Quick reference

Electrical Theory and Circuit Fundamentals

  • Ohm's law: V = I × R; power P = V × I = I²R = V²/R.

  • Series circuit: R_total = R1 + R2 + ...; current is common, voltage divides in proportion to resistance.

  • Parallel circuit: 1/R_total = 1/R1 + 1/R2 + ...; voltage is common, current divides inversely with resistance.

  • AC RMS values: V_rms = V_peak / √2; for a sine wave RMS is 0.707 × peak and average is 0.637 × peak.

  • Impedance Z = √(R² + X²); inductive reactance X_L = 2πfL, capacitive reactance X_C = 1/(2πfC).

  • Power factor = true power (W) / apparent power (VA); three-phase power P = √3 × V_L × I_L × cos φ.

  • Star (wye) and delta relationships: V_line = √3 × V_phase in star; I_line = √3 × I_phase in delta.

  • Kirchhoff's laws: sum of currents at a node is zero; sum of voltages around a closed loop is zero.

  • Conductor resistance R = ρL/A, so resistance rises with length and falls with cross-sectional area.

Quick reference

Wiring Systems, Cables and Accessories

  • Cable current-carrying capacity depends on conductor size, insulation rating, installation method, grouping and ambient temperature.

  • Standard harmonised colours: line brown, neutral blue, protective conductor green/yellow; old UK colours red (line) and black (neutral).

  • Cable selection considers voltage drop, disconnection time, thermal constraints and mechanical protection.

  • Steel conduit and trunking must be earthed and have continuity assured across joints; plastic systems need separate CPC.

  • Socket outlets require fused plugs or circuit protection sized to the cable and load; accessories must match the circuit rating.

  • Non-sheathed cables in walls need conduit or capping; buried cables need egress protection (e.g. earthed metallic covering or RCD).

  • Bending radius must not be less than the manufacturer's minimum to avoid insulation and conductor damage.

  • Cable derating factors are multiplied together (grouping × ambient temperature × thermal insulation) to give the effective capacity.

Quick reference

Protection, Earthing and Bonding

  • Protective device must satisfy I_a × Z_s ≤ U_0 for the disconnection time required by the circuit type.

  • Earth fault loop impedance Z_s = Z_e + (R1 + R2) of the circuit conductors.

  • BS 7671 disconnection times: 0.4 s for TN final circuits ≤32 A, 5 s for distribution circuits and TT systems (with conditions).

  • RCDs to BS EN 61008/61009: 30 mA for additional protection, 300 mA for fire protection of premises.

  • Main protective bonding connects extraneous-conductive-parts to the MET; main bonding conductor minimum 10 mm² (or half the earthing conductor if larger).

  • Supplementary bonding may be required in special locations (e.g. bathrooms) to reduce touch voltage.

  • TT system relies on earth electrodes and RCD protection; Z_s values are typically too high for overcurrent disconnection.

  • Type B, C and D MCBs differ in magnetic trip thresholds (3-5×, 5-10×, 10-20× In respectively).

  • Fuse and MCB discrimination ensures only the device nearest the fault operates.

Quick reference

Electrical Installations and Equipment

  • Every installation must have a main switch, overcurrent protection, and means of isolation for maintenance.

  • Special locations (bathrooms, swimming pools, agricultural) have additional requirements such as 30 mA RCD and zone restrictions.

  • Equipment must be selected to suit its environment (IP rating, temperature, corrosion, mechanical impact).

  • Motors require overload protection, isolation and often starting controls; motor circuit protection differs from cable protection.

  • Distribution boards need clear labelling, a schedule of circuits, and accessible protective devices.

  • Isolation and switching devices must break all live conductors and be capable of being locked off.

  • Equipment enclosures must ensure basic protection (IPXXB) against direct contact under normal conditions.

  • Fire safety: cables serving life safety systems need fire-resistant construction and dedicated protection.

Quick reference

Inspection, Testing and Commissioning

  • Sequence: safe isolation, visual inspection, continuity of protective conductors, ring final circuit continuity, insulation resistance, polarity, earth electrode resistance, earth fault loop impedance, RCD tests, functional tests.

  • Insulation resistance test at 500 V DC; minimum acceptable value 1 MΩ for most circuits (SELV/PELV 250 V).

  • Ring final circuit test: end-to-end readings r1, rn, r2; expected cross-connection readings are (r1+rn)/4 and (r1+r2)/4.

  • Polarity test confirms line and neutral are correctly connected at every point.

  • Earth fault loop impedance measured by loop tester or calculated from Ze + (R1+R2).

  • RCD test: verify trip time at 1× IΔn and 5× IΔn, and no trip at ½ IΔn; check test button function.

  • Continuity of protective conductors tested with low-resistance ohmmeter after nulling leads.

  • Commissioning includes verifying protective device settings, labels, certificates and schedules of test results.

Quick reference

Electrical Safety, Regulations and Codes of Practice

  • BS 7671 (IET Wiring Regulations) is the primary UK standard; the Electricity at Work Regulations 1989 impose statutory duties.

  • Live working is permitted only when it is unreasonable to work dead, and suitable precautions are taken.

  • Safe isolation procedure: identify supply, isolate, lock off, prove tester, prove dead, and re-prove tester.

  • Proving dead requires an approved voltage indicator tested on a known source before and after use.

  • Permit-to-work and lockout/tagout systems control work on high-energy or complex installations.

  • Risk assessment must consider arc flash, stored energy, and the competence of persons.

  • Portable appliance testing intervals are determined by equipment type and environment, not by a single fixed rule.

  • Regulations require adequate earthing, protective devices, and maintenance of electrical systems in safe condition.

Quick reference

Practical Assessment and Fault Diagnosis

  • Fault-finding approach: gather symptoms, form hypotheses, test systematically, confirm root cause before repair.

  • Common faults: open circuit (no continuity), short circuit (low resistance between conductors), earth fault (insulation breakdown).

  • Nuisance RCD tripping can result from accumulated leakage, moisture, or shared neutral faults.

  • High loop impedance indicates poor earthing or loose connections; low insulation resistance indicates damaged insulation or moisture.

  • Voltage drop measurements across a circuit reveal loose or high-resistance joints.

  • Continuity tests must be performed with the circuit isolated and the tester nulled.

  • Thermal imaging and clamp meters assist in locating overloaded or loose connections.

  • After repair, re-test affected circuits and update certificates and schedules.