RETA CARO · Keep the key ideas within reach.

Quick reference

Industrial Refrigeration I - Core Principles and Components

  • Sensible heat changes temperature without a phase change (Q = m·cp·ΔT); latent heat is absorbed or released at constant temperature during a phase change.

  • Refrigeration capacity: 1 ton of refrigeration = 12,000 Btu/hr = 200 Btu/min = 3.517 kW.

  • Pressure–enthalpy diagram: the evaporator absorbs heat between the expansion-valve outlet and the compressor suction; the condenser rejects heat between compressor discharge and expansion-valve inlet.

  • Superheat = actual suction temperature minus saturation temperature at suction pressure; subcooling = saturation temperature at condensing pressure minus liquid line temperature.

  • Compressor displacement (ft³/min) = bore area × stroke × RPM × number of cylinders; volumetric efficiency falls as compression ratio rises.

  • Pressure ratio = absolute discharge pressure ÷ absolute suction pressure; high ratios raise discharge temperature and reduce capacity.

  • A thermostatic expansion valve controls evaporator superheat by modulating refrigerant flow; a flooded evaporator uses a float or level control instead.

  • Refrigerant lines: liquid lines sized to limit pressure drop and flashing; suction lines sized for minimal pressure drop to preserve compressor capacity.

  • Evaporator approach (TD) is the temperature difference between the refrigerated space or medium and the refrigerant saturation temperature.

Quick reference

Ammonia Safety (Industrial Refrigeration IV, Chapter 7)

  • Anhydrous ammonia is flammable at roughly 15–28% by volume in air and is classified as a 2.2 (nonflammable, toxic) gas under transport rules; it is toxic and corrosive to tissue.

  • Ammonia is lighter than air (vapor density about 0.6 relative to air), so it rises and accumulates at high points and ceilings.

  • The NIOSH IDLH for ammonia is 300 ppm; the OSHA PEL is 50 ppm as an 8-hour TWA; the ACGIH STEL is 35 ppm.

  • Ammonia is highly soluble in water; water is the preferred absorbent for vapor release, but never spray water into liquid ammonia pools because it adds heat and accelerates vaporization.

  • Ammonia ignites with difficulty; a direct ignition source plus high concentration is required, and oil-soaked insulation can be a fire hazard near leaks.

  • PPE for ammonia response includes full-face respirator or SCBA, chemical splash goggles, and ammonia-resistant gloves; butyl or neoprene is preferred over natural rubber.

  • Machinery rooms require ventilation, ammonia detection with alarm and shutdown interlocks, and emergency exits that open outward; the room must be separated from occupied spaces.

  • Emergency shutdown and isolation: close king valves and pump-down/isolation valves to limit release, and never enter a high-concentration area without SCBA and a backup person.

  • First aid for ammonia exposure: flush eyes and skin with copious water for at least 15 minutes, remove contaminated clothing, and seek medical attention; inhalation victims need fresh air and oxygen.