Grease-Fouled Window Unit in a Canteen

RAC Servicing (DomRAC) NC II · Put your knowledge to work in context.

All case studies

Grease-Fouled Window Unit in a Canteen

A 1.5 HP window-type air conditioner cools the staff canteen of a small factory, running 06:00–22:00 daily, seven days a week. The kitchen hood exhaust discharges 3 m from the unit's outdoor grille. Airflow from the supply grille has dropped noticeably and the evaporator ices up after about 2 hours of running. The caretaker has cleaned the filter every month. The technician finds the evaporator fins coated with a sticky brown film, the blower wheel caked with the same deposit, and the condensate drain partly clogged. He proposes to spray the evaporator with muriatic acid, rinse it with a high-pressure washer with the unit in place and the power on so he can watch the fan, then "add a little R-22 because the suction pressure is low". Before cleaning, suction pressure was 58 psig and amp draw 7.9 A (nameplate RLA 8.4 A); ambient 33 °C. The customer wants a one-visit fix.

1. Critique the proposed cleaning method and state the correct approach.

Read the worked answer

Three parts of the plan will damage the unit. Muriatic (hydrochloric) acid attacks aluminium fins; residue left in the coil causes pinholes in the tubing months later. A high-pressure washer at close range flattens fins and drives water into the blower motor, control box and insulation. And running the fan while spraying water is a shock hazard and a reliable way to short the PCB.

Correct approach: isolate and lock off first. Apply a neutral or mildly alkaline cleaner labelled for aluminium evaporators with a low-pressure sprayer (a hand pump is enough), pre-wet the fins, respect the dwell time, then rinse thoroughly with the nozzle at 45° to the fins and 150–250 mm away, shielding the electrics. Remove the blower wheel and clean it separately in a parts bath - it cannot be cleaned in place. Flush the drain pan and prove the drain with water. Dry, megger the fan motor, then re-energise.

2. Explain the iced evaporator and the 58 psig suction reading. Should refrigerant be added?

Read the worked answer

The icing and the low suction are symptoms of airflow, not of charge. Grease-coated fins and a caked blower wheel cut the air volume across the coil; less heat is absorbed, so the evaporator runs colder than design and the saturated suction temperature falls - 58 psig on R-22 is roughly 0 °C at the coil - and in a humid canteen that surface ices.

The amp draw confirms it: 7.9 A against 8.4 A RLA is a lightly loaded compressor, exactly what a starved evaporator produces. Adding R-22 now would push the charge above design while the real fault remains; once the coil is finally cleaned the unit would be overcharged - high head pressure, possible floodback, and compressor damage on a unit that runs 16 hours a day.

Clean first. Run 20–30 minutes at stable indoor and outdoor conditions, then judge the charge by the manufacturer's method (weigh-in, or subcooling on a capillary system where superheat is fixed by the cap tube). If the readings then sit inside spec, no refrigerant is added at all.

3. Set out a maintenance plan and the customer communication that prevents a repeat.

Read the worked answer

Schedule: filter cleaning every two weeks rather than monthly, because the unit sits downstream of a kitchen hood; evaporator and blower degreasing quarterly, or sooner if the air temperature split falls; drain check monthly in the wet season. Record at every visit - suction pressure, ambient, supply/return temperature split (target roughly 8–11 K for a window unit) and amp draw - so the trend drives the next service rather than a single reading.

Root cause: the grease comes from the hood exhaust 3 m away. Recommend extending or redirecting the duct, or relocating the condenser intake, otherwise the coil re-fouls at the same rate and the quarterly clean becomes permanent.

Communication: show the before/after photographs and the amp reading, explain plainly that the charge was not touched and why, and price the quarterly degrease against a compressor replacement. Write the interval and the readings on the service record so the next technician inherits evidence, not opinions.