Quick reference

Electrical Theory and Fundamentals

  • Ohm's law: E = I × R; power P = E × I = I²R = E²/R.

  • Series circuit: total resistance is the sum of resistances; current is the same through all elements.

  • Parallel circuit: total resistance is less than the smallest branch resistance; 1/RT = 1/R1 + 1/R2 + ...

  • AC effective (RMS) value equals the DC value producing the same heating; RMS = peak ÷ √2 for a sine wave.

  • Effective impedance Z = √(R² + X²), where X is net reactance (XL − XC).

  • Inductive reactance XL = 2πfL; capacitive reactance XC = 1/(2πfC).

  • Three-phase power: P = √3 × E × I × power factor for a balanced load.

  • A transformer changes voltage in the ratio of primary to secondary turns; power in equals power out (minus losses).

  • Conductor resistance varies directly with length and inversely with circular mil area: R = K·L/CM.

Quick reference

Branch Circuits, Feeders, and Service Calculations

  • Standard branch-circuit ratings include 15, 20, 30, 40, and 50 A; the overcurrent device sets the branch-circuit rating.

  • General lighting load for dwellings is calculated at 3 VA per square foot of floor area.

  • Small-appliance branch circuits in a dwelling: two or more 20 A circuits at 1500 VA each.

  • Laundry branch circuit in a dwelling: one 20 A circuit at 1500 VA minimum.

  • Demand factors apply to the general lighting and receptacle load above 3000 VA per the standard lighting demand table.

  • Service/feeder neutral load may be reduced but not below the maximum unbalanced load; certain nonlinear loads limit reduction.

  • Fixed electric space-heating loads are computed at 100 percent of nameplate rating.

  • The largest motor load is increased by 25 percent when sizing service and feeder conductors.

  • Range and appliance loads use the standard demand tables rather than simple summation.

Quick reference

Wiring Methods, Raceways, and Enclosures

  • Raceway fill: conductors must not exceed the permitted percentage of interior cross-sectional area (e.g., 40 percent for 3 or more conductors).

  • The number of conductors permitted in a raceway is found from the conductor dimension tables and the applicable fill percentage.

  • Boxes must be sized for the number and size of conductors, devices, and equipment grounding conductors present.

  • Each unspliced conductor passing through a box counts as one conductor volume allowance; spliced conductors count by size.

  • Raceways must be supported and secured within the required distance of boxes and at intervals set by the wiring method.

  • Expansion fittings are required where raceways cross building expansion joints or where thermal expansion is expected.

  • Bends in a single run between boxes or fittings are limited to 360 degrees total.

  • Metal raceways and enclosures must be bonded and connected to the equipment grounding conductor path.

Quick reference

Conductors, Cables, Boxes, and Outlet Devices

  • Ampacity of conductors is taken from the applicable conductor ampacity tables, then adjusted for ambient temperature and number of current-carrying conductors.

  • The 60°C column is the default ampacity basis unless the terminals and equipment are rated for a higher temperature.

  • Conductors in parallel must be the same length, same material, same size, and same insulation type.

  • Receptacle outlets must be spaced so that no point along the floor line is more than 6 feet from an outlet in dwelling unit walls.

  • Kitchen counter receptacles require ground-fault circuit-interrupter protection and no point along the counter more than 24 inches from a receptacle.

  • Boxes must be accessible; junction boxes may not be buried in walls or ceilings.

  • Cable must be secured within the required distance of boxes and supported at intervals specified for the cable type.

  • Conductor identification: grounded conductor is white or gray; equipment grounding conductor is green, green with yellow stripe, or bare.

Quick reference

Overcurrent Protection and Grounding/Bonding

  • Standard overcurrent device ratings: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100 A, and so on.

  • The next-higher standard rating may be used where the conductor ampacity does not correspond to a standard device rating, subject to the code limit.

  • Ground-fault circuit interrupter protection protects people from line-to-ground shock; it does not protect against line-to-line or overload.

  • Arc-fault circuit interrupter protection detects arcing and is required on specified dwelling branch circuits.

  • The service disconnecting means must be installed at a readily accessible location nearest the point of entry of the service conductors.

  • Bonding jumpers around water meters and other interrupting devices maintain continuity of the grounding path.

  • Equipment grounding conductors provide a low-impedance path to clear faults and must be sized per the equipment grounding conductor table.

  • Grounding electrode conductor sizing is based on the largest service conductor or the applicable table, whichever governs.

Quick reference

Motors, Controls, and HVAC Equipment

  • Motor branch-circuit conductors are sized at not less than 125 percent of the motor full-load current from the motor tables.

  • Motor overload protection protects the motor from overload; branch-circuit short-circuit and ground-fault protection protects the circuit.

  • The motor disconnecting means must be within sight of the motor and controller, or capable of being locked open.

  • Motor controller rating must be at least the horsepower rating of the motor it controls.

  • Motor full-load current is taken from the code motor tables, not from the nameplate, for conductor and protection sizing.

  • A separate overload device is set according to the motor's service factor and temperature rise, per the code rules.

  • HVAC equipment disconnects must be within sight of and readily accessible from the equipment.

  • Hermetic refrigerant motor-compressor branch circuits use the nameplate rated-load current for sizing per the code article.

Quick reference

Special Occupancies, Locations, and Equipment

  • Class I locations are those where flammable gases or vapors may be present; Class II is combustible dust; Class III is easily ignitable fibers.

  • Division 1 locations have the hazardous condition present under normal operation; Division 2 only under abnormal conditions.

  • Equipment in hazardous locations must be marked with the class, division or zone, and group for which it is approved.

  • Wet locations require weatherproof, gasketed enclosures and listed wet-location fittings.

  • Bathroom, garage, and outdoor receptacles in dwellings require ground-fault circuit-interrupter protection.

  • Swimming pool and similar installation rules require equipotential bonding of metallic parts.

  • Health care facility patient care areas have special grounding and receptacle requirements.

  • Tempory wiring must be listed and installed so it is protected from physical damage.

Quick reference

Safety, Code Administration, and Permit/Inspection Requirements

  • The authority having jurisdiction interprets and enforces the adopted electrical code and may require permits and inspections.

  • Work must be inspected before it is concealed; cover inspection is required before walls or ceilings are closed.

  • Permits are required for new electrical installations, alterations, and additions as defined by the adopted code and local ordinance.

  • Lockout/tagout procedures de-energize and isolate circuits before work begins.

  • Personal protective equipment, including voltage-rated gloves and eye protection, is required for energized work.

  • Approved plans and specifications must be on site and available to the inspector.

  • Defective or noncompliant work must be corrected and reinspected before the installation may be energized.

  • Only listed and labeled equipment may be installed; field modification of listed equipment voids the listing.

Quick reference

Alaska Statutes, Regulations, and Licensing Law

  • Alaska electrical work is regulated by the state through statutes and regulations administered by the Department of Labor and Workforce Development.

  • An electrician must hold the appropriate state license or be a registered apprentice working under supervision.

  • Licensing categories include journeyman and master electrician, plus an administrator certificate for electrical contractors.

  • Continuing education is required to renew an electrician license; the number of hours and cycle are set by regulation.

  • Electrical contractors must be licensed and must employ a licensed administrator.

  • Working outside the scope of a license or without a license is subject to civil penalties and disciplinary action.

  • The Alaska statutes define what electrical work requires a license and list the exemptions.

  • License renewal, reinstatement, and disciplinary procedures are governed by state regulation and board rules.

Quick reference

Electrical Theory and Fundamentals

  • Ohm's law: E = I × R; power P = E × I = I²R = E²/R.

  • Series circuit: total resistance is the sum of resistances; current is the same through all elements.

  • Parallel circuit: total resistance is less than the smallest branch resistance; 1/RT = 1/R1 + 1/R2 + ...

  • AC effective (RMS) value equals the DC value producing the same heating; RMS = peak ÷ √2 for a sine wave.

  • Effective impedance Z = √(R² + X²), where X is net reactance (XL − XC).

  • Inductive reactance XL = 2πfL; capacitive reactance XC = 1/(2πfC).

  • Three-phase power: P = √3 × E × I × power factor for a balanced load.

  • A transformer changes voltage in the ratio of primary to secondary turns; power in equals power out (minus losses).

  • Conductor resistance varies directly with length and inversely with circular mil area: R = K·L/CM.

Quick reference

Branch Circuits, Feeders, and Service Calculations

  • Standard branch-circuit ratings include 15, 20, 30, 40, and 50 A; the overcurrent device sets the branch-circuit rating.

  • General lighting load for dwellings is calculated at 3 VA per square foot of floor area.

  • Small-appliance branch circuits in a dwelling: two or more 20 A circuits at 1500 VA each.

  • Laundry branch circuit in a dwelling: one 20 A circuit at 1500 VA minimum.

  • Demand factors apply to the general lighting and receptacle load above 3000 VA per the standard lighting demand table.

  • Service/feeder neutral load may be reduced but not below the maximum unbalanced load; certain nonlinear loads limit reduction.

  • Fixed electric space-heating loads are computed at 100 percent of nameplate rating.

  • The largest motor load is increased by 25 percent when sizing service and feeder conductors.

  • Range and appliance loads use the standard demand tables rather than simple summation.

Quick reference

Wiring Methods, Raceways, and Enclosures

  • Raceway fill: conductors must not exceed the permitted percentage of interior cross-sectional area (e.g., 40 percent for 3 or more conductors).

  • The number of conductors permitted in a raceway is found from the conductor dimension tables and the applicable fill percentage.

  • Boxes must be sized for the number and size of conductors, devices, and equipment grounding conductors present.

  • Each unspliced conductor passing through a box counts as one conductor volume allowance; spliced conductors count by size.

  • Raceways must be supported and secured within the required distance of boxes and at intervals set by the wiring method.

  • Expansion fittings are required where raceways cross building expansion joints or where thermal expansion is expected.

  • Bends in a single run between boxes or fittings are limited to 360 degrees total.

  • Metal raceways and enclosures must be bonded and connected to the equipment grounding conductor path.

Quick reference

Conductors, Cables, Boxes, and Outlet Devices

  • Ampacity of conductors is taken from the applicable conductor ampacity tables, then adjusted for ambient temperature and number of current-carrying conductors.

  • The 60°C column is the default ampacity basis unless the terminals and equipment are rated for a higher temperature.

  • Conductors in parallel must be the same length, same material, same size, and same insulation type.

  • Receptacle outlets must be spaced so that no point along the floor line is more than 6 feet from an outlet in dwelling unit walls.

  • Kitchen counter receptacles require ground-fault circuit-interrupter protection and no point along the counter more than 24 inches from a receptacle.

  • Boxes must be accessible; junction boxes may not be buried in walls or ceilings.

  • Cable must be secured within the required distance of boxes and supported at intervals specified for the cable type.

  • Conductor identification: grounded conductor is white or gray; equipment grounding conductor is green, green with yellow stripe, or bare.

Quick reference

Overcurrent Protection and Grounding/Bonding

  • Standard overcurrent device ratings: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100 A, and so on.

  • The next-higher standard rating may be used where the conductor ampacity does not correspond to a standard device rating, subject to the code limit.

  • Ground-fault circuit interrupter protection protects people from line-to-ground shock; it does not protect against line-to-line or overload.

  • Arc-fault circuit interrupter protection detects arcing and is required on specified dwelling branch circuits.

  • The service disconnecting means must be installed at a readily accessible location nearest the point of entry of the service conductors.

  • Bonding jumpers around water meters and other interrupting devices maintain continuity of the grounding path.

  • Equipment grounding conductors provide a low-impedance path to clear faults and must be sized per the equipment grounding conductor table.

  • Grounding electrode conductor sizing is based on the largest service conductor or the applicable table, whichever governs.

Quick reference

Motors, Controls, and HVAC Equipment

  • Motor branch-circuit conductors are sized at not less than 125 percent of the motor full-load current from the motor tables.

  • Motor overload protection protects the motor from overload; branch-circuit short-circuit and ground-fault protection protects the circuit.

  • The motor disconnecting means must be within sight of the motor and controller, or capable of being locked open.

  • Motor controller rating must be at least the horsepower rating of the motor it controls.

  • Motor full-load current is taken from the code motor tables, not from the nameplate, for conductor and protection sizing.

  • A separate overload device is set according to the motor's service factor and temperature rise, per the code rules.

  • HVAC equipment disconnects must be within sight of and readily accessible from the equipment.

  • Hermetic refrigerant motor-compressor branch circuits use the nameplate rated-load current for sizing per the code article.

Quick reference

Special Occupancies, Locations, and Equipment

  • Class I locations are those where flammable gases or vapors may be present; Class II is combustible dust; Class III is easily ignitable fibers.

  • Division 1 locations have the hazardous condition present under normal operation; Division 2 only under abnormal conditions.

  • Equipment in hazardous locations must be marked with the class, division or zone, and group for which it is approved.

  • Wet locations require weatherproof, gasketed enclosures and listed wet-location fittings.

  • Bathroom, garage, and outdoor receptacles in dwellings require ground-fault circuit-interrupter protection.

  • Swimming pool and similar installation rules require equipotential bonding of metallic parts.

  • Health care facility patient care areas have special grounding and receptacle requirements.

  • Tempory wiring must be listed and installed so it is protected from physical damage.

Quick reference

Safety, Code Administration, and Permit/Inspection Requirements

  • The authority having jurisdiction interprets and enforces the adopted electrical code and may require permits and inspections.

  • Work must be inspected before it is concealed; cover inspection is required before walls or ceilings are closed.

  • Permits are required for new electrical installations, alterations, and additions as defined by the adopted code and local ordinance.

  • Lockout/tagout procedures de-energize and isolate circuits before work begins.

  • Personal protective equipment, including voltage-rated gloves and eye protection, is required for energized work.

  • Approved plans and specifications must be on site and available to the inspector.

  • Defective or noncompliant work must be corrected and reinspected before the installation may be energized.

  • Only listed and labeled equipment may be installed; field modification of listed equipment voids the listing.

Quick reference

Alaska Statutes, Regulations, and Licensing Law

  • Alaska electrical work is regulated by the state through statutes and regulations administered by the Department of Labor and Workforce Development.

  • An electrician must hold the appropriate state license or be a registered apprentice working under supervision.

  • Licensing categories include journeyman and master electrician, plus an administrator certificate for electrical contractors.

  • Continuing education is required to renew an electrician license; the number of hours and cycle are set by regulation.

  • Electrical contractors must be licensed and must employ a licensed administrator.

  • Working outside the scope of a license or without a license is subject to civil penalties and disciplinary action.

  • The Alaska statutes define what electrical work requires a license and list the exemptions.

  • License renewal, reinstatement, and disciplinary procedures are governed by state regulation and board rules.

Quick reference

Electrical Theory and Fundamentals

  • Ohm's law: E = I × R; power P = E × I = I²R = E²/R.

  • Series circuit: total resistance is the sum of resistances; current is the same through all elements.

  • Parallel circuit: total resistance is less than the smallest branch resistance; 1/RT = 1/R1 + 1/R2 + ...

  • AC effective (RMS) value equals the DC value producing the same heating; RMS = peak ÷ √2 for a sine wave.

  • Effective impedance Z = √(R² + X²), where X is net reactance (XL − XC).

  • Inductive reactance XL = 2πfL; capacitive reactance XC = 1/(2πfC).

  • Three-phase power: P = √3 × E × I × power factor for a balanced load.

  • A transformer changes voltage in the ratio of primary to secondary turns; power in equals power out (minus losses).

  • Conductor resistance varies directly with length and inversely with circular mil area: R = K·L/CM.

Quick reference

Branch Circuits, Feeders, and Service Calculations

  • Standard branch-circuit ratings include 15, 20, 30, 40, and 50 A; the overcurrent device sets the branch-circuit rating.

  • General lighting load for dwellings is calculated at 3 VA per square foot of floor area.

  • Small-appliance branch circuits in a dwelling: two or more 20 A circuits at 1500 VA each.

  • Laundry branch circuit in a dwelling: one 20 A circuit at 1500 VA minimum.

  • Demand factors apply to the general lighting and receptacle load above 3000 VA per the standard lighting demand table.

  • Service/feeder neutral load may be reduced but not below the maximum unbalanced load; certain nonlinear loads limit reduction.

  • Fixed electric space-heating loads are computed at 100 percent of nameplate rating.

  • The largest motor load is increased by 25 percent when sizing service and feeder conductors.

  • Range and appliance loads use the standard demand tables rather than simple summation.

Quick reference

Wiring Methods, Raceways, and Enclosures

  • Raceway fill: conductors must not exceed the permitted percentage of interior cross-sectional area (e.g., 40 percent for 3 or more conductors).

  • The number of conductors permitted in a raceway is found from the conductor dimension tables and the applicable fill percentage.

  • Boxes must be sized for the number and size of conductors, devices, and equipment grounding conductors present.

  • Each unspliced conductor passing through a box counts as one conductor volume allowance; spliced conductors count by size.

  • Raceways must be supported and secured within the required distance of boxes and at intervals set by the wiring method.

  • Expansion fittings are required where raceways cross building expansion joints or where thermal expansion is expected.

  • Bends in a single run between boxes or fittings are limited to 360 degrees total.

  • Metal raceways and enclosures must be bonded and connected to the equipment grounding conductor path.

Quick reference

Conductors, Cables, Boxes, and Outlet Devices

  • Ampacity of conductors is taken from the applicable conductor ampacity tables, then adjusted for ambient temperature and number of current-carrying conductors.

  • The 60°C column is the default ampacity basis unless the terminals and equipment are rated for a higher temperature.

  • Conductors in parallel must be the same length, same material, same size, and same insulation type.

  • Receptacle outlets must be spaced so that no point along the floor line is more than 6 feet from an outlet in dwelling unit walls.

  • Kitchen counter receptacles require ground-fault circuit-interrupter protection and no point along the counter more than 24 inches from a receptacle.

  • Boxes must be accessible; junction boxes may not be buried in walls or ceilings.

  • Cable must be secured within the required distance of boxes and supported at intervals specified for the cable type.

  • Conductor identification: grounded conductor is white or gray; equipment grounding conductor is green, green with yellow stripe, or bare.

Quick reference

Overcurrent Protection and Grounding/Bonding

  • Standard overcurrent device ratings: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100 A, and so on.

  • The next-higher standard rating may be used where the conductor ampacity does not correspond to a standard device rating, subject to the code limit.

  • Ground-fault circuit interrupter protection protects people from line-to-ground shock; it does not protect against line-to-line or overload.

  • Arc-fault circuit interrupter protection detects arcing and is required on specified dwelling branch circuits.

  • The service disconnecting means must be installed at a readily accessible location nearest the point of entry of the service conductors.

  • Bonding jumpers around water meters and other interrupting devices maintain continuity of the grounding path.

  • Equipment grounding conductors provide a low-impedance path to clear faults and must be sized per the equipment grounding conductor table.

  • Grounding electrode conductor sizing is based on the largest service conductor or the applicable table, whichever governs.

Quick reference

Motors, Controls, and HVAC Equipment

  • Motor branch-circuit conductors are sized at not less than 125 percent of the motor full-load current from the motor tables.

  • Motor overload protection protects the motor from overload; branch-circuit short-circuit and ground-fault protection protects the circuit.

  • The motor disconnecting means must be within sight of the motor and controller, or capable of being locked open.

  • Motor controller rating must be at least the horsepower rating of the motor it controls.

  • Motor full-load current is taken from the code motor tables, not from the nameplate, for conductor and protection sizing.

  • A separate overload device is set according to the motor's service factor and temperature rise, per the code rules.

  • HVAC equipment disconnects must be within sight of and readily accessible from the equipment.

  • Hermetic refrigerant motor-compressor branch circuits use the nameplate rated-load current for sizing per the code article.

Quick reference

Special Occupancies, Locations, and Equipment

  • Class I locations are those where flammable gases or vapors may be present; Class II is combustible dust; Class III is easily ignitable fibers.

  • Division 1 locations have the hazardous condition present under normal operation; Division 2 only under abnormal conditions.

  • Equipment in hazardous locations must be marked with the class, division or zone, and group for which it is approved.

  • Wet locations require weatherproof, gasketed enclosures and listed wet-location fittings.

  • Bathroom, garage, and outdoor receptacles in dwellings require ground-fault circuit-interrupter protection.

  • Swimming pool and similar installation rules require equipotential bonding of metallic parts.

  • Health care facility patient care areas have special grounding and receptacle requirements.

  • Tempory wiring must be listed and installed so it is protected from physical damage.

Quick reference

Safety, Code Administration, and Permit/Inspection Requirements

  • The authority having jurisdiction interprets and enforces the adopted electrical code and may require permits and inspections.

  • Work must be inspected before it is concealed; cover inspection is required before walls or ceilings are closed.

  • Permits are required for new electrical installations, alterations, and additions as defined by the adopted code and local ordinance.

  • Lockout/tagout procedures de-energize and isolate circuits before work begins.

  • Personal protective equipment, including voltage-rated gloves and eye protection, is required for energized work.

  • Approved plans and specifications must be on site and available to the inspector.

  • Defective or noncompliant work must be corrected and reinspected before the installation may be energized.

  • Only listed and labeled equipment may be installed; field modification of listed equipment voids the listing.

Quick reference

Alaska Statutes, Regulations, and Licensing Law

  • Alaska electrical work is regulated by the state through statutes and regulations administered by the Department of Labor and Workforce Development.

  • An electrician must hold the appropriate state license or be a registered apprentice working under supervision.

  • Licensing categories include journeyman and master electrician, plus an administrator certificate for electrical contractors.

  • Continuing education is required to renew an electrician license; the number of hours and cycle are set by regulation.

  • Electrical contractors must be licensed and must employ a licensed administrator.

  • Working outside the scope of a license or without a license is subject to civil penalties and disciplinary action.

  • The Alaska statutes define what electrical work requires a license and list the exemptions.

  • License renewal, reinstatement, and disciplinary procedures are governed by state regulation and board rules.