SG PPE Electrical flashcards
SG PPE Electrical · Build recall with a focused review session.
33 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ohm's Law
- The relationship V = I × R, where V is voltage in volts, I is current in amperes, and R is resistance in ohms. Used to calculate any one value when the other two are known.
- Power Formula
- Electrical power P = V × I, also expressed as I²R or V²/R. Measured in watts and used to size protective devices and cables.
- Series Resistance
- Total resistance in a series circuit equals the sum of individual resistances. Current is the same through all components, while voltage divides across them.
- Parallel Resistance
- Total resistance is the reciprocal of the sum of reciprocals of individual resistances. Voltage is common across branches and current divides between them.
- RMS Voltage
- Root-mean-square value of an AC waveform, equal to peak value divided by √2 (0.707 × peak for a sine wave). It represents the equivalent heating effect of DC.
- Power Factor
- The ratio of true power in watts to apparent power in volt-amperes. A value below one indicates reactive load from inductance or capacitance.
- Three-Phase Power
- For a balanced three-phase load, power equals √3 × line voltage × line current × power factor. Used to size three-phase equipment and protection.
- Conductor Resistance
- Resistance equals resistivity times length divided by cross-sectional area (R = ρL/A). Longer or thinner conductors have higher resistance and greater voltage drop.
- Harmonised Cable Colours
- Standard UK/EU colours: brown for line, blue for neutral, and green/yellow for protective conductor. Older installations may use red and black.
- Cable Derating Factors
- Factors applied to tabulated current capacity to account for grouping, ambient temperature, and thermal insulation. They are multiplied together to give effective capacity.
- Voltage Drop Limit
- BS 7671 recommends a maximum 3% voltage drop for lighting and 5% for other circuits from the origin of the installation. Ensures equipment operates correctly.
- Bending Radius
- Minimum radius to which a cable may be bent without damaging insulation or conductors. Specified by the manufacturer and typically a multiple of cable diameter.
- Protective Conductor
- A conductor that provides a path for fault current and bonds exposed metalwork. Identified by green/yellow colouring and essential for automatic disconnection.
- Earth Fault Loop Impedance
- Total impedance of the path from the origin through the live conductor, the fault, and back via the protective conductor. Must be low enough for disconnection.
- Disconnection Time
- The maximum time permitted for a protective device to operate under fault conditions. Typically 0.4 seconds for final circuits up to 32 A and 5 seconds for distribution circuits.
- RCD Sensitivity
- The rated residual operating current of an RCD. 30 mA is required for additional protection, while 300 mA is used for fire protection of premises.
- Main Protective Bonding
- Connection of extraneous-conductive-parts to the main earthing terminal. The bonding conductor is typically at least 10 mm² or half the earthing conductor size.
- TT System
- An earthing arrangement where the supply neutral is earthed at the source and the installation uses its own earth electrode. Usually requires RCD protection for fault disconnection.
- MCB Trip Types
- Type B trips at 3-5 times rated current, Type C at 5-10 times, and Type D at 10-20 times. Selection depends on inrush current and loop impedance.
- IP Rating
- Ingress protection code indicating resistance to solids and liquids. The first digit covers solids and the second covers water, e.g. IP44.
- Special Locations
- Areas such as bathrooms, swimming pools, and agricultural buildings with additional protective requirements. Often include 30 mA RCD protection and zone restrictions.
- Isolation Device
- A switch or isolator that disconnects all live conductors and can be locked off. Essential for safe maintenance and repair work.
- Motor Overload Protection
- A protective device that prevents sustained overcurrent from damaging motor windings. Distinct from short-circuit protection and set to the motor's full-load current.
- Insulation Resistance Test
- A test at 500 V DC measuring resistance between live conductors and earth. A minimum of 1 MΩ is generally acceptable for most circuits.
- Ring Final Circuit Test
- End-to-end resistance readings r1, rn, and r2 are taken. Cross-connected readings should equal (r1+rn)/4 and (r1+r2)/4 to confirm ring integrity.
- Polarity Test
- Verifies that line and neutral are correctly connected at every accessory and that switches are in the line conductor. Prevents dangerous reversed connections.
- RCD Trip Time Test
- Verifies operation at rated residual current and five times rated current, and confirms no trip at half rated current. Ensures the device protects as intended.
- Safe Isolation
- A procedure to confirm a circuit is dead before work: identify, isolate, lock off, prove tester, prove dead, and re-prove tester on a known source.
- BS 7671
- The IET Wiring Regulations, the primary UK standard for electrical installation design and verification. It sets requirements for safety, protection, and testing.
- Electricity at Work Regulations
- UK statutory regulations imposing duties on employers and employees to maintain electrical systems safely. They underpin safe working practices and competence requirements.
- Proving Dead
- Confirming a circuit is de-energised using an approved voltage indicator tested before and after use. A critical step in safe isolation.
- Short Circuit Fault
- An unintended low-resistance path between live conductors, causing high current flow. Protective devices must interrupt it rapidly to prevent damage or fire.
- Nuisance RCD Tripping
- Unwanted RCD operation caused by accumulated leakage currents, moisture, or shared neutral faults. Diagnosed by isolating circuits and testing leakage individually.