City & Guilds 2391-51 flashcards
City & Guilds 2391-51 · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- BS 7671 legal status
- BS 7671 is the national wiring standard; it is non-statutory, but compliance is commonly accepted as evidence that statutory duties under the Electricity at Work Regulations have been met.
- EAWR Regulation 14
- Prohibits work on or near live conductors unless it is unreasonable for the equipment to be dead and suitable precautions, including a written risk assessment, have been taken.
- Part P Building Regulations
- Applies to electrical installations in dwellings in England and Wales; certain work is notifiable to building control and the work must comply with Part P requirements.
- GS38 test lead requirements
- Test probes to GS38 have no more than 4 mm exposed metal tip, finger guards, fused leads and adequate voltage category rating, protecting the user during live testing.
- Prove dead procedure
- Identify and isolate the circuit, lock off, prove the voltage detector on a known source, test the conductors, then re-prove the detector to confirm it still works.
- Lock off and warning notice
- The isolation device is padlocked with the key retained by the person working, and a warning notice is fixed so others cannot inadvertently restore the supply.
- Two-pole voltage detector
- An approved two-pole device to GS38 is used to prove conductors dead; non-contact or single-pole voltage indicators are not acceptable for proving dead.
- Competence under EAWR
- Regulation 16 requires that no person works on electrical systems unless competent to do so, or is supervised by someone who is competent, preventing unsafe working.
- Sampling in periodic inspection
- Periodic inspection may examine a sample of the installation where justified; the sample is increased if defects are found and the approach is recorded as a limitation.
- Recording limitations
- Items not inspected or tested, such as inaccessible areas or circuits omitted from the sample, must be listed on the condition report so the reader knows the extent covered.
- Previous documentation review
- Prior certificates, schedules of test results, drawings and records of alterations are reviewed before a periodic inspection to plan sampling and identify changes.
- Agreeing extent with client
- Before starting, the client and inspector agree in writing which parts of the installation and which circuits are covered, and what limitations apply.
- Main protective bonding size
- The main protective bonding conductor size is determined from the supply neutral conductor size using BS 7671 Table 54.8, typically 10 mm2 for a 25 mm2 neutral.
- Safe zones for buried cables
- Cables buried in walls must run within defined safe zones, typically within 150 mm of a corner or ceiling or aligned with an accessory, otherwise extra protection is required.
- Signs of heat damage
- Discoloured or brittle insulation, melted plastic, blackened terminals and a burning smell indicate overheating from loose connections or overload and require investigation.
- Consumer unit enclosure checks
- The enclosure should be sound, correctly IP rated for its location, with no unused open knockouts, intact barriers and a legible and accurate circuit chart.
- EIC versus EICR
- An Electrical Installation Certificate is issued after initial verification of new work; an Electrical Installation Condition Report records the condition of an existing installation after periodic inspection.
- Initial verification coverage
- Initial verification covers the whole new installation or alteration, comparing it with the design, and requires full inspection and testing without any sampling.
- Purpose of periodic inspection
- Periodic inspection determines whether an existing installation is safe for continued use, identifying deterioration, damage, defects and non-compliance with the current standard.
- Domestic EICR interval
- Guidance suggests a maximum of ten years between periodic inspections for a domestic installation, or at a change of occupancy or change of use.
- Ring final continuity readings
- End-to-end resistances r1, rn and r2 are measured; r1 should equal rn, and r2 is approximately 1.67 times r1 for 2.5 mm2 line and 1.5 mm2 CPC.
- Ring final R1+R2 value
- After cross-connecting line and neutral at the board, the expected R1+R2 at each socket is (r1+r2)/4, with readings increasing towards the mid-point of the ring.
- Insulation resistance minimum
- For circuits up to 500 V the test is at 500 V DC and the minimum acceptable insulation resistance is 1 Mohm; SELV and PELV require 250 V DC and 0.5 Mohm.
- Main bonding continuity value
- Continuity of main protective bonding is measured between the main earthing terminal and the bonding clamp, with a typical acceptable result of 0.05 ohm or less.
- External earth loop impedance
- Ze is measured at the origin with the installation isolated, the main switch off and the main earthing conductor disconnected, using a suitable earth fault loop impedance tester.
- Zs 0.8 rule
- Measured Zs should not exceed 0.8 times the tabulated maximum Zs, because tabulated values apply at 20 degrees C while conductors run hotter in service.
- RCD five-times tripping time
- A general non-delay RCD should trip within 40 ms when tested at five times its rated residual operating current, and the test is repeated on both half-cycles.
- Prospective fault current measurement
- Prospective short-circuit current between line and neutral and prospective earth fault current between line and earth are both measured at the origin, and the higher is recorded.
- C1 classification code
- C1 means danger is present, there is a risk of injury, and immediate remedial action is required, usually involving isolation of the affected circuit or installation.
- C2 classification code
- C2 means a potentially dangerous condition exists and urgent remedial action is required; a report containing any C2 observation cannot be recorded as satisfactory.
- C3 classification code
- C3 means improvement is recommended; the condition is not dangerous but would benefit from improvement, and no immediate action is required.
- FI classification code
- FI means further investigation is required because a defect or departure is suspected but cannot be confirmed without additional access, testing or dismantling.