Psi to feet of head
Multiply psi by 2.31 to convert pressure into feet of water column, and multiply feet of head by 0.433 to convert back into psi.
Weight of one gallon
One gallon of water weighs 8.34 pounds and occupies 231 cubic inches; one cubic foot holds 7.48 gallons and weighs 62.4 pounds.
Air gap definition
The unobstructed vertical distance through free air between a water supply outlet and the flood level rim of the receiving fixture, giving the highest level of backflow protection available.
Reduced pressure zone assembly
A testable backflow preventer containing two check valves and a differential relief valve that protects against both backsiphonage and backpressure, and requires annual certified testing.
Water hammer arrestor
A device containing a trapped air chamber or spring-loaded piston, installed near quick-closing valves to absorb the pressure surge produced when flow stops suddenly.
Trench protection threshold
Excavations 5 feet deep or more require sloping, shoring, or a trench box, and a competent person must classify the soil and inspect the excavation daily.
Maximum pipe velocity
Water piping is sized so velocity does not exceed about 8 feet per second in cold water lines or about 5 feet per second in hot water lines.
Pressure reducing valve
A device installed on the building service when street pressure exceeds 80 psi, reducing it to a usable range, typically about 50 to 60 psi.
Water supply fixture units
A weighted value assigned to each fixture based on its flow demand; values are summed along a branch and converted to probable gpm demand by table.
Frost depth burial
Water service pipe must be buried below the local frost line, which in Wisconsin ranges from roughly 3.5 feet in the south to about 6 feet in the north.
Residual flow pressure
The pressure remaining at a fixture while water is flowing; code tables set a minimum for each fixture type, commonly in the range of 8 to 20 psi.
Service shutoff valve
A full-flow valve installed on the water service near the point of entry so the entire building supply can be shut off for repairs or emergencies.
Horizontal drain slope
Horizontal drainage pipe 2-1/2 inches and smaller must slope at 1/4 inch per foot; pipe 3 inches and larger must slope at 1/8 inch per foot.
Trap seal depth
A trap must hold a liquid seal between 2 and 4 inches deep, and the vertical drop from the fixture outlet to the trap weir cannot exceed 24 inches.
Trap arm length limit
The developed length from trap weir to vent fitting is limited by pipe size, from 5 feet for 1-1/4 inch pipe up to 16 feet for 4 inch pipe.
Vent terminal location
A vent must terminate at least 6 inches above the roof, at least 3 feet from operable windows and doors, and at least 10 feet from outdoor air intakes.
Cleanout placement
Cleanouts are required at the base of each stack, at the building sewer, at 100 foot intervals along horizontal runs, and at changes of direction greater than 45 degrees.
Wet vent
A single pipe that serves both as the vent for one fixture and as the drain for another fixture discharging downstream of it, sized by table.
Prohibited S-trap
A trap with a horizontal outlet on the same plane as its inlet; it self-siphons and loses its seal, so the code prohibits it.
Water closet clearance
A water closet requires at least 15 inches from its centerline to any side wall or partition and at least 21 inches of clear space in front of the bowl.
Water closet fixture units
A 1.6 gallon per flush tank-type water closet is rated at 3 water supply fixture units and 4 drainage fixture units in standard tables.
T&P relief valve
Required on every water heater, set at or below the tank rating, installed in the top 6 inches, with a full-size discharge ending 6 to 24 inches above the floor.
Dishwasher drain protection
The dishwasher discharge must pass through an air gap or a high loop fastened under the counter before it connects to the sink drain or disposer.
Floor drain trap primer
A device that automatically adds water to a floor drain trap to replace evaporation, keeping the required 2 to 4 inch seal intact between uses.
Accessible water closet height
An accessible water closet has its bowl rim 17 to 19 inches above the floor and its centerline 16 to 18 inches from the side wall.
Indirect waste receptor
A fixture that receives liquid waste discharged through an air gap from appliances such as ice machines, sterilizers, or dishwashing equipment, never by direct connection.
SPS 382
The Wisconsin Administrative Code chapter that governs the design, construction, installation, and inspection of plumbing systems in buildings and on premises.
Rough-in inspection
An inspection performed after piping is installed and tested but before the work is concealed by framing, insulation, or finished surfaces.
Plumbing permit requirement
A permit must be obtained before installing, altering, or replacing plumbing piping, fixtures, or appliances, except for minor repairs the code specifically exempts.
Annual RPZ testing
Reduced pressure zone backflow assemblies must be tested at least once each year by a certified tester, with results reported to the water utility.
POWTS permit
A private onsite wastewater treatment system requires a soil evaluation and a state or county permit before it may be installed or replaced.
Master plumber license
The credential required in Wisconsin to obtain plumbing permits, contract for plumbing work, and supervise journeymen and apprentices on the job.