AK Fire Alarm study materials
AK Fire Alarm study resources

AK Fire Alarm cheat sheet

AK Fire Alarm · Keep the key ideas within reach.

Quick reference

Fire Alarm System Fundamentals and Terminology

  • A fire alarm system comprises initiating devices, notification appliances, control equipment, and interconnecting wiring supervised against fault conditions.

  • Addressable systems assign each device a unique digital address; conventional systems use zone circuits where multiple devices share one indicating circuit.

  • Detector spacing follows NFPA 72 Chapter 17 tables; spacing is generally 30 ft for standard smoke detectors on smooth ceilings up to 10 ft high.

  • A zone is a defined area of coverage; an annunciator displays status by zone or point and may be remote from the main control unit.

  • Supervising station types: central station, proprietary, remote supervising, and auxiliary - each with distinct signal routing and staffing rules.

  • Alarm, trouble, and supervisory signals are distinct conditions; supervisory signals indicate off-normal status of systems like sprinkler valves, not fire.

  • Spot-type detectors cover a defined area; projected-beam and air-sampling detectors protect large or high-ceiling spaces.

  • Positive alarm sequence delays notification up to 15 seconds for alarm verification and 180 seconds total for investigation, per NFPA 72.

Quick reference

Codes and Standards (NFPA 72, NFPA 70/NEC, NFPA 101, Alaska Fire Code)

  • NFPA 72 governs installation, inspection, testing, and maintenance of fire alarm systems; NFPA 70 (NEC) governs wiring methods and power.

  • NFPA 101 (Life Safety Code) sets occupancy-based requirements for detection, notification, and means of egress protection.

  • Alaska Fire Code adopts NFPA 1 and NFPA 101 with state amendments; local jurisdictions may add stricter requirements.

  • NEC Article 760 covers fire alarm wiring: Class 2/3 circuits use PLTC or FPL cable; NPLFA and PLFA power-limited classifications govern conductor sizing.

  • Class A circuits survive a single open; Class B circuits do not - survivability requirements depend on occupancy and system type.

  • NFPA 72 requires smoke detector spacing per the manufacturer's published listing and the coverage tables in Chapter 17.

  • Inspection, testing, and maintenance frequencies come from NFPA 72 Table 14.4.3.2; smoke detectors are tested annually at minimum.

  • Record of completion and record of inspection/testing forms (NFPA 72 Figure 7.8.2) document system acceptance and ongoing compliance.

Quick reference

Initiating Devices and Detection

  • Ionization detectors respond to products of combustion; photoelectric detectors respond to visible smoke - each suits different fire signatures.

  • Heat detectors are rate-of-rise, fixed-temperature, or combination; they respond slower than smoke detectors and suit spaces with nuisance smoke.

  • Manual pull stations mount 42–48 in. above finished floor to the operating handle, within 5 ft of an exit door.

  • Duct smoke detectors sample airflow and are required where air-handling systems exceed 2,000 cfm and serve more than one floor or 15,000 cfm total.

  • Projected-beam detectors suit large open areas; spacing and beam path must avoid obstructions and be within listed limits.

  • Air-sampling (ASD) detectors draw air through a pipe network; hole spacing and transport time are set by the manufacturer's listing.

  • Detector placement must maintain at least 3 ft horizontal distance from air supply diffusers and 36 in. from obstructions per NFPA 72.

  • Waterflow switches and valve tamper switches are initiating devices; tamper switches typically report supervisory, waterflow reports alarm.

Quick reference

Notification Appliances and Audibility/Visibility

  • Public mode audibility requires 15 dBA above ambient or 5 dBA above maximum ambient, whichever is greater, measured at 10 ft.

  • Private mode requires 10 dBA above ambient; sleeping areas require 75 dBA at the pillow or 15 dBA above ambient, whichever is greater.

  • Visible appliances must meet candela ratings per NFPA 72 Chapter 18; 15 cd minimum for most spaces, higher for larger rooms or sleeping areas.

  • Strobe mounting height: 80–96 in. above finished floor, or 6 in. below the ceiling, whichever is lower.

  • Audiovisual synchronization is required where multiple visible appliances are in the same view; synchronization within 10 ms per NFPA 72.

  • Voice evacuation systems must produce intelligible voice messages; intelligibility is measured by STI or CIS and must meet design criteria.

  • Notification appliance circuit voltage drop must be calculated to ensure the last appliance receives its listed minimum operating voltage.

  • Temporal-three pattern is the standard evacuation signal: three pulses, pause, three pulses, pause, three pulses, long pause.

Quick reference

Circuits, Wiring, and Power Supplies

  • Primary power: 120 VAC dedicated branch circuit; secondary power: batteries or generator sized for 24 hours standby plus 5 minutes alarm (or 15 min voice).

  • Battery capacity calculation: (standby current × standby hours) + (alarm current × alarm minutes/60) = ampere-hours required, then apply a 1.2 derating factor.

  • Class A circuits require a return path; a single open does not disable the circuit. Class B circuits lose function beyond an open.

  • Supervised circuits detect opens, shorts, and ground faults; end-of-line resistors terminate Class B circuits and must be at the last device.

  • NAC voltage drop: Vdrop = 2 × I × R × length, where R is resistance per unit length; keep last-device voltage above listed minimum.

  • Power-limited circuits must be separated from non-power-limited circuits by 2 in. or a barrier per NEC 760.

  • Ground fault detection is required on the system; a single ground fault should not cause an alarm or trouble that disables protection.

  • Battery recharge: the charging system must restore batteries to 80% capacity within 24 hours per NFPA 72.

Quick reference

Control Units, Signaling, and Supervisory Functions

  • The fire alarm control unit (FACU) processes initiating signals, activates notification, and reports alarm, trouble, and supervisory conditions.

  • Alarm signal processing: the control unit must activate notification within 10 seconds of an alarm signal from an initiating device.

  • Trouble signals must annunciate within 200 seconds of a fault; distinct audible and visual trouble indication is required at the FACU.

  • Supervisory signals (valve tamper, low air, low water) must annunciate within 200 seconds and are distinct from trouble and alarm.

  • Remote annunciators display zone or point status and must be supervised against connection faults.

  • Digital alarm communicator transmitters (DACT) transmit via two phone lines or network paths; two distinct transmission paths are required.

  • Alarm silence and system reset functions must be distinct; silencing notification must not prevent subsequent alarms from reactivating.

  • Drill switch or key-operated functions allow testing without transmitting signals to the supervising station, when permitted.

Quick reference

Inspection, Testing, and Maintenance

  • NFPA 72 Table 14.4.3.2 sets frequencies: control units annually, initiating devices annually, notification appliances annually (semi-annually in some cases).

  • Smoke detectors: functional test annually; sensitivity test within one year of installation and every two years thereafter, per manufacturer.

  • Battery tests: annual load test and 30-minute discharge test; replacement when capacity falls below 80% of rating.

  • Inspection is visual (no operation); testing verifies functional performance; maintenance restores or replaces components.

  • Test records must be retained and made available to the authority having jurisdiction; NFPA 72 requires documentation of all tests.

  • Sprinkler system supervisory devices (valve tamper, waterflow) are tested quarterly or as required by NFPA 25 and NFPA 72.

  • Voice evacuation systems require intelligibility testing and annual functional testing of the voice message and amplification.

  • Remote supervising station connections are tested annually; DACT connections tested monthly when required by the AHJ.

Quick reference

Installation Practices, Plan Review, and Documentation

  • Plan review checks: device layout and spacing, circuit classifications, battery calculations, voltage drop, and sequence of operations.

  • Shop drawings must show device locations, wiring riser diagram, conduit routing, and point-to-point connections.

  • The record of completion documents system description, device inventory, and certifications signed by the installer and AHJ.

  • As-built drawings reflect actual installed conditions and must be updated after any modification to the system.

  • Penetrations through fire-rated assemblies must be firestopped with listed materials to maintain the assembly rating.

  • Conductor identification: fire alarm circuits must be color-coded or tagged; red is conventional for fire alarm notification.

  • Sequence of operations matrix defines cause-and-effect for each initiating zone: which outputs activate, delay, or shut down.

  • Acceptance testing follows NFPA 72 Chapter 14 and requires AHJ witness; deficiencies must be corrected and retested before sign-off.

Quick reference

Installation Practices, Plan Review, and Documentation

  • Mounting heights: manual stations 42–48 in. to handle; visible appliances 80–96 in. to bottom or 6 in. below ceiling.

  • Smoke detector placement: at least 36 in. from air diffusers and obstructions; 4 in. minimum from wall when wall-mounted.

  • Conduit fill and support per NEC Chapter 3; fire alarm cable in plenums must be plenum-rated (FPLP).

  • Separation of power-limited and non-power-limited conductors: 2 in. minimum or listed barrier per NEC 760.30.

  • Battery calculations and voltage drop calculations must be submitted with plans for AHJ review.

  • Riser diagrams show panel locations, circuit numbers, and device counts per circuit; point-to-point wiring shows terminal connections.

  • Documentation package: shop drawings, calculations, sequence of operations, record of completion, and test records.

  • Modifications to an existing system require updated as-builts and may require a new record of completion and AHJ acceptance test.

Quick reference

Fire Alarm System Fundamentals and Terminology

  • A fire alarm system comprises initiating devices, notification appliances, control equipment, and interconnecting wiring supervised against fault conditions.

  • Addressable systems assign each device a unique digital address; conventional systems use zone circuits where multiple devices share one indicating circuit.

  • Detector spacing follows NFPA 72 Chapter 17 tables; spacing is generally 30 ft for standard smoke detectors on smooth ceilings up to 10 ft high.

  • A zone is a defined area of coverage; an annunciator displays status by zone or point and may be remote from the main control unit.

  • Supervising station types: central station, proprietary, remote supervising, and auxiliary - each with distinct signal routing and staffing rules.

  • Alarm, trouble, and supervisory signals are distinct conditions; supervisory signals indicate off-normal status of systems like sprinkler valves, not fire.

  • Spot-type detectors cover a defined area; projected-beam and air-sampling detectors protect large or high-ceiling spaces.

  • Positive alarm sequence delays notification up to 15 seconds for alarm verification and 180 seconds total for investigation, per NFPA 72.

Quick reference

Codes and Standards (NFPA 72, NFPA 70/NEC, NFPA 101, Alaska Fire Code)

  • NFPA 72 governs installation, inspection, testing, and maintenance of fire alarm systems; NFPA 70 (NEC) governs wiring methods and power.

  • NFPA 101 (Life Safety Code) sets occupancy-based requirements for detection, notification, and means of egress protection.

  • Alaska Fire Code adopts NFPA 1 and NFPA 101 with state amendments; local jurisdictions may add stricter requirements.

  • NEC Article 760 covers fire alarm wiring: Class 2/3 circuits use PLTC or FPL cable; NPLFA and PLFA power-limited classifications govern conductor sizing.

  • Class A circuits survive a single open; Class B circuits do not - survivability requirements depend on occupancy and system type.

  • NFPA 72 requires smoke detector spacing per the manufacturer's published listing and the coverage tables in Chapter 17.

  • Inspection, testing, and maintenance frequencies come from NFPA 72 Table 14.4.3.2; smoke detectors are tested annually at minimum.

  • Record of completion and record of inspection/testing forms (NFPA 72 Figure 7.8.2) document system acceptance and ongoing compliance.

Quick reference

Initiating Devices and Detection

  • Ionization detectors respond to products of combustion; photoelectric detectors respond to visible smoke - each suits different fire signatures.

  • Heat detectors are rate-of-rise, fixed-temperature, or combination; they respond slower than smoke detectors and suit spaces with nuisance smoke.

  • Manual pull stations mount 42–48 in. above finished floor to the operating handle, within 5 ft of an exit door.

  • Duct smoke detectors sample airflow and are required where air-handling systems exceed 2,000 cfm and serve more than one floor or 15,000 cfm total.

  • Projected-beam detectors suit large open areas; spacing and beam path must avoid obstructions and be within listed limits.

  • Air-sampling (ASD) detectors draw air through a pipe network; hole spacing and transport time are set by the manufacturer's listing.

  • Detector placement must maintain at least 3 ft horizontal distance from air supply diffusers and 36 in. from obstructions per NFPA 72.

  • Waterflow switches and valve tamper switches are initiating devices; tamper switches typically report supervisory, waterflow reports alarm.

Quick reference

Notification Appliances and Audibility/Visibility

  • Public mode audibility requires 15 dBA above ambient or 5 dBA above maximum ambient, whichever is greater, measured at 10 ft.

  • Private mode requires 10 dBA above ambient; sleeping areas require 75 dBA at the pillow or 15 dBA above ambient, whichever is greater.

  • Visible appliances must meet candela ratings per NFPA 72 Chapter 18; 15 cd minimum for most spaces, higher for larger rooms or sleeping areas.

  • Strobe mounting height: 80–96 in. above finished floor, or 6 in. below the ceiling, whichever is lower.

  • Audiovisual synchronization is required where multiple visible appliances are in the same view; synchronization within 10 ms per NFPA 72.

  • Voice evacuation systems must produce intelligible voice messages; intelligibility is measured by STI or CIS and must meet design criteria.

  • Notification appliance circuit voltage drop must be calculated to ensure the last appliance receives its listed minimum operating voltage.

  • Temporal-three pattern is the standard evacuation signal: three pulses, pause, three pulses, pause, three pulses, long pause.

Quick reference

Circuits, Wiring, and Power Supplies

  • Primary power: 120 VAC dedicated branch circuit; secondary power: batteries or generator sized for 24 hours standby plus 5 minutes alarm (or 15 min voice).

  • Battery capacity calculation: (standby current × standby hours) + (alarm current × alarm minutes/60) = ampere-hours required, then apply a 1.2 derating factor.

  • Class A circuits require a return path; a single open does not disable the circuit. Class B circuits lose function beyond an open.

  • Supervised circuits detect opens, shorts, and ground faults; end-of-line resistors terminate Class B circuits and must be at the last device.

  • NAC voltage drop: Vdrop = 2 × I × R × length, where R is resistance per unit length; keep last-device voltage above listed minimum.

  • Power-limited circuits must be separated from non-power-limited circuits by 2 in. or a barrier per NEC 760.

  • Ground fault detection is required on the system; a single ground fault should not cause an alarm or trouble that disables protection.

  • Battery recharge: the charging system must restore batteries to 80% capacity within 24 hours per NFPA 72.

Quick reference

Control Units, Signaling, and Supervisory Functions

  • The fire alarm control unit (FACU) processes initiating signals, activates notification, and reports alarm, trouble, and supervisory conditions.

  • Alarm signal processing: the control unit must activate notification within 10 seconds of an alarm signal from an initiating device.

  • Trouble signals must annunciate within 200 seconds of a fault; distinct audible and visual trouble indication is required at the FACU.

  • Supervisory signals (valve tamper, low air, low water) must annunciate within 200 seconds and are distinct from trouble and alarm.

  • Remote annunciators display zone or point status and must be supervised against connection faults.

  • Digital alarm communicator transmitters (DACT) transmit via two phone lines or network paths; two distinct transmission paths are required.

  • Alarm silence and system reset functions must be distinct; silencing notification must not prevent subsequent alarms from reactivating.

  • Drill switch or key-operated functions allow testing without transmitting signals to the supervising station, when permitted.

Quick reference

Inspection, Testing, and Maintenance

  • NFPA 72 Table 14.4.3.2 sets frequencies: control units annually, initiating devices annually, notification appliances annually (semi-annually in some cases).

  • Smoke detectors: functional test annually; sensitivity test within one year of installation and every two years thereafter, per manufacturer.

  • Battery tests: annual load test and 30-minute discharge test; replacement when capacity falls below 80% of rating.

  • Inspection is visual (no operation); testing verifies functional performance; maintenance restores or replaces components.

  • Test records must be retained and made available to the authority having jurisdiction; NFPA 72 requires documentation of all tests.

  • Sprinkler system supervisory devices (valve tamper, waterflow) are tested quarterly or as required by NFPA 25 and NFPA 72.

  • Voice evacuation systems require intelligibility testing and annual functional testing of the voice message and amplification.

  • Remote supervising station connections are tested annually; DACT connections tested monthly when required by the AHJ.

Quick reference

Installation Practices, Plan Review, and Documentation

  • Plan review checks: device layout and spacing, circuit classifications, battery calculations, voltage drop, and sequence of operations.

  • Shop drawings must show device locations, wiring riser diagram, conduit routing, and point-to-point connections.

  • The record of completion documents system description, device inventory, and certifications signed by the installer and AHJ.

  • As-built drawings reflect actual installed conditions and must be updated after any modification to the system.

  • Penetrations through fire-rated assemblies must be firestopped with listed materials to maintain the assembly rating.

  • Conductor identification: fire alarm circuits must be color-coded or tagged; red is conventional for fire alarm notification.

  • Sequence of operations matrix defines cause-and-effect for each initiating zone: which outputs activate, delay, or shut down.

  • Acceptance testing follows NFPA 72 Chapter 14 and requires AHJ witness; deficiencies must be corrected and retested before sign-off.

Quick reference

Installation Practices, Plan Review, and Documentation

  • Mounting heights: manual stations 42–48 in. to handle; visible appliances 80–96 in. to bottom or 6 in. below ceiling.

  • Smoke detector placement: at least 36 in. from air diffusers and obstructions; 4 in. minimum from wall when wall-mounted.

  • Conduit fill and support per NEC Chapter 3; fire alarm cable in plenums must be plenum-rated (FPLP).

  • Separation of power-limited and non-power-limited conductors: 2 in. minimum or listed barrier per NEC 760.30.

  • Battery calculations and voltage drop calculations must be submitted with plans for AHJ review.

  • Riser diagrams show panel locations, circuit numbers, and device counts per circuit; point-to-point wiring shows terminal connections.

  • Documentation package: shop drawings, calculations, sequence of operations, record of completion, and test records.

  • Modifications to an existing system require updated as-builts and may require a new record of completion and AHJ acceptance test.