- Purpose of NFPA 70
- The National Electrical Code, NFPA 70, is an installation code of minimum requirements; it is not a design specification, manual, or instruction book for untrained persons.
- Chapter 8 independence
- Communications systems covered by NEC Chapter 8 are not subject to the requirements of Chapters 1 through 7 unless a Chapter 8 article specifically references them.
- Chapters 5 through 7 role
- Chapters 5, 6, and 7 supplement or modify Chapters 1 through 4 for special occupancies, special equipment, and special conditions; the general chapters still apply.
- Three-phase power formula
- In a balanced three-phase circuit, power in watts equals 1.732 times line-to-line voltage times line current times the power factor.
- Continuous load conductor sizing
- Branch-circuit conductors must have an ampacity of at least 125 percent of the continuous load plus 100 percent of the noncontinuous load before ampacity adjustment factors are applied.
- Box fill for 12 AWG
- For box-fill calculations, each 12 AWG conductor counts as 2.25 cubic inches, a 14 AWG counts 2.00, and a 10 AWG counts 2.50 cubic inches.
- NM cable support interval
- Nonmetallic-sheathed cable must be secured within 12 inches of every box or fitting and at intervals not exceeding 4.5 feet along its run.
- Conduit fill three conductors
- Where a raceway contains more than two conductors, the conductors may fill no more than 40 percent of the raceway cross-sectional area.
- Direct burial depth general
- General direct-buried conductors and cables require 24 inches of cover; residential branch circuits may be buried 12 inches and rigid metal conduit 6 inches.
- Receptacle spacing wall rule
- In dwelling units, receptacle outlets must be arranged so that no point along the floor line of any wall space is more than 6 feet from a receptacle.
- Small conductor overcurrent limits
- Under the small-conductor rule, 14 AWG copper is protected at 15 amperes, 12 AWG at 20 amperes, and 10 AWG at 30 amperes.
- GFCI protection threshold
- A Class A ground-fault circuit interrupter trips at 4 to 6 milliamperes; dwellings require GFCI protection in bathrooms, garages, outdoors, kitchens, laundry areas, and basements.
- Ground rod supplemental electrode
- A single ground rod that does not measure 25 ohms or less to earth must be supplemented by one additional electrode at least 6 feet away.
- Concrete-encased electrode
- A concrete-encased electrode consists of at least 20 feet of bare copper conductor or 1/2-inch reinforcing steel encased in concrete in direct contact with earth.
- Equipment grounding conductor sizing
- Equipment grounding conductors are sized using NEC Table 250.122 according to the ampere rating of the overcurrent device protecting the circuit, not the conductor size.
- Luminaire closet clearance
- A surface-mounted incandescent luminaire in a clothes closet needs 12 inches of clearance from the storage space; recessed and fluorescent types have smaller required clearances.
- Fixed space heating load
- Branch-circuit conductors and overcurrent devices for fixed electric space heating must be sized at not less than 125 percent of the total connected heating load.
- Switch rating requirement
- Snap switches must have current and voltage ratings not less than the load they control, and the switch must be marked with its ratings.
- Motor inverse-time breaker
- Short-circuit protection for a motor branch circuit using an inverse-time circuit breaker may be set as high as 250 percent of the motor full-load current.
- Motor conductor ampacity
- Motor branch-circuit conductors must have an ampacity of at least 125 percent of the full-load current value taken from the appropriate NEC motor table.
- Motor overload protection sizing
- Overload protection for a motor marked with a service factor of 1.15 is generally sized at 125 percent of the nameplate full-load current.
- Hazardous location classes
- In the NEC hazardous location system, Class I locations contain flammable gases or vapors, Class II contains combustible dust, and Class III contains ignitable fibers or flyings.
- Division 1 versus 2
- Division 1 covers locations where the hazardous material is present under normal operating conditions; Division 2 covers abnormal conditions such as equipment failure or container rupture.
- Emergency system definition
- Emergency systems under Article 700 serve life safety and are legally mandated; optional standby systems under Article 702 have no such legal requirement.
- Pool equipotential bonding
- Pool shells, metal fittings, and associated equipment must be bonded together with a copper conductor not smaller than 8 AWG to form a common equipotential grid.
- PV source current factor
- Photovoltaic source circuit currents are multiplied by 125 percent before sizing conductors and overcurrent devices, because modules can exceed rated output.
- Fire pump overcurrent protection
- Fire pump overcurrent devices must be sized to carry the motor locked-rotor current indefinitely so the pump is not disconnected during starting.
- Class 2 circuit definition
- Class 2 circuits are power-limited circuits whose voltage and current are restricted by listed power supplies, allowing reduced wiring protection requirements.
- Separation of Class 2
- Class 2 and Class 3 conductors generally may not be placed in the same raceway, cable, or enclosure as electric light and power conductors.
- Fire alarm circuit class
- Class A fire alarm circuits continue to operate after a single open or ground fault; Class B circuits do not and signal the trouble condition instead.
- Utah electrician licensing agency
- The Utah Division of Occupational and Professional Licensing, within the Department of Commerce, licenses electricians and enforces the Electricians Licensing Act.
- Utah electrical contractor license
- In Utah, an electrical contractor license is required to bid or perform electrical work for compensation; contractor and electrician licenses are issued through DOPL.