UT Electrician: Wiring Methods and Materials

UT Electrician · Work through your exam, one topic at a time.

All guide sections

Wiring Methods and Materials

Conductors

Minimum sizes are 14 AWG copper and 12 AWG aluminum (310.106). Ampacities come from Table 310.16 based on insulation rating and terminal temperature; the 60 °C column applies unless terminals are rated higher. Adjustment for more than three current-carrying conductors in a raceway appears in Table 310.15(C)(1), and ambient temperature correction tables apply on top of that. Equipment grounding conductors are not counted as current-carrying. Neutral conductors count only when they carry harmonic current in a wye system.

Raceways and cables

Know the permitted uses and support rules: EMT supported every 10 ft and within 3 ft of a box; rigid metal conduit every 10 ft; PVC every 3 ft for 1/2 in. through 1 in.; NM cable every 4.5 ft and within 12 in. of a box; MC and AC cable every 6 ft and within 12 in. No more than 360° of bends between pull points. Conduit fill follows Chapter 9 Table 1 - one conductor 53%, two 31%, three or more 40%. Minimum cover in earth (Table 300.5): rigid metal conduit 6 in., PVC 18 in., direct-buried cable 24 in. (18 in. for residential branch circuits at 120 V/20 A or less with GFCI protection). Conductors within 1-1/4 in. of framing need nail plates or bushings (300.4).

Traps

Using NM cable outdoors or in wet locations, forgetting that ENT and PVC have temperature and sunlight limitations, miscounting current-carrying conductors for derating, and assuming derated ampacity can exceed the small-conductor limits of 240.4(D).

Worked example

Six 12 AWG THHN current-carrying conductors in one raceway: 30 A × 0.80 = 24 A after adjustment, but 240.4(D) still caps the overcurrent device at 20 A unless 240.4(B) or (E) applies.