General Electrical Knowledge and NEC Structure

  • NFPA 70 (NEC) has nine chapters: Chapters 1-4 are general, Chapters 5-7 supplement or modify them, Chapter 8 is independent, and Chapter 9 contains tables.

  • "Shall" indicates a mandatory requirement; "should" and Informational Notes are explanatory and not enforceable.

  • Annexes A through I are informational only unless a Code article specifically references them.

  • Article 100 definitions apply throughout the Code and are located in Chapter 1.

  • Under 90.4 the authority having jurisdiction interprets the Code, may grant written exceptions, and is responsible for enforcement.

  • Chapter 2 covers wiring and protection (Articles 200-285), Chapter 3 covers wiring methods (300-398), and Chapter 4 covers equipment for general use (400-490).

  • Article 110 general requirements include 110.14 terminations, 110.26 working space, and 110.28 enclosure types.

Quick reference

Electrical Calculations and Theory

  • Ohm's law: V = I x R. Power: P = V x I = I squared x R = V squared / R.

  • Balanced three-phase power: P = 1.732 x line voltage x line current x power factor.

  • Single-phase voltage drop: VD = (2 x K x I x L) / circular mils; use 1.732 instead of 2 for three-phase.

  • K values used for voltage drop: 12.9 for copper and 21.2 for aluminum.

  • Dwelling general lighting load is 3 VA per square foot under Table 220.12; small-appliance and laundry branch circuits are 1,500 VA each.

  • Continuous loads require branch-circuit conductors and overcurrent devices at 125 percent of continuous load plus 100 percent of noncontinuous load (210.19, 210.20).

  • Box-fill volume per conductor (Table 314.16(B)): 14 AWG = 2.00 cubic inches, 12 AWG = 2.25, 10 AWG = 2.50.

  • A neutral that carries only the unbalanced current of other conductors is not counted as a current-carrying conductor (310.15(E)).

Quick reference

Wiring Methods and Materials

  • Raceway fill (Chapter 9 Table 1): one conductor 53 percent, two conductors 31 percent, more than two conductors 40 percent.

  • Pull box sizing (314.28): straight pulls use 8 times the largest raceway trade diameter; angle pulls use 6 times.

  • Support intervals: NM cable within 12 inches of a box and every 4.5 feet; EMT and rigid metal conduit every 10 feet and within 3 feet of a box.

  • Minimum cover (300.5): 24 inches general direct burial, 18 inches for PVC, 6 inches for rigid metal conduit, 12 inches for residential branch circuits.

  • A box or conduit body is required at every splice, pull point, and outlet (300.15).

  • 300.4 requires protection from physical damage where conductors are within 1 1/4 inches of the framing surface.

  • Chapter 9 Table 8 lists conductor areas and Table 4 lists raceway areas for fill calculations.

  • Cable tray, busways, and wireways are covered by Articles 392, 368, and 376 respectively.

Quick reference

Wiring and Protection

  • Receptacle spacing (210.52): no point along the floor line may be more than 6 feet from a receptacle; wall spaces 2 feet or wider are counted.

  • GFCI protection is required in dwelling bathrooms, garages, outdoors, kitchens, laundry areas, basements, crawl spaces, and within 6 feet of sinks.

  • AFCI protection is required on dwelling 120-volt branch circuits rated 20 amperes or less in bedrooms, kitchens, laundry areas, and most other rooms (210.12).

  • Small-conductor overcurrent limits (240.4(D)): 14 AWG = 15 amperes, 12 AWG = 20 amperes, 10 AWG = 30 amperes.

  • 210.70 requires lighting outlets in habitable rooms, bathrooms, hallways, stairways, garages, and outdoor entrances.

  • Overcurrent devices must be readily accessible and may not be located in bathrooms or over steps (240.24).

  • Ground-fault protection of equipment (230.95) is required for solidly grounded wye services over 150 volts to ground and exceeding 1,000 amperes.

  • Service disconnecting means ratings are set by 230.79, with service-entrance conductors sized by Article 230 and Table 310.16.

Quick reference

Grounding and Bonding

  • 250.50 requires all available grounding electrodes to be bonded together into a single grounding electrode system.

  • Common electrodes: underground metal water pipe with 10 feet of earth contact, 8-foot ground rod, concrete-encased electrode, and ground ring.

  • A single ground rod must show 25 ohms or less; if not, a second electrode at least 6 feet away must be added (250.53).

  • Grounding electrode conductors are sized from Table 250.66; equipment grounding conductors from Table 250.122.

  • The service neutral is grounded only at the service; panelboards downstream use a separate equipment grounding terminal bar (250.24, 408.40).

  • Metal water piping and structural steel must be bonded per 250.104, with bonding jumpers sized from Table 250.102(C)(1).

  • Equipment grounding conductors must be green, green with a yellow stripe, or bare (250.119).

  • 250.4 requires a permanent, low-impedance ground-fault current path able to carry fault current safely.

Quick reference

Equipment for General Use

  • Appliance branch circuits must have a rating not less than the appliance marked rating, and 125 percent for continuous-duty appliances (422.10).

  • Fixed electric space heating conductors and overcurrent devices are sized at 125 percent of the connected load (424.3).

  • Clothes closet luminaires: 12 inches of clearance for surface-mounted incandescent, 6 inches for recessed incandescent (410.16).

  • Transformer overcurrent protection is set by 450.3, and 450.14 requires a disconnecting means for transformers.

  • Panelboards require overcurrent protection not greater than the panelboard rating (408.36).

  • Receptacles in wet or damp locations must be listed weather-resistant types with in-use covers where required (406.9).

  • Flexible cords and cables (Article 400) may not be used as a substitute for the fixed wiring of a structure.

Quick reference

Motors, HVAC, and Motor Controls

  • Motor full-load current for conductor and short-circuit protection comes from Tables 430.247-430.250, not the nameplate; nameplate current is used for overload sizing.

  • Motor branch-circuit conductors must have ampacity of at least 125 percent of the motor full-load current (430.22).

  • 430.52 short-circuit protection: inverse-time breaker 250 percent, dual-element fuse 175 percent, non-time-delay fuse 300 percent of full-load current.

  • 430.32 overload protection: 125 percent of nameplate current for motors with a 1.15 service factor, otherwise 115 percent.

  • The motor disconnecting means must be within sight of both the motor and the controller (430.102).

  • Several motors on one branch circuit: 125 percent of the largest full-load current plus the sum of the others (430.24).

  • Hermetic refrigerant motor-compressors: conductors at 125 percent and overcurrent protection at 175 percent, up to 225 percent, of rated load current (440.32, 440.22).

  • Motor control circuits are covered in Article 430 Part VI; remote-control circuits are Class 1 circuits under Article 725.

Quick reference

Special Occupancies

  • Class I locations contain flammable gases or vapors, Class II locations contain combustible dust, and Class III locations contain ignitable fibers or flyings (Article 500).

  • Division 1 means the hazard exists under normal conditions; Division 2 means the hazard exists only under abnormal conditions.

  • Articles 505 and 506 provide the Zone classification system as an alternative to divisions for Class I locations.

  • Seals are required in conduit leaving Class I, Division 1 enclosures (501.15).

  • Article 517 covers health care facilities, where critical care areas require hospital-grade receptacles and redundant grounding.

  • Article 511 covers commercial garages, Article 514 motor fuel dispensing facilities, and Article 555 marinas and boatyards.

  • Article 700 covers emergency systems, Article 701 legally required standby, Article 702 optional standby, and Article 708 critical operations power systems.

Quick reference

Special Equipment and Special Conditions

  • Pools and spas (Article 680): equipotential bonding with at least 8 AWG copper, and receptacles GFCI protected and at least 6 feet from the water edge.

  • Solar photovoltaic systems (Article 690): short-circuit current is multiplied by 125 percent for conductor and overcurrent device sizing, and rapid shutdown is required.

  • Fire pumps (Article 695): the overcurrent device must carry the locked-rotor current indefinitely.

  • Energy storage systems are Article 706 and electric vehicle charging is Article 625.

  • Temporary wiring is Article 590; it must be removed after construction and temporary receptacles require GFCI protection.

  • Interconnected electric power production sources are Article 705, and signs and outline lighting are Article 600.

  • Cranes and hoists, electric welders, and induction heating equipment are covered by Articles 610, 630, and 665.

Quick reference

Low-Voltage, Communications, and Signaling Systems

  • Articles 725, 760, 770, 800, 820, and 830 cover Class 1/2/3 circuits, fire alarm, optical fiber, communications, CATV/radio, and broadband systems.

  • Class 2 and Class 3 circuits are power-limited; permitted power sources are listed in Chapter 9 Tables 11(A) and 11(B).

  • Class 2 and Class 3 conductors generally may not occupy the same raceway, cable, or enclosure as power conductors (725.136).

  • Communications cables must be separated from power conductors by at least 2 inches where not in raceways (800.133).

  • Fire alarm Class A circuits continue operating after a single open or ground fault; Class B circuits do not.

  • Fire alarm cable must be listed for the purpose and installed per the permitted Chapter 3 or cable methods of Article 760.

  • Low-voltage lighting systems are limited to 30 volts or less and require listed power supplies (Article 411).

Quick reference

Utah Electrical Statutes, Administrative Rules, and Licensing Requirements

  • The Utah Electricians Licensing Act is administered by the Division of Occupational and Professional Licensing (DOPL) within the Department of Commerce.

  • Administrative rule R156-55b implements the Electricians Licensing Act and establishes licensing and renewal requirements.

  • License categories include apprentice, journeyman, master, residential journeyman, and residential master electrician.

  • Electrical work must be performed under a licensed electrical contractor, and a permit must be obtained from the local building authority before work begins.

  • Local jurisdictions inspect electrical installations and may require correction of Code violations before the work is energized.

  • Apprentices must be registered with DOPL and work under the supervision of a journeyman or master electrician.

  • DOPL may deny, suspend, revoke, or place a license on probation for Code violations, incompetence, or dishonest dealing.

  • Utah adopts the National Electrical Code by administrative rule; the edition in effect applies to permits issued while it is in force.