- Sensible heat equation
- Btu/h = 1.08 × CFM × temperature difference in °F, using standard air at 0.075 lb/ft³ and 0.24 Btu/lb·°F specific heat.
- One ton of refrigeration
- A cooling rate equal to 12,000 Btu per hour, originally defined as the heat absorbed by melting one ton of ice in 24 hours.
- Sensible heat ratio
- The ratio of sensible heat removed to total heat removed by a coil; typical comfort cooling values range from 0.70 to 0.80.
- Standard air density
- 0.075 pounds per cubic foot at 70°F and sea level; density falls about 3.5% per 1,000 ft of elevation, reducing mass flow.
- AFUE definition
- Annual Fuel Utilization Efficiency; the seasonal efficiency rating of furnaces and boilers, with condensing units typically above 90%.
- Combustion air requirement
- Approximately 50 cubic feet of indoor air per 1,000 Btu/h of appliance input when drawn from an unconfined space.
- Hydronic Btu formula
- Btu/h = 500 × gallons per minute × temperature drop in °F, using water at 8.33 lb per gallon and 60 minutes per hour.
- Furnace temperature rise
- Supply air temperature minus return air temperature; it must fall within the range printed on the furnace rating plate.
- Ventilation rate procedure
- ASHRAE 62.1 method: breathing zone rate equals people component times occupants plus area component times floor area.
- Velocity pressure formula
- VP in inches of water equals (velocity in fpm divided by 4005) squared, using the standard air constant 4005.
- Heat recovery ventilator
- An HRV transfers sensible heat between exhaust and supply airstreams; an ERV also transfers moisture, useful in tight Alaska envelopes.
- Duct velocity guidelines
- Typical design targets: 600–900 fpm in supply trunks, 400–700 fpm in branches, and 300–500 fpm in return ducts.
- Superheat measurement
- Actual suction line temperature minus the saturation temperature at suction pressure; target 8–12°F at the evaporator outlet with a TXV.
- Subcooling measurement
- Saturation temperature at the liquid-line pressure minus the actual liquid-line temperature; target 8–12°F for TXV systems.
- Refrigerant glide
- The temperature difference between bubble point and dew point in a zeotropic blend such as R-410A or R-407C during phase change.
- Recovery cylinder fill limit
- A refrigerant recovery cylinder may never be filled beyond 80% of its water capacity by weight, to allow thermal expansion.
- Copper tubing types
- Type K is heavy wall for underground use, Type L is standard above ground, and Type M is light wall for interior work only.
- Equal friction duct sizing
- A duct design method that maintains a constant pressure loss per foot of length through the entire supply and return system.
- Condensate drain slope
- Drains must slope at least 1/8 inch per foot toward the discharge and include a trap at the air handler to prevent air bypass.
- Insulation R-value per inch
- Approximate values: fiberglass 3.7, closed-cell polyisocyanurate 6.0, and spray polyurethane foam 6.5 per inch of thickness.
- Ohm's law and power
- E = I × R; single-phase watts = volts × amps × power factor; three-phase watts adds a 1.732 multiplier.
- Thermostat terminal letters
- R is 24V power, W is heat, Y is cooling, G is fan, C is common, and O or B is the reversing valve.
- Motor nameplate ratings
- Full-load amps, minimum circuit ampacity, and maximum overcurrent protection determine conductor size and breaker rating for the unit.
- Run capacitor tolerance
- A capacitor's measured microfarads should be within plus or minus 10% of the nameplate rating; outside that range it should be replaced.
- EPA Section 608 certification
- Federal credential required to service refrigerant-containing equipment; types cover small appliances, high pressure, low pressure, or universal.
- Carbon monoxide properties
- CO is colorless, odorless, and slightly lighter than air; it bonds to hemoglobin and is detected only with a calibrated instrument.
- Manifold gauge color code
- Blue hose connects to the low side, red to the high side, and yellow to the center port for charging or recovery.
- Nitrogen pressure testing
- Leak testing uses dry nitrogen regulated to the system design pressure; oxygen and acetylene must never be used as trace gases.
- Alaska Mechanical Administrator
- State license required for mechanical contractor work; the administrator must meet experience requirements and pass a written examination.
- Alaska HVAC journeyman licensing
- There is no statewide HVAC journeyman license; licensing is handled by municipalities such as Anchorage and Fairbanks.
- Alaska Business License
- Required for any person or entity conducting business in the state, renewed every two years through the Department of Commerce.
- Alaska workers' compensation
- Under Alaska Statute Title 23, employers must carry workers' compensation coverage; independent-contractor status is narrowly defined.