- Hierarchy of hazard control
- Order of effectiveness from best to weakest: elimination, substitution, engineering controls, administrative controls, then personal protective equipment. PPE is the last line of defense, not the first choice.
- Lockout/tagout sequence
- Notify affected workers, shut down, isolate the energy source, apply lock and tag, release stored energy such as capacitors and pressure, then verify zero energy before starting work.
- Fire classes A, B, C
- Class A is ordinary combustibles extinguished with water; Class B is flammable liquids using foam, CO2, or dry chemical; Class C is energized electrical using CO2 or dry chemical, never water.
- Manifold gauge color code
- Blue hose connects to the low-pressure suction side, red to the high-pressure discharge side, and yellow to the center service port for vacuum, recovery, or charging operations.
- Superheat formula
- Superheat equals suction line temperature minus the evaporating saturation temperature at suction pressure. For fixed-orifice or capillary systems, a target of about 5 to 10 K is typical.
- Micron and evacuation target
- One micron equals 1/1000 mm Hg and atmospheric pressure is about 760,000 microns. A vacuum of 500 microns or lower held for 15 minutes with the pump isolated indicates acceptable dehydration.
- Flare and torque rule
- Flare faces must be square, burr-free, and lightly oiled, and flare nuts are tightened to the manufacturer's torque with a torque wrench rather than by feel to prevent leaks.
- Nitrogen purge while brazing
- Flow dry nitrogen at low pressure through the pipe during brazing to prevent internal oxidation scale, which can later block the capillary tube, strainer, or thermostatic expansion valve.
- Pressure test with dry nitrogen
- Pressurize the system with dry nitrogen to the manufacturer's test pressure, typically 1.5 times working pressure, and hold. A pressure drop corrected for temperature indicates a leak.
- Triple evacuation procedure
- Evacuate the system, break the vacuum with dry nitrogen, and repeat three times, finishing with a deep evacuation to 500 microns held for 15 minutes to confirm no moisture or leak.
- Condensate trap purpose
- On a draw-through coil, a trap equal to the coil static pressure prevents air from being pulled in through the drain, which would otherwise cause overflow and water damage.
- Delta-T check
- The indoor air temperature drop across a properly operating domestic split evaporator is typically 8 to 11 K. A low value suggests low charge, dirty coil, or low airflow.
- Capacitor microfarad test
- Measure the capacitor with a meter set to capacitance and compare to the rated microfarads, allowing about plus or minus 6 percent. A bulged or out-of-range capacitor is replaced.
- Condenser cleaning direction
- Wash coils from the clean side toward the dirty side so debris is pushed out rather than driven deeper into the fins, and rinse chemical cleaners fully to avoid corrosion.
- Subcooling formula
- Subcooling equals the condensing saturation temperature at discharge pressure minus the liquid line temperature. For thermostatic expansion valve systems, a target of about 5 to 10 K is typical.
- Compressor winding tests
- An open winding reads infinite resistance, a shorted winding reads near zero, and a grounded winding shows continuity to the shell. Compare windings to each other for balance.
- Frozen evaporator causes
- A frozen evaporator results from restricted airflow such as a dirty filter or blocked return, low refrigerant charge, or a faulty defrost or fan control. Superheat and pressures distinguish them.
- High discharge pressure causes
- High discharge pressure points to a dirty condenser, failed condenser fan, overcharge, non-condensables in the system, or high ambient temperature. Check each in that order.
- Restriction versus undercharge
- Both cause low suction and high superheat. A restriction shows a temperature drop across the device such as the capillary or strainer, while undercharge shows low subcooling and no such drop.
- Recovery cylinder fill limit
- Never fill a recovery cylinder above 80 percent of its water capacity by weight. Use a scale, keep the cylinder upright, and never heat it with an open flame.
- Recovery versus recycling
- Recovery removes refrigerant from a system. Recycling cleans it on site of oil, moisture, and particulates but does not restore AHRI 700 purity; reclamation does that at a certified facility.
- Refrigerant vapor density hazard
- Refrigerant vapor is heavier than air and collects at floor level in basements and plant rooms, displacing oxygen. Ventilate and test the atmosphere before entry.
- Ozone depletion potential
- ODP ranks a substance's ozone-destroying effect relative to CFC-11, which equals 1.0. CFCs are highest, HCFCs such as R-22 are about 0.055, and HFCs are zero.
- Global warming potential
- GWP ranks a substance's climate impact relative to carbon dioxide, which equals 1. R-410A is about 2,088, R-134a about 1,430, R-32 about 675, and propane about 3.
- Venting prohibition
- Deliberate release of refrigerant to the atmosphere during service, recovery, or disposal is prohibited. Refrigerant must be recovered, recycled, or reclaimed instead.
- Zeotropic blend charging
- Zeotropic blends such as R-407C have a temperature glide and must be charged as liquid from the cylinder to maintain the correct composition. R-410A has negligible glide.
- Recovery methods compared
- Liquid recovery is fastest, vapor recovery handles the final portion, and push-pull uses the system to move liquid into the cylinder. Small critically charged systems use vapor recovery only.
- Refrigerant PPE
- Wear safety glasses or goggles, refrigerant-rated gloves, long sleeves, and safety shoes. Liquid refrigerant causes frostbite, and vapor can displace oxygen in enclosed spaces.
- Capacitor stored charge hazard
- Capacitors hold charge after power is removed. Isolate and lock out the unit, then discharge the capacitor and verify with a meter before touching electrical terminals.
- Refrigerant recordkeeping
- Log the refrigerant type, amount recovered, amount charged, and cylinder identification for each job, and retain records for the period required by local regulation.
- Leak repair obligation
- Appliances above a threshold charge must be repaired within a set period after a leak is detected, or the owner must document a retrofit or retirement plan.