AL Plumber study materials
AL Plumber study resources

AL Plumber: Vents and Venting Systems

AL Plumber · Work through your exam, one topic at a time.

All guide sections

Vents and Venting Systems

Purpose and types

A vent equalizes pressure in the drainage system so trap seals survive. Know these types: individual, common, wet, circuit, stack, relief, and air admittance valves (where allowed). The stack vent is the extension of the soil stack above the highest branch; the vent stack is a separate vertical vent. Every trap needs a vent unless it is specifically exempted by a special venting arrangement.

Trap arm distance

The trap arm length - from the trap weir to the vent connection - is limited by pipe diameter and slope. Typical table values: 1-1/4 in = 5 ft, 1-1/2 in = 6 ft, 2 in = 8 ft, 3 in = 12 ft, 4 in = 16 ft. Always check the adopted code table, since slope changes these values.

Termination

Vents extend above the roof, clear of windows, doors, and air intakes - commonly 10 ft horizontally or 2 ft above an opening. Consider frost closure in cold climates (increase size before penetrating the roof).

Common traps

  • Venting a trap with a vent that is downstream of another fixture's drain (wet venting without meeting the rules).
  • Forgetting that vent size cannot be reduced in the direction of flow.
  • Running a vent horizontally below the flood-level rim of the fixture it serves.
  • Using an AAV where the code requires a true vent to atmosphere.
  • Terminating a vent inside a building or below a window.

Rule of thumb

If the trap arm is too long for its diameter, the trap will siphon - shorten the arm or upsize the pipe.

Worked example: A 2 in trap arm with a 10 ft developed length exceeds the 8 ft limit and must be shortened or the vent relocated closer to the trap.