SAQCC Gas LPG Commercial/Industrial flashcards
SAQCC Gas LPG Commercial/Industrial · Build recall with a focused review session.
31 cards. Read the term and the definition here. The deck at the top of this page is optional.
- LPG vapour density relative to air
- LPG vapour is about 1.5 to 2 times denser than air, so leaks sink and accumulate at low points, drains and pits. Ventilation and gas detection must therefore be at low level.
- Maximum LPG cylinder fill
- Cylinders are filled to roughly 80 to 85 percent of liquid volume, leaving a vapour space. This allows for thermal expansion of liquid LPG, which expands about 0.3 percent per degree Celsius.
- Propane versus butane cold performance
- Commercial propane remains usable to about minus 40 degrees Celsius, while commercial butane stops vapourising near 0 degrees Celsius. Winter blends are propane-enriched for cold conditions.
- LPG lower explosive limit
- LPG has a lower explosive limit near 2 percent by volume and an upper limit near 10 percent. Odourisation allows detection at roughly one-fifth of the LEL.
- Two-stage LPG regulator pressures
- A first-stage regulator reduces cylinder pressure to about 1 to 2 bar. A second-stage regulator then delivers about 28 to 37 mbar to commercial appliances.
- LPG cylinder relief valve function
- Cylinder relief valves protect against overpressure from fire exposure and are typically set around 15 to 17 bar for propane. They discharge vapour, not liquid.
- LPG mass to gas volume
- One kilogram of liquid propane yields roughly 0.5 cubic metres of vapour at standard conditions. A 48 kg cylinder therefore holds about 24 cubic metres of gas.
- LPG leak detection placement
- Because LPG vapour is heavier than air, fixed detectors are mounted near floor level, and low-level ventilation openings are required in cylinder rooms and plant areas.
- Natural gas main constituent
- Natural gas is typically 85 to 95 percent methane, giving it a relative density near 0.6. Being lighter than air, it rises and disperses, so detectors are mounted high.
- Methane explosive range
- Methane has a lower explosive limit of about 5 percent and an upper limit of about 15 percent by volume. Combustion is only possible within this band in air.
- Methane stoichiometric air ratio
- Complete combustion of methane needs about 9.5 volumes of air per volume of gas, roughly 10:1. Insufficient primary air produces carbon monoxide and sooting.
- Natural gas calorific value
- Typical natural gas gross calorific value is about 38 to 42 megajoules per cubic metre. This figure is used for appliance rating and gas billing calculations.
- Natural gas odourisation level
- Natural gas is odourised with mercaptan or tetrahydrothiophene so it is smellable at about 1 percent by volume, well below the 5 percent lower explosive limit.
- Low-pressure gas pipe pressure drop
- Low-pressure natural gas pipework is sized so pressure drop does not exceed about 1 millibar on domestic and commercial runs, with gas velocity kept below roughly 20 to 25 metres per second.
- Gas installation leak test
- New pipework is strength and leak tested with air or inert gas at about 1.5 times working pressure, held for a defined period. Testing with gas or oxygen is prohibited.
- Carbon monoxide from gas appliances
- Incomplete combustion produces carbon monoxide. Yellow lazy flames, sooting and flue CO above roughly 20 to 30 parts per million indicate inadequate primary air or a blocked flue.
- Natural gas detector mounting height
- Methane is lighter than air, so fixed gas detectors and high-level ventilation openings are positioned near the ceiling or roof of the plant room.
- R410A composition and pressure
- R410A is a 50/50 blend of R32 and R125 and operates at roughly 1.6 times the pressure of R22. Only R410A-rated gauges and hoses may be used.
- Refrigerant safety group codes
- ASHRAE groups refrigerants by toxicity and flammability: A1 low toxicity and no flame propagation, A2L mildly flammable, A3 highly flammable such as propane, B2L toxic and flammable such as ammonia.
- Superheat diagnostic meaning
- Superheat is evaporator outlet temperature minus saturation temperature, typically 5 to 8 kelvin. Low superheat suggests overcharge; high superheat suggests undercharge or a restriction.
- Subcooling diagnostic meaning
- Subcooling is saturation temperature minus liquid line temperature, typically 5 to 10 kelvin. Excessive subcooling indicates overcharge; low subcooling indicates undercharge or flash gas.
- Zeotropic blend glide
- Blends such as R407C have a temperature glide, so bubble and dew points differ. Charging and leak checking must reference the correct point on the pressure-temperature chart.
- Flammable refrigerant charge limit
- R290 propane systems are restricted to small charges, typically under 150 grams per circuit for domestic units, and require no ignition sources in the occupied space.
- Refrigerant ODP and GWP values
- R12 has an ozone depletion potential of 1.0, R22 about 0.055, and HFCs such as R410A zero. Global warming potential: R410A about 2088, R32 about 675, R290 about 3.
- Recovery cylinder filling limit
- Recovered refrigerant goes into dedicated recovery cylinders, never disposable or unmarked vessels, and cylinders must not be filled above 80 percent liquid volume.
- Evacuation micron level
- Systems are evacuated to below about 500 microns before charging. Moisture left in the circuit forms acid and ice at the metering device, so a filter-drier is fitted.
- Oxygen cylinder identification
- In South African and ISO practice, industrial oxygen cylinders are black with a white shoulder, while medical oxygen cylinders are white. Valve thread and shoulder stamping remain the authoritative identifiers.
- Acetylene withdrawal rate limit
- Acetylene cylinders contain a porous mass and acetone. Maximum safe withdrawal is about one-seventh of cylinder contents per hour, and outlet pressure must never exceed 1.5 bar gauge.
- Oxygen handling hazard
- Oxygen is an oxidiser, not a fuel, but it greatly accelerates combustion. Oil or grease on oxygen fittings can ignite, so only oxygen-clean equipment may be used.
- Cylinder hydrostatic test interval
- Compressed gas cylinders undergo periodic hydrostatic testing, commonly every 5 to 10 years depending on gas and standard, and are stamped with the next test date.
- Cylinder gas content calculation
- Free gas content equals water capacity multiplied by fill pressure. A 50 litre cylinder at 200 bar holds roughly 10,000 litres of gas at atmospheric pressure.