RME Board Exam flashcards
RME Board Exam · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ohm's law
- Current through a conductor is directly proportional to voltage and inversely proportional to resistance, written V = I × R; it gives any one quantity when the other two are known.
- Electric power formula
- Power in a DC or purely resistive circuit equals voltage times current, P = V × I, and can also be written P = I²R or P = V²/R.
- Series circuit resistance
- In a series circuit the same current flows through every element and total resistance is the sum RT = R1 + R2 + R3 + …, so adding loads reduces current.
- Parallel circuit resistance
- In a parallel circuit voltage is equal across branches and the reciprocal of total resistance is the sum of reciprocals, 1/RT = 1/R1 + 1/R2 + …, giving a total below the smallest branch.
- Kirchhoff's current law
- At any junction the total current entering equals the total current leaving; the algebraic sum of currents at a node is zero.
- Kirchhoff's voltage law
- Around any closed loop the algebraic sum of all voltage rises and drops is zero, so source voltage equals the sum of the series voltage drops.
- RMS value of sine wave
- The root-mean-square value is 0.707 times the peak value of a sine wave; it is the effective value producing the same heating as an equal DC value.
- Inductive reactance
- Inductive reactance opposes alternating current and rises with frequency and inductance, XL = 2πfL, measured in ohms; it is zero at DC.
- Capacitive reactance
- Capacitive reactance opposes alternating current and falls as frequency or capacitance increases, XC = 1/(2πfC) in ohms; it is infinite at DC.
- Series RLC impedance
- Impedance is the vector sum of resistance and net reactance, Z = √(R² + (XL − XC)²) in ohms, and current equals voltage divided by Z.
- Power factor
- Power factor is the ratio of real power in watts to apparent power in volt-amperes, PF = cos θ = P/(V × I); it equals 1.0 for purely resistive loads.
- Balanced three-phase power
- Real power in a balanced three-phase system equals √3 times line voltage times line current times power factor, P = √3 × VL × IL × cos θ.
- Transformer turns ratio
- The voltage ratio equals the turns ratio and the inverse of the current ratio, V1/V2 = N1/N2 = I2/I1; ideal transformer input power equals output power.
- One horsepower in watts
- One mechanical horsepower equals 746 watts; motor input power in watts is output horsepower times 746 divided by efficiency.
- Conductor resistance from dimensions
- Resistance equals resistivity times length divided by cross-sectional area, R = ρL/A, so longer or thinner conductors have proportionally higher resistance.
- Kilowatt-hour energy
- Energy in kilowatt-hours equals power in kilowatts multiplied by time in hours; a 2 kW load running 3 hours consumes 6 kWh.
- PEC code basis
- The Philippine Electrical Code is the Philippine adaptation of NFPA 70, the National Electrical Code, with local amendments; Philippine supply is 60 Hz, nominally 230 V line-to-neutral and 400 V three-phase.
- Small conductor overcurrent limits
- Unless a specific article permits otherwise, overcurrent devices must not exceed 15 A for 14 AWG copper, 20 A for 12 AWG, and 30 A for 10 AWG conductors.
- Continuous load overcurrent sizing
- The overcurrent device must be at least 125% of the continuous load current plus 100% of the noncontinuous load current, using the next standard rating.
- Voltage drop limits
- Branch-circuit conductors are sized so drop does not exceed 3% of supply voltage, and feeder plus branch drop does not exceed 5% at the load.
- Working space depth
- Clear depth in front of live equipment is 600 mm for Condition 1, 900 mm for Condition 2, and 1000 mm for Condition 3, with 2.0 m headroom.
- Dwelling receptacle spacing rule
- In dwelling units no point along the floor line of a wall space may be more than 600 mm from a receptacle outlet, and wall spaces 600 mm or wider require one.
- GFCI required locations
- Ground-fault circuit-interrupter protection is required for receptacles in bathrooms, garages, outdoors, kitchens, laundry areas, basements, crawl spaces, and near sinks.
- Conduit fill percentages
- Raceway fill limits are 53% for one conductor, 31% for two conductors, and 40% for three or more conductors, taken from the Chapter 9 tables.
- Box fill per conductor
- Each 14 AWG conductor counts 2.0 cubic inches, 12 AWG counts 2.25, and 10 AWG counts 2.5; clamps, devices, and grounding conductors add allowances.
- Ground rod minimum size
- A rod-type grounding electrode must be at least 2.44 m (8 ft) long and 16 mm (5/8 in) in diameter, and must be driven to full depth.
- Supplemental grounding electrode rule
- A single rod, pipe, or plate electrode must be supplemented by an additional electrode unless it demonstrates 25 ohms or less resistance to earth.
- Standard overcurrent device ratings
- Standard fuse and breaker ratings include 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, and 200 amperes.
- Service disconnect location
- The service disconnecting means must be at a readily accessible location, installed outside the building or inside nearest the point of entry of the service conductors.
- Ampacity table application
- Conductor ampacity is taken from Table 310.16, then corrected for ambient temperature and adjusted for more than three current-carrying conductors in a raceway or cable.
- Residential branch circuit burial depth
- Residential branch circuits of 120 V or less and 20 A or less with GFCI protection need 450 mm (18 in) burial; other direct-buried cables require 600 mm (24 in).
- Equipment grounding conductor sizing
- The equipment grounding conductor is sized from Table 250.122 using the rating of the overcurrent device protecting the circuit, not the circuit conductor ampacity.