ASSE 6010 study materials
ASSE 6010 study resources

ASSE 6010 flashcards

ASSE 6010 · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Backflow
Reverse flow of water or other substances into the potable water distribution system, caused by either backsiphonage or backpressure.
Cross-connection
Any actual or potential connection between a potable water system and a source of contamination or pollution.
Backsiphonage
Backflow caused by negative or subatmospheric pressure in the supply piping, which draws nonpotable liquid into the potable system.
Backpressure
Backflow caused when downstream pressure exceeds the supply pressure, pushing nonpotable water into the potable system.
Air gap
A physical vertical separation between a potable water outlet and the flood-level rim of a receiving vessel; it provides the highest degree of protection.
Health hazard
A cross-connection involving contamination that could cause illness or death, such as sewage, toxic chemicals, or pathogenic organisms.
Non-health hazard
A cross-connection involving a pollutant that may be unpleasant or objectionable but does not create an immediate health risk.
Containment protection
Protection installed at the water service entrance to prevent backflow from a customer's premises into the public water main.
Isolation protection
Protection installed at individual fixtures or branches to protect the potable water system within a building.
Annual testing
A common program requirement that each testable backflow prevention assembly be field-tested at least once every twelve months.
Approved assembly
A backflow prevention device listed by a recognized testing laboratory or approved by the local authority having jurisdiction.
Cross-connection survey
A site inspection that identifies actual or potential cross-connections, evaluates hazard, and determines required protection.
Test report
A record of assembly test results submitted to the water purveyor, property owner, and authority having jurisdiction as required.
Reduced pressure principle
An assembly with two check valves and a differential relief valve; it is used for health hazards and provides high protection.
Double check valve assembly
An assembly with two independent check valves and test cocks; it is used for non-health hazards and does not discharge water.
Pressure vacuum breaker
An assembly with a check valve and an air inlet; it must be installed above downstream piping and is used for non-health hazards.
Atmospheric vacuum breaker
A non-testable device with an air inlet that opens at atmospheric pressure; it cannot be under continuous pressure or have a downstream shutoff.
Relief valve
The hydraulically operated valve in an RPZ that discharges water when the pressure differential across the first check is lost.
Test cock
A small valve on an assembly used to connect test equipment and obtain pressure readings at specific points.
Check valve
A valve that allows flow in one direction only and closes to prevent reverse flow.
Differential pressure gauge
A test instrument that measures the difference between two pressures, commonly upstream and downstream pressures across a check valve.
Test cock flushing
Opening test cocks before connecting hoses to remove debris and prevent contamination or damage to the gauge.
RPZ relief test
A field test that determines the pressure at which the relief valve opens and discharges, verifying proper operation.
Check valve tightness
A field test that confirms a check valve holds against reverse pressure without leaking past the seat.
Gauge calibration
Periodic verification of test equipment accuracy, typically required at least annually by the authority or manufacturer.
Test cock numbering
Test cocks are numbered from upstream to downstream, beginning with number one at the supply side.
Relief valve discharge
Continuous discharge from an RPZ relief valve often indicates a leaking check valve, debris on the seat, or thermal expansion.
Fouled check valve
A check valve that fails to seat because of debris, scale, or worn rubber, causing backflow or relief valve discharge.
Strainer maintenance
Cleaning or replacing the upstream strainer removes debris that can clog check valves and cause test failures.
Manufacturer parts
Repair of backflow assemblies should use original manufacturer components to maintain approval and reliable operation.
Retest after repair
After any repair or replacement of components, the assembly must be field-tested again before being placed in service.
Freeze damage
Water freezing inside an assembly can crack bodies and distort seats, so assemblies must be drained or protected in freezing weather.