Plumbing Code and Standards

  • The National Plumbing Code of the Philippines (NPCP) is the reference code for the MPLE; R.A. 1378 (Plumbing Law) gives the code its legal force and created the Board of Master Plumbers.

  • Fixture unit (FU) values: water closet (tank type) = 3 FU; lavatory = 1 FU; bathtub = 2 FU; shower head = 2 FU; kitchen sink = 2 FU; floor drain = 2 FU; urinal (flush valve) = 5 FU.

  • Minimum trap arm length rule: the developed length of a trap arm must be at least 2 times the trap arm diameter, and the fall must not exceed one pipe diameter to prevent siphonage.

  • Vent stack sizing depends on the total fixture units served and the stack length; a 1-1/2 in vent serves up to 8 FU at 1 in stack length, but larger FU loads require 2 in or more.

  • Soil pipe carries sewage (water closets, urinals); waste pipe carries non-fecal liquid waste (sinks, lavatories); a combined drain carries both and must be sized for the total FU.

  • Cleanout requirements: a cleanout is required at the base of each soil/waste stack, at the upper end of each horizontal drain, and at intervals not exceeding 15 m (50 ft) in horizontal runs.

  • Water supply sizing uses the fixture unit method with the Hunter curve: convert FU to probable demand in gpm, then select pipe diameter from velocity limits (typically 1.2-2.4 m/s or 4-8 fps).

  • Backflow protection: an air gap (minimum 2 times the effective opening, not less than 1 in) is the only acceptable protection for high-hazard connections; a reduced-pressure-zone (RPZ) assembly protects against both backpressure and backsiphonage.

Quick reference

Plumbing System Design and Installation

  • Minimum fixture drain/trap size: lavatory 1-1/4 in (1-1/2 in in some codes), kitchen sink 1-1/2 in, water closet 3 in, floor drain 2 in; the trap must be the same size as the fixture drain.

  • Slope requirements: 3 in and smaller horizontal drainage pipe slope at 1/4 in per foot; 4 in and larger slope at 1/8 in per foot; no drainage pipe may slope less than 1/8 in per foot.

  • Water service and building supply: minimum size 3/4 in for a single-family dwelling; pressure at fixtures must be at least 8 psi (residual) and not exceed 80 psi unless a pressure-reducing valve is installed.

  • Vent termination: vent must extend at least 6 in above the roof, be at least 3 ft from any window or air intake, and be at least 10 ft from a property line or adjoining building.

  • A water closet must be installed on a drain of at least 3 in diameter; the closet bend is 3 in and the stack must be at least 3 in to carry the 3 FU closet.

  • Interceptors: grease interceptors are required for commercial kitchens and must be sized by the fixture flow and grease retention capacity; oil/sand interceptors are required for garages and service stations.

  • Water heater relief valve: a temperature-pressure (T&P) relief valve is required, piped full-size to a safe discharge point, terminating not more than 6 in above the floor or outside.

  • Backwater valve: required on any fixture drain or building drain subject to backflow from a public sewer; the valve must be installed on the building drain downstream of the fixtures it serves.

Quick reference

Plumbing Materials, Fixtures, and Fittings

  • PVC (polyvinyl chloride) is used for cold water and DWV; CPVC for hot and cold water up to 180°F (82°C); PEX for hot/cold water; GI (galvanized iron) for cold water and some drainage.

  • Copper tube types: Type K (thickest, underground), Type L (standard water service), Type M (thinnest, above-ground only); all are joined by soldering, brazing, or press fittings.

  • Cast iron soil pipe is joined by lead-and-oakum, rubber compression gaskets (no-hub), or mechanical couplings; no-hub couplings require a torque of about 60 in-lb on the clamps.

  • Fixture materials: vitreous china for water closets and lavatories; enameled cast iron for sinks and tubs; stainless steel for commercial sinks; acrylic/fiberglass for tubs and showers.

  • Fittings: a sanitary tee has a curved branch for vertical-to-horizontal flow; a wye (Y) and 1/8 bend is used for horizontal-to-horizontal drainage; a P-trap has a 2-4 in water seal.

  • Water closet flush valves (flushometers) require a minimum 1 in supply and 15-25 psi flowing pressure; tank-type closets require only 1/2 in supply and 8 psi.

  • Pipe sizing abbreviations: nominal pipe size (NPS) vs. actual OD; Schedule 40 PVC has a higher pressure rating than Schedule 20 but lower than Schedule 80 for the same nominal size.

  • Water hammer arrestors are installed near quick-closing valves (flushometers, solenoid valves) to absorb pressure surges; they are not a substitute for proper pipe support.

Quick reference

Plumbing Laws, Ethics, and Professional Practice

  • R.A. 1378 (Plumbing Law) regulates the practice of plumbing in the Philippines; it created the Board of Master Plumbers under PRC and requires registration for master plumbers.

  • Only a registered master plumber may prepare, sign, and seal plumbing plans and specifications; a master plumber's seal and PRC license number are required on drawings submitted for permit.

  • The plumbing code is enforced by the local building official and the local health officer; a plumbing permit must be secured before installation and a certificate of final inspection after.

  • Ethics: a master plumber must not sign plans prepared by unlicensed persons, must not accept commissions from suppliers that compromise design integrity, and must maintain client confidentiality.

  • Continuing professional development (CPD) units are required for license renewal under R.A. 10912; the PRC sets the number of CPD units per renewal cycle.

  • Conflict of interest: a master plumber serving as a consultant must disclose any financial interest in a supplier or contractor; failure to disclose is a violation of the code of ethics.

  • Violations: practicing without a license, falsifying plans, or allowing another to use one's seal are grounds for suspension or revocation of the license by the PRC Board.

  • Contract documents: the agreement between owner and plumber should specify scope, drawings, specifications, payment terms, and warranty; verbal changes should be confirmed in writing.