WA Water/Wastewater Operator · Keep the key ideas within reach.

Quick reference

Source Water and Water Quality

  • Washington surface water sources are classified by the federal Surface Water Treatment Rule; groundwater under direct influence of surface water (GWUDI) must be treated as surface water.

  • Turbidity limits: conventional filtration must produce finished water ≤0.3 NTU in at least 95% of monthly samples, with no sample exceeding 1 NTU.

  • Total coliform Rule: no more than 5% of monthly samples may be positive for systems collecting 40 or more samples per month; any positive triggers repeat sampling.

  • Disinfection byproduct limits under Stage 2 DBPR: TTHM running annual average ≤80 µg/L and HAA5 ≤60 µg/L.

  • Lead action level is 0.015 mg/L and copper action level is 1.3 mg/L, measured at the 90th percentile of tap samples.

  • Nitrate MCL is 10 mg/L as nitrogen; arsenic MCL is 0.010 mg/L; fluoride MCL is 4.0 mg/L with a secondary limit of 2.0 mg/L.

  • Alkalinity, pH, and temperature govern corrosion control; negative Langelier Saturation Index indicates water tends to be corrosive.

  • Source water assessment and wellhead protection programs identify potential contamination threats within the contributing area.

Quick reference

Treatment Processes

  • Coagulation destabilizes particles by neutralizing negative surface charge; rapid mix velocity gradient typically 300-1000 per second for under 30 seconds.

  • Flocculation builds settleable flocs at a velocity gradient of roughly 10-75 per second with detention time of 15-45 minutes.

  • Sedimentation design overflow rate for conventional clarifiers is commonly 0.3-1.0 gpm/ft²; shallower settling depth improves removal per Stokes' law.

  • Rapid sand filtration rate is typically 2-6 gpm/ft²; filter run ends on headloss limit, turbidity breakthrough, or run time.

  • Backwash requires bed expansion of about 20-50% and air scour or surface wash to break up mudballs.

  • CT (disinfectant concentration × contact time) must meet the required value for the log inactivation credited; baffling factor reduces theoretical contact time.

  • Softening by lime precipitation removes calcium and magnesium; excess lime raises pH and requires recarbonation for stability.

  • Ion exchange, activated alumina, and reverse osmosis are used for nitrate, arsenic, and dissolved solids removal respectively.

Quick reference

Distribution Systems

  • Minimum residual disinfectant in distribution is typically 0.2 mg/L free chlorine; detectable residual must be maintained throughout the system.

  • System pressure must be maintained at a minimum of 20 psi under all conditions, including fire flow, to prevent backflow contamination.

  • Water age increases with low demand and oversized mains; long detention degrades residual and raises disinfection byproduct formation.

  • Head loss in pipes follows the Hazen-Williams equation; C factors of 100-140 represent roughness, with lower values for older unlined mains.

  • Cross-connection control requires an air gap or reduced-pressure-zone backflow assembly; testable assemblies are tested annually.

  • Storage tanks need turnover, vent screening, and overflow protection; altitude valves and mixing systems control level and quality.

  • Leak detection uses acoustic listening, correlators, or step testing; minimum night flow indicates the level of real losses.

  • Flushing velocity of at least 2.5 ft/s scours sediment; unidirectional flushing sequences from clean to dirty zones.

Quick reference

Collection Systems

  • Sanitary sewer design velocity: minimum 2 ft/s for self-cleansing, maximum about 10 ft/s to limit scour and hydrogen sulfide release.

  • Manning's equation: Q = (1.486/n) A R^(2/3) S^(1/2); typical n for vitrified clay or concrete pipe is 0.013.

  • Infiltration enters through defective pipe and joints; inflow enters through direct connections such as roof drains and catch basins.

  • Peak wet-weather flow is estimated by the rational method Q = CiA or by unit hydrograph methods for combined systems.

  • Lift stations use wet wells with pumps alternating to equalize wear; check valves and air release prevent backflow and surge.

  • Hydrogen sulfide causes corrosion of concrete crown, odors, and toxicity; dosing ferric salts or nitrate controls sulfide.

  • Confined space entry into sewers requires atmospheric testing for oxygen, flammables, and H2S before and during entry.

  • Sewer rehabilitation methods include cured-in-place lining, slip lining, and grouting; smoke testing locates inflow sources.

Quick reference

Pumps, Motors, and Mechanical Equipment

  • Pump affinity laws: flow varies with speed, head with speed squared, power with speed cubed for a given impeller diameter.

  • Brake horsepower = (Q × H × specific gravity) / (3960 × pump efficiency) with Q in gpm and H in feet.

  • NPSH available must exceed NPSH required to avoid cavitation; cavitation causes noise, vibration, and impeller erosion.

  • Centrifugal pumps operate near best efficiency point; running far left or right of BEP shortens bearing and seal life.

  • Motor full-load current is read from the nameplate; overload heaters are sized at 115-125% of FLA per NEC.

  • Vibration analysis, thermography, and lubricant analysis are predictive maintenance tools; alignment and balance reduce wear.

  • Positive displacement pumps deliver nearly constant flow against varying head and require a relief valve on the discharge.

  • Mechanical seals and packing require controlled leakage or flush water; packing is adjusted to a slight drip.

Quick reference

Disinfection and Chemical Feed

  • Chlorine dose = demand + residual; free chlorine reacts with ammonia to form chloramines, which are weaker disinfectants.

  • Breakpoint chlorination requires a chlorine-to-ammonia weight ratio near 7.6 to 1 to convert ammonia to nitrogen gas.

  • Hypochlorite strength degrades over time and with heat; sodium hypochlorite solution is typically 12.5% and stored cool and dark.

  • Chlorine gas is 2.5 times heavier than air; one ton cylinder leak requires respiratory protection and emergency response.

  • CT requirement: log inactivation credit depends on disinfectant type, concentration, contact time, pH, and temperature.

  • Chemical feed pumps are calibrated by drawdown test; dose in mg/L = (feed rate in lb/day × 8.34) / flow in MGD.

  • UV disinfection dose is measured in mJ/cm²; transmittance of the water affects delivered dose.

  • Ozone is generated on site, requires contact chamber and off-gas destruction; bromate formation is a concern.

Quick reference

Laboratory Analysis and Process Control

  • Nephelometric turbidity is measured in NTU; calibration uses formazin or approved polymer standards.

  • DPD colorimetric method measures free and total chlorine; total minus free approximates combined chlorine.

  • pH meter calibration uses two buffers bracketing the sample, commonly pH 7 and pH 10; slope should be 95-105%.

  • Jar testing determines coagulant dose by varying chemical dose and mixing conditions and measuring settled turbidity.

  • Total coliform presence/absence uses defined substrate methods; positive samples must be followed by repeat sampling.

  • TSS is measured by filtering a known volume and drying at 103-105 °C; volatile solids are ignited at 550 °C.

  • BOD5 measures oxygen consumed over five days at 20 °C; nitrification inhibition may be needed.

  • Quality control includes blanks, duplicates, spikes, and control charts; holding times and preservation must be met.

Quick reference

Safety, Regulations, and Recordkeeping

  • Washington operator certification is issued by the Department of Health; water treatment and distribution certifications are separate.

  • Consumer Confidence Report (annual water quality report) must be delivered to customers by July 1 each year.

  • Monitoring violations and MCL violations require public notification within 24 hours for acute risks and 30 days for others.

  • Confined space entry requires a permit, atmospheric testing, attendant, and retrieval system; IDLH atmospheres require supplied air.

  • Hazard communication requires Safety Data Sheets and labeling for all chemicals; chlorine and ammonia have specific emergency plans.

  • Records for bacteriological samples, chemical analyses, and operation must be retained at least five years per federal rule.

  • Lockout/tagout isolates energy sources before equipment maintenance; verify zero energy state before work.

  • Fall protection is required at 4 feet in general industry; ladder and guardrail rules apply to tank and basin access.