RETA CARO study materials
RETA CARO study resources

RETA CARO flashcards

RETA CARO · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Ton of refrigeration
A cooling rate equal to 12,000 Btu per hour, or 200 Btu per minute, equivalent to about 3.517 kilowatts of refrigeration capacity.
Sensible heat
Heat that changes the temperature of a substance without changing its phase, calculated as mass times specific heat times temperature difference.
Latent heat
Heat absorbed or released during a phase change at constant temperature, such as boiling liquid refrigerant in an evaporator or condensing vapor in a condenser.
Superheat
The number of degrees the refrigerant vapor at a given point is above its saturation temperature for the existing pressure, commonly measured at evaporator outlet.
Subcooling
The number of degrees the liquid refrigerant is below its saturation temperature at the existing pressure, typically measured at the condenser outlet or liquid line.
Pressure ratio
Absolute discharge pressure divided by absolute suction pressure; higher ratios increase discharge temperature and reduce compressor volumetric efficiency.
Thermostatic expansion valve
A metering device that regulates refrigerant flow into the evaporator to maintain a set superheat, using a bulb sensing suction line temperature.
Volumetric efficiency
The ratio of actual vapor volume pumped to the compressor displacement volume, reduced by clearance volume, re-expansion, and pressure ratio.
Evaporator approach
The temperature difference between the medium being cooled and the refrigerant saturation temperature in the evaporator; a larger approach indicates reduced heat transfer.
Condenser subcooling purpose
Subcooling the liquid before the expansion valve ensures a solid liquid column at the valve and prevents flash gas from reducing valve capacity.
Compressor displacement
The theoretical volume swept by the compressor pistons per unit time, calculated from bore area, stroke, speed, and number of cylinders.
Liquid line sizing
Liquid lines are sized small enough to limit refrigerant charge but large enough to keep pressure drop low and prevent flashing before the expansion valve.
Suction line sizing
Suction lines are sized to minimize pressure drop, since excess drop lowers suction pressure and reduces compressor capacity and efficiency.
Refrigeration cycle order
The sequence is compressor, condenser, expansion device, evaporator; the compressor raises pressure, the condenser rejects heat, and the evaporator absorbs heat.
Flash gas
Vapor formed when liquid refrigerant pressure drops below its saturation pressure; excessive flash gas at the expansion valve reduces cooling capacity.
Ammonia IDLH
The immediately dangerous to life or health concentration for ammonia is 300 ppm, the level at which escape without respiratory protection may fail.
Ammonia vapor density
Ammonia vapor is about 0.6 times the density of air, so it is lighter than air and tends to rise and collect at ceilings and high points.
Ammonia OSHA PEL
The permissible exposure limit for ammonia is 50 ppm as an eight-hour time-weighted average; the ACGIH short-term exposure limit is 35 ppm.
Ammonia flammability range
Ammonia vapor is flammable in air at roughly 15 to 28 percent by volume and requires a strong ignition source because it ignites with difficulty.
Water on ammonia vapor
Water spray absorbs ammonia vapor effectively because ammonia is highly soluble in water, but water must not be sprayed into liquid ammonia pools.
Ammonia PPE
Response PPE includes SCBA or full-face respirator, chemical splash goggles, and ammonia-resistant gloves such as butyl or neoprene rather than natural rubber.
Ammonia eye first aid
Flush exposed eyes with copious water for at least 15 minutes, remove contaminated clothing, and obtain medical evaluation promptly after exposure.
Machinery room ventilation
Ammonia machinery rooms require mechanical ventilation, ammonia detection with alarm and shutdown interlocks, and outward-opening emergency exits separated from occupied areas.
King valve
A manual shutoff valve at the liquid receiver outlet used to isolate the liquid supply during emergencies or pump-down procedures.
Pump-down procedure
A controlled sequence that draws refrigerant vapor from a section into the receiver or condenser to reduce the charge before repair or isolation.
Ammonia detection alarm
Fixed ammonia sensors in machinery rooms trigger alarms and often ventilation or shutdown interlocks at set low and high concentration thresholds.
Ammonia health effects
Ammonia is corrosive to eyes, skin, and respiratory tissue; inhalation causes burning, coughing, and pulmonary injury, and liquid contact can cause frostbite.
SCBA entry rule
Never enter an ammonia release area without self-contained breathing apparatus and a standby person outside who can assist or summon help.
Ammonia transport classification
Anhydrous ammonia is classified as a toxic gas (Division 2.2 with toxic subsidiary risk) for transport, requiring placarding and emergency response information.
Ammonia oil fire hazard
Oil-soaked insulation or debris near an ammonia leak can ignite and sustain fire, so contaminated materials should be removed and ignition sources controlled.
Ammonia emergency shutdown
Close isolation and king valves to stop flow, isolate the affected section, and avoid operating equipment that could spread vapor or create ignition sources.
Ammonia odor threshold
Ammonia has a pungent odor detectable at roughly 5 to 50 ppm, well below the IDLH, but odor fatigue can reduce warning effectiveness.