AK Fire Alarm study materials
AK Fire Alarm study resources

AK Fire Alarm flashcards

AK Fire Alarm · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Addressable System
A fire alarm system in which each initiating device and notification appliance has a unique digital address, allowing the control unit to identify the specific device in alarm or trouble.
Conventional Zone System
A system where multiple devices share a single circuit, so the control unit reports only the zone in alarm rather than the individual device that initiated the signal.
Supervisory Signal
A signal indicating an off-normal condition of a system or device that is not a fire alarm, such as a closed sprinkler control valve or low air pressure.
Positive Alarm Sequence
An NFPA 72 feature allowing up to 15 seconds for alarm verification and 180 seconds total for investigation before notification appliances activate, requiring trained personnel.
NFPA 72 Scope
The National Fire Alarm and Signaling Code governs the application, installation, location, performance, inspection, testing, and maintenance of fire alarm and signaling systems.
NEC Article 760
The National Electrical Code article covering fire alarm systems, establishing wiring methods, power-limited classifications, and conductor requirements for fire alarm circuits.
Class A Circuit
A supervised circuit that includes a return path to the control unit, so a single open or break does not prevent operation of devices beyond the fault.
Alaska Fire Code Adoption
Alaska adopts NFPA 1 and NFPA 101 with state amendments; local jurisdictions may impose additional requirements stricter than the statewide minimum.
Photoelectric Detector
A smoke detector that responds to visible smoke by detecting light scattered or obscured by smoke particles, effective for smoldering fires producing larger particles.
Ionization Detector
A smoke detector that responds to products of combustion by measuring changes in ionization current, effective for fast-flaming fires producing smaller particles.
Manual Pull Station Height
Manual fire alarm boxes must be mounted so the operating handle is 42 to 48 inches above the finished floor, typically within 5 feet of an exit.
Duct Smoke Detector
A detector installed in an air-handling duct that samples airflow to detect smoke; required where air-handling systems exceed 2,000 cfm and serve multiple floors.
Temporal-Three Signal
The standard evacuation signal pattern of three audible pulses, a pause, three pulses, a pause, three pulses, then a long pause, repeated continuously.
Public Mode Audibility
Notification must produce 15 dBA above average ambient or 5 dBA above maximum ambient, whichever is greater, measured at 10 feet from the appliance.
Strobe Mounting Height
Visible notification appliances must be mounted 80 to 96 inches above the finished floor, or within 6 inches of the ceiling, whichever is lower.
Sleeping Area Audibility
In sleeping areas, notification must produce 75 dBA at the pillow or 15 dBA above ambient, whichever is greater, to reliably awaken occupants.
Battery Capacity Formula
Required ampere-hours equal standby current times standby hours plus alarm current times alarm minutes divided by 60, with a 1.2 derating factor applied.
End-of-Line Resistor
A resistor installed at the last device on a Class B supervised circuit that allows the control unit to detect opens and shorts in the wiring.
NAC Voltage Drop
The voltage lost along a notification appliance circuit, calculated as twice the current times resistance times length, keeping the last appliance above its listed minimum.
Secondary Power Requirement
Batteries or a generator must supply 24 hours of standby followed by 5 minutes of alarm, or 15 minutes for voice evacuation systems.
Alarm Processing Time
The fire alarm control unit must activate notification appliances within 10 seconds of receiving an alarm signal from an initiating device.
Trouble Signal Annunciation
A trouble condition must annunciate audibly and visibly at the control unit within 200 seconds of the fault, distinct from alarm and supervisory signals.
Digital Alarm Communicator
A transmitter that sends signals to a supervising station over telephone or network paths; two distinct transmission paths are required for reliability.
Remote Annunciator
A unit located away from the main control panel that displays alarm, trouble, and supervisory status by zone or point and must be supervised against faults.
Smoke Detector Sensitivity Test
Detector sensitivity must be checked within one year of installation and every two years thereafter, or per manufacturer's published instructions.
Battery Load Test
An annual test discharging the battery to verify capacity; batteries are replaced when capacity drops below 80 percent of the rated ampere-hour capacity.
Inspection Versus Testing
Inspection is a visual examination without operating the device; testing verifies functional performance; maintenance restores or replaces deficient components.
Record of Completion
An NFPA 72 form documenting the installed system description, device inventory, and certifications signed by the installer and the authority having jurisdiction.
Sequence of Operations
A matrix defining cause-and-effect for each initiating zone, specifying which outputs activate, which systems shut down, and any time delays.
As-Built Drawings
Drawings reflecting the actual installed condition of the fire alarm system, updated after any modification and retained for inspection by the authority.
Plenum-Rated Cable
Fire alarm cable installed in air-handling plenums must be listed as plenum-rated (FPLP) with low smoke and flame spread characteristics.
Power-Limited Separation
Power-limited fire alarm conductors must be separated from non-power-limited conductors by at least 2 inches or a listed barrier per NEC 760.