AL Plumber: Backflow Prevention and Cross-Connection Control

AL Plumber ยท Work through your exam, one topic at a time.

All guide sections

Backflow Prevention and Cross-Connection Control

Two mechanisms

Backsiphonage is caused by negative pressure in the supply; backpressure is caused by downstream pressure exceeding supply pressure. Both can pull contaminants into potable water. The degree of hazard governs the device: high hazard (toxic, sewage, chemicals) versus low hazard (aesthetic only).

Assemblies and devices

  • Air gap - the best protection, a physical separation; typically at least twice the pipe diameter, minimum 1 in.
  • RPZ (reduced pressure zone) - high hazard, testable, with relief port.
  • DCVA (double check valve) - low hazard, testable.
  • PVB (pressure vacuum breaker) - cannot be under continuous pressure and cannot have downstream shutoff valves.
  • AVB (atmospheric vacuum breaker) - no downstream shutoff, no continuous pressure.
  • Hose bibb vacuum breaker - at every threaded hose outlet.

Testable assemblies require annual testing by a certified tester, with records kept. Devices must be accessible for testing and repair. Thermal expansion control is required downstream of a backflow preventer on a closed system.

Common traps

  • Choosing a DCVA for a high-hazard application when an RPZ is required.
  • Installing a PVB under continuous pressure.
  • Putting a shutoff valve downstream of an AVB.
  • Forgetting annual testing.
  • Confusing a backwater valve (drainage) with a backflow preventer (supply).

Rule of thumb

High hazard โ†’ air gap or RPZ. Low hazard โ†’ DCVA or PVB. If it must be tested and repaired in place, it must be accessible.

Worked example: A chemical-mixing station fed from a potable line is a high hazard; install an RPZ at the branch and test it annually.