-phase P = √3 × VL × IL × cos θ; apparent power S = V × I; reactive power Q = V × I × sin θ; PF = P/S = cos θ.

  • Machine and energy relations: 1 hp = 746 W; efficiency η = Pout/Pin; ideal transformer V1/V2 = N1/N2 = I2/I1; energy in kWh = kW × hours.

Quick reference

Philippine Electrical Code

  • The PEC is the Philippine adaptation of NFPA 70 (National Electrical Code) with local amendments; Philippine supply is 60 Hz, nominally 230 V line-to-neutral and 400 V three-phase.

  • Small-conductor overcurrent limits: 15 A for 14 AWG copper, 20 A for 12 AWG, 30 A for 10 AWG, unless a specific article permits otherwise.

  • Continuous loads: overcurrent device rating ≥ 125% of continuous current plus 100% of noncontinuous current, selected from the standard rating list (15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100 A …).

  • Voltage drop: maximum 3% on a branch circuit and 5% total for feeder plus branch circuit, measured at the load.

  • Working space in front of live equipment: depth 600 mm (Condition 1), 900 mm (Condition 2), 1000 mm (Condition 3); height 2.0 m; width 762 mm.

  • Dwelling receptacle spacing: no point on the floor line may be more than 600 mm from a receptacle; any wall space 600 mm or wider needs a receptacle; kitchen countertops follow the same 600 mm rule.

  • GFCI protection is required for receptacles in bathrooms, garages, outdoors, kitchens, laundry areas, basements, crawl spaces, and within reach of sinks.

  • Raceway and box limits: conduit fill is 53% (1 conductor), 31% (2), 40% (3 or more); box fill counts 2.0 in³ per 14 AWG, 2.25 in³ per 12 AWG, 2.5 in³ per 10 AWG.

  • Grounding: a rod electrode is at least 2.44 m long and 16 mm diameter; a single rod must be supplemented unless its earth resistance is 25 Ω or less; equipment grounding conductors are sized from the overcurrent device rating.