AR Electrician flashcards
AR Electrician · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ohm's Law
- Ohm's law states that voltage equals current multiplied by resistance, E = I × R; rearranged, current equals voltage divided by resistance and resistance equals voltage divided by current.
- RMS Versus Peak Voltage
- For a sine wave, the RMS value equals 0.707 times the peak value and the peak equals 1.414 times the RMS value, so 120 V RMS corresponds to about 170 V peak.
- Three-Phase Power Formula
- For a balanced three-phase load, power in watts equals 1.732 times line voltage times line current times the power factor of the load.
- Conductor Resistance Formula
- Resistance equals a constant K times length in feet divided by circular mil area; K is about 12.9 for copper and 21.2 for aluminum at 75 degrees Celsius.
- NM Cable Restrictions
- Nonmetallic-sheathed cable is restricted to dry locations and may not be installed in wet locations, inside raceways, or where it would be subject to physical damage.
- EMT Support Spacing
- Electrical metallic tubing must be fastened within 3 ft of each box or fitting and supported at intervals not exceeding 10 ft along the run.
- Rigid Metal Conduit Burial
- Rigid metal conduit buried in earth requires a minimum cover of 6 in, while PVC conduit 2 in and smaller requires 18 in of cover.
- Service Drop Clearances
- Overhead service-drop conductors must be at least 10 ft above grade at the drip loop, 12 ft over residential driveways, and 18 ft over public streets.
- Dwelling Service Disconnecting Means
- A one-family dwelling service disconnecting means must be rated at least 100 A, installed as a single means, and located nearest the point of service conductor entry.
- Small-Appliance Branch Circuits
- Dwelling unit kitchens require at least two 20 A small-appliance branch circuits supplying countertop receptacles, and no other outlets may be connected to them.
- Ground Rod Ohm Rule
- A single driven ground rod must show 25 ohms or less resistance to earth, or it must be supplemented by one additional electrode at least 6 ft away.
- Grounding Electrode Conductor Sizing
- The grounding electrode conductor is sized using Table 250.66, which bases its minimum size on the size of the largest service-entrance or feeder conductor.
- Equipment Grounding Conductor Sizing
- The equipment grounding conductor is sized from Table 250.122 based on the rating of the overcurrent device protecting the circuit conductors.
- Metal Water Pipe Bonding
- Metal water piping must be bonded to the grounding system within 5 ft of where it enters the building and qualifies as an electrode only with 10 ft of earth contact.
- Next-Size-Up Rule
- The next higher standard overcurrent device may be used where conductor ampacity is 800 A or less, the circuit is not multioutlet, and the device does not exceed 800 A.
- Standard Overcurrent Device Ratings
- Standard ratings include 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, and 400 amperes.
- Service Ground-Fault Protection
- Ground-fault protection of equipment is required for solidly grounded wye services rated 1000 A or more with more than 150 V to ground, limited to 1200 A pickup.
- Box Fill Conductor Volumes
- Conductor volume allowances are 2.0 cubic inches for 14 AWG, 2.25 for 12 AWG, 2.5 for 10 AWG, and 3.0 for 8 AWG copper conductors.
- Conduit Fill Percentages
- Raceway fill may not exceed 53 percent for one conductor, 31 percent for two conductors, or 40 percent for three or more conductors.
- Free Conductor Length
- At least 6 in of free conductor must be left at each box, extending at least 3 in beyond the box opening to allow splices and device connections.
- Dwelling General Lighting Load
- Dwelling unit general lighting and general-use receptacles are calculated at 3 volt-amperes per square foot of floor area, excluding open porches and garages.
- Dwelling Lighting Demand Factors
- The first 3000 VA of dwelling lighting load is taken at 100 percent, the next 3000 VA at 35 percent, and any remaining volt-amperes at 25 percent.
- Range Demand One Unit
- Table 220.55 permits a demand load of 8 kW for a single household electric range with a nameplate rating of 12 kW or less.
- Motor Branch Conductor Sizing
- Motor branch-circuit conductors must have an ampacity of at least 125 percent of the motor full-load current taken from Table 430.250.
- Motor Overload Protection
- Motor overload protection is normally selected at 115 to 125 percent of the motor nameplate full-load current, with higher values allowed for certain slow-starting motors.
- Motor Short-Circuit Protection Values
- Table 430.52 permits an inverse-time circuit breaker at 250 percent and a dual-element time-delay fuse at 175 percent of motor full-load current.
- Class I Division 1
- A Class I Division 1 location is one where ignitable concentrations of flammable gases or vapors exist under normal operating conditions or frequently during repair work.
- Pool Equipotential Bonding
- Permanently installed pools require all metal parts, including the shell and fittings, to be bonded together with a solid 8 AWG copper conductor.
- Patient Care Redundant Grounding
- Patient care areas of health care facilities require a copper equipment grounding conductor installed in the raceway in addition to the raceway itself as a ground path.
- Working Space Depth
- For equipment rated 600 V or less under condition 1, the working space must be at least 36 in deep, 30 in wide, and 6 ft 6 in high.
- Arc Flash PPE Selection
- NFPA 70E requires arc-rated clothing and personal protective equipment chosen according to the incident energy exposure or arc flash PPE category of the task.
- Lockout Tagout Sequence
- The procedure is to de-energize the equipment, verify the absence of voltage with a tested meter, release stored energy, and apply a lock and tag.