SAQCC Gas LPG Commercial/Industrial study materials
SAQCC Gas LPG Commercial/Industrial study resources

SAQCC Gas LPG Commercial/Industrial cheat sheet

SAQCC Gas LPG Commercial/Industrial · Keep the key ideas within reach.

Quick reference

Liquefied Petroleum Gas (LPG)

  • LPG vapour density is roughly 1.5-2.0 times that of air, so leaks pool at low points; ventilation openings and detectors belong at low level.

  • Propane and butane have different vapour pressures: commercial propane stays usable to about -40 °C, commercial butane only to about 0 °C, so winter blends are propane-enriched.

  • Liquid LPG expands about 0.3 % per °C; cylinders and vessels are never filled above roughly 80-85 % liquid volume to leave a vapour space for thermal expansion.

  • Approximate calorific values: propane 93 MJ/m3 (25,900 kJ/m3 gross), butane 122 MJ/m3 (gross); both burn with high primary aeration requirements (propane ~24:1 stoichiometric air).

  • Cylinder relief valves are set to protect against fire exposure, typically in the 15-17 bar range for propane cylinders, and discharge vapour not liquid.

  • LPG is odourised (ethyl mercaptan) so leaks are detectable at about one-fifth of the lower explosive limit; LPG LEL is roughly 2 % v/v and UEL roughly 10 % v/v.

  • A 48 kg LPG cylinder holds about 48 kg of liquid, which vapourises to roughly 24 m3 of propane gas at standard conditions (approx. 0.51 kg/L liquid density).

  • Regulators are two-stage on commercial installations: a first-stage regulator reduces cylinder pressure to about 1-2 bar, and a second-stage delivers 28-37 mbar for appliances.

  • Copper pipework is common for LPG but must be annealed and protected; steel pipe is used for larger commercial runs, and jointing compound must be LPG-resistant.

Quick reference

Natural Gas

  • Natural gas is predominantly methane (typically 85-95 %), is lighter than air (relative density ~0.6), and rises and disperses on release, so detectors go high.

  • Typical South African natural gas gross calorific value is about 38-42 MJ/m3; stoichiometric air requirement for methane is about 9.5:1 (roughly 10 volumes air per volume gas).

  • Methane LEL is about 5 % v/v and UEL about 15 % v/v; combustion is only possible within this band, so gas detection alarms commonly trip at 10-20 % LEL.

  • Natural gas is odourised with mercaptan or THT to give a detectable smell at about 1 % v/v, well below the LEL.

  • Gas piping sizing uses pressure drop limits: typically no more than about 1 mbar drop for low-pressure (2-7 kPa) domestic/commercial runs, with velocity kept below roughly 20-25 m/s.

  • Installations require an isolating valve at the meter/entry, and appliance connections use approved unions; flueing must be checked for spillage with a CO analyser or smoke match test.

  • Combustion CO is produced by incomplete combustion: yellow lazy flame, sooting and CO above 20-30 ppm in flue gases indicate excess primary air deficiency or blocked flue.

  • For gas leak testing, use air or inert gas at 1.5 times working pressure (minimum 1 bar) for a defined hold period; never pressure-test with gas or oxygen.

Quick reference

Air Conditioning and Refrigeration Gas

  • Common refrigerants and their safety groups: R410A (A1), R32 (A2L, mildly flammable), R290 propane (A3, highly flammable), R717 ammonia (B2L, toxic), R744 CO2 (A1 but high pressure).

  • R410A is a near-azeotropic blend of R32/R125 (50/50) and must be charged as liquid; it operates at roughly 1.6 times the pressure of R22, so only R410A-rated gauges and hoses may be used.

  • Superheat and subcooling are the diagnostic measures: target superheat is typically 5-8 K at the evaporator and subcooling 5-10 K; low superheat suggests overcharge, high superheat suggests undercharge or restriction.

  • Refrigerant glide applies to zeotropic blends (e.g. R407C): bubble and dew points differ, so charging and leak checking must reference the correct point on the PT chart.

  • R32 and R290 are flammable; R290 systems are limited to small charges (typically under 150 g per circuit for domestic units) and require no ignition sources in the occupied space.

  • Ozone depletion potential: CFCs (R12) ODP 1.0, HCFCs (R22) ODP ~0.055, HFCs (R134a, R410A) ODP 0. GWP: R410A ~2088, R32 ~675, R290 ~3.

  • Recovery, not venting, is mandatory: recovered refrigerant must be stored in dedicated recovery cylinders, never in disposable or unmarked vessels, and cylinders must not be filled above 80 % liquid.

  • Moisture in a refrigeration circuit forms acid and ice at the metering device; a filter-drier is fitted on the liquid line and the system is evacuated to below 500 microns before charging.

  • Pressure testing with nitrogen is standard; oxygen-free nitrogen is used with a regulator, and the system is never pressurised with oxygen or air because of oil-combustion risk.

Quick reference

Compressed Industrial and Medical Gases

  • Cylinder colour codes (South African/ISO practice): oxygen black with white shoulder, acetylene maroon, nitrogen grey/black, argon grey, carbon dioxide grey, medical oxygen white body with black shoulder.

  • Cylinder identification must never rely on colour alone; the valve outlet thread and shoulder stamping (gas name, test date, working pressure) are the authoritative identifiers.

  • Oxygen is an oxidiser, not a fuel: it does not burn but accelerates combustion; oil or grease on oxygen fittings can ignite, so only oxygen-clean equipment is used.

  • Acetylene cylinders contain a porous mass and acetone; the maximum safe withdrawal rate is about one-seventh of the cylinder contents per hour, and pressure must never exceed 1.5 bar gauge.

  • Compressed gas cylinders are hydrostatically tested periodically (commonly every 5-10 years depending on gas and standard) and stamped with the next test date.

  • Cylinders are stored upright and secured, with full and empty separated, oxidisers separated from fuels by at least 3 m or a fire wall, and away from heat sources.

  • Medical oxygen purity is typically 99.5 % minimum; medical air is filtered and tested for dew point, CO, CO2 and oil content, and piped medical systems are identified by specific NIST/quick-connect fittings.

  • Burst disc and pressure-relief devices protect cylinders and manifolds; a cylinder heated by fire may rupture, so the area is evacuated and cooled from cover if safe.

  • A full 50 L oxygen cylinder at 200 bar holds roughly 10,000 litres of gas at atmospheric pressure (contents = water capacity x pressure).