AK Fire Alarm key terms
AK Fire Alarm · Get comfortable with the vocabulary.
- Initiating Device Circuit (IDC)
- Related: Class A Circuit, Class B Circuit, Conventional Zone
The wiring path connecting automatic or manual initiating devices to the control unit, monitored so the panel can distinguish normal, alarm, open-circuit, and short-circuit conditions.
- Notification Appliance Circuit (NAC)
- Related: Synchronization, Candela Rating, Voltage Drop
The circuit that supplies power and signal to horns, strobes, speakers, and other alerting devices, typically supervised for opens and shorts and often limited in the load it can carry.
- Class A Circuit
- Related: Class B Circuit, Initiating Device Circuit (IDC), Supervision
A supervised circuit whose conductors leave the control unit and return on a separate path, so a single open or ground fault does not prevent operation of all devices on the circuit.
- Class B Circuit
- Related: Class A Circuit, End-of-Line Resistor, Supervision
A supervised circuit that runs out from the control unit and ends at the last device, so a single open fault disables all devices beyond the break while a short may impair the whole circuit.
- End-of-Line Resistor (EOLR)
- Related: Class B Circuit, Conventional Zone, Supervision
A resistor installed at the far end of a conventional Class B circuit that allows the panel to monitor wiring continuity and to detect a short across the zone.
- Addressable System
- Related: Addressable Device, Signaling Line Circuit, Conventional Zone
A system in which each initiating or notification device has a unique address, letting the control unit report the identity and location of individual devices rather than only a circuit or zone.
- Conventional Zone
- Related: Addressable System, End-of-Line Resistor, Initiating Device Circuit (IDC)
A grouping of initiating devices sharing one circuit, where the panel reports only the zone that went into alarm rather than which specific device operated.
- Addressable Device
- Related: Addressable System, Signaling Line Circuit, Detector Spacing
An initiating or notification appliance with a settable address that communicates individually with the control unit over the signaling line circuit and can be identified in reports and annunciation.
- Signaling Line Circuit (SLC)
- Related: Addressable System, Addressable Device, Class A Circuit
The addressable communication loop or path that carries digital data and power between the control unit and addressable devices, supporting individual device status reporting.
- Supervision
- Related: Trouble Signal, End-of-Line Resistor, Class A Circuit
Continuous monitoring of a circuit or component for abnormal conditions such as opens, shorts, or grounds, with a trouble signal generated when the monitored condition departs from normal.
- Trouble Signal
- Related: Supervision, Supervisory Signal, Alarm Signal
A distinctive audible and visual indication that a fault exists in the system, such as a wiring break, power loss, or device failure, requiring attention but not indicating an alarm condition.
- Supervisory Signal
- Related: Trouble Signal, Alarm Signal, Supervision
A signal indicating that a monitored system component, such as a valve or sprinkler switch, has changed from its normal or required condition and needs human attention.
- Alarm Signal
- Related: Notification Appliance Circuit (NAC), Audible Notification Appliance, Visible Notification Appliance
The output of the system that warns occupants of a fire or other emergency, typically produced by horns, strobes, or speakers and distinct from trouble or supervisory signals.
- Smoke Detector
- Related: Photoelectric Detector, Ionization Detector, Detector Spacing
An automatic initiating device that senses combustion products such as visible or invisible particles and signals the control unit, commonly using ionization or photoelectric sensing technology.
- Photoelectric Detector
- Related: Ionization Detector, Smoke Detector, Detector Spacing
A smoke detector that responds when smoke particles scatter or block a light beam within its sensing chamber, generally more responsive to visible smoldering smoke than to fast flaming fires.
- Ionization Detector
- Related: Photoelectric Detector, Smoke Detector, Detector Spacing
A smoke detector that responds when combustion particles alter the flow of ions between charged plates, generally more responsive to small particles from fast flaming fires than to large visible smoke.
- Detector Spacing
- Related: Smoke Detector, Heat Detector, Spot-Type Detector
The maximum distance permitted between smoke or heat detectors, and between detectors and walls, based on listed spacing and the ceiling height and configuration of the protected area.
- Heat Detector
- Related: Detector Spacing, Spot-Type Detector, Smoke Detector
An automatic initiating device that responds to a fixed temperature threshold, a rapid rate of temperature rise, or both, rather than to smoke or combustion products.
- Spot-Type Detector
- Related: Detector Spacing, Heat Detector, Smoke Detector
A detector whose sensing element responds to conditions at a specific location, as opposed to a projected-beam or line-type detector that senses along a path or area.
- Manual Pull Station
- Related: Initiating Device Circuit (IDC), Alarm Signal, Mounting Height
A hand-operated initiating device mounted along an exit path so occupants can manually activate the fire alarm when they observe a fire or other emergency.
- Audible Notification Appliance
- Related: Audibility, Visible Notification Appliance, Alarm Signal
A device such as a horn, bell, or speaker that produces an alarm sound intended to alert occupants, subject to sound pressure requirements and ambient noise considerations.
- Visible Notification Appliance
- Related: Candela Rating, Synchronization, Audible Notification Appliance
A strobe or other light-emitting device that provides a visual alarm signal, especially for occupants who are deaf or hard of hearing or in high-noise environments.
- Candela Rating
- Related: Visible Notification Appliance, Synchronization, Audibility
The measure of luminous intensity of a visible notification appliance, used to select strobes whose light output meets the required level for the room size and mounting conditions.
- Synchronization
- Related: Visible Notification Appliance, Candela Rating, Notification Appliance Circuit (NAC)
The coordinated flashing of visible notification appliances on a circuit or system so that strobes flash together within permitted timing limits, reducing seizure risk and meeting code requirements.
- Audibility
- Related: Audible Notification Appliance, Sound Pressure Level, Visible Notification Appliance
The sound pressure level produced by alarm notification appliances, measured relative to ambient noise, that must be sufficient to alert occupants throughout the protected area.
- Sound Pressure Level (SPL)
- Related: Audibility, Audible Notification Appliance
A measure of sound intensity, usually expressed in decibels, used to evaluate whether alarm signals exceed ambient noise by the required margin in a protected space.
- Voltage Drop
- Related: Notification Appliance Circuit (NAC), Primary Power Supply, Secondary Power Supply
The reduction in voltage along circuit conductors caused by resistance and load current, which must be calculated to ensure notification appliances receive adequate operating voltage at the end of a run.
- Primary Power Supply
- Related: Secondary Power Supply, Voltage Drop, Battery Backup
The normal source of commercial electrical power for the fire alarm system, typically a dedicated branch circuit that supplies the control unit and its charging equipment.
- Secondary Power Supply
- Related: Primary Power Supply, Battery Backup, Supervision
The standby source, usually rechargeable batteries or an engine-driven generator, that powers the fire alarm system when the primary power fails.
- Battery Backup
- Related: Secondary Power Supply, Primary Power Supply, Voltage Drop
Rechargeable batteries and charging circuitry that provide standby and alarm power for a specified duration when normal building power is interrupted.
- Control Unit
- Related: Addressable System, Conventional Zone, Trouble Signal
The central panel that receives signals from initiating devices, processes them, activates notification appliances, and annunciates alarm, trouble, and supervisory conditions.
- Annunciator
- Related: Control Unit, Trouble Signal, Alarm Signal
A remote or local display panel that indicates the status and location of alarm, trouble, and supervisory conditions, often used at entrances for responding personnel.
- Mounting Height
- Related: Manual Pull Station, Visible Notification Appliance, Accessibility
The required vertical elevation for devices such as manual pull stations and notification appliances, set so they are reachable or perceivable by occupants including those with disabilities.
- Inspection
- Related: Testing, Maintenance, Record of Completion
A visual and functional check of fire alarm system components to confirm they are installed, unobstructed, and in the condition required by the applicable codes and standards.
- Testing
- Related: Inspection, Maintenance, Record of Completion
The operational verification of system components and functions, performed at required intervals, to confirm that devices, circuits, and control functions respond as intended.
- Maintenance
- Related: Inspection, Testing, Record of Completion
The ongoing work of repairing, cleaning, adjusting, or replacing fire alarm components so the system continues to perform reliably between inspections and tests.
- Record of Completion
- Related: As-Built Drawings, Inspection, Plan Review
A document prepared at installation that records the system configuration, device locations, and design details, serving as a baseline for later inspection, testing, and maintenance.
- As-Built Drawings
- Related: Record of Completion, Plan Review, Shop Drawings
Drawings updated to reflect the actual installed configuration of the fire alarm system, including device locations and circuit routing, used for maintenance and future modifications.
- Plan Review
- Related: As-Built Drawings, Record of Completion, Authority Having Jurisdiction (AHJ)
The process of examining submitted fire alarm design documents for compliance with applicable codes, standards, and local requirements before installation is approved.
- Authority Having Jurisdiction (AHJ)
- Related: Plan Review, Record of Completion, Alaska Fire Code
The organization, office, or individual responsible for enforcing code requirements and approving equipment, installations, and procedures for the fire alarm system.
- Alaska Fire Code
- Related: Authority Having Jurisdiction (AHJ), NFPA 101, NFPA 72
The state-adopted fire prevention regulations, based on a model fire code with state amendments, that govern fire protection and life safety requirements in Alaska jurisdictions.
- NFPA 72
- Related: NFPA 70 (NEC), NFPA 101, Inspection
The National Fire Alarm and Signaling Code, which sets requirements for the design, installation, testing, inspection, and maintenance of fire alarm and signaling systems.
- NFPA 70 (NEC)
- Related: NFPA 72, Voltage Drop, Primary Power Supply
The National Electrical Code, which establishes requirements for electrical wiring, overcurrent protection, grounding, and installation methods that apply to fire alarm circuits.
- NFPA 101
- Related: NFPA 72, Alaska Fire Code, Occupancy Classification
The Life Safety Code, which addresses means of egress, occupancy classification, and fire protection features including when and where fire alarm systems are required.
- Occupancy Classification
- Related: NFPA 101, Alaska Fire Code, Plan Review
The category assigned to a building or space based on its use, which determines the fire alarm, detection, and egress features that the life safety code requires.