Cross-connection

Any actual or potential link between a potable water system and a source of contamination or pollution that could allow nonpotable fluid to enter the drinking water supply.

Related: Backflow, Air gap, Backsiphonage
Backflow

The unwanted reverse flow of water or other substances into the potable water system, moving opposite to the intended direction of flow. It is caused by either backsiphonage or backpressure.

Related: Backsiphonage, Backpressure, Cross-connection
Backsiphonage

Reverse flow created when pressure in the supply piping drops below atmospheric, pulling nonpotable liquid through a cross-connection into the system. Main breaks and heavy fire demand are common causes.

Related: Backpressure, Cross-connection
Backpressure

Reverse flow created when pressure downstream of a cross-connection is higher than the supply pressure, forcing nonpotable fluid into the potable system. Boilers, pumps, and elevated tanks are typical sources.

Related: Backsiphonage, Reduced pressure principle assembly (RP)
Air gap

The unobstructed vertical distance between the lowest opening of a water outlet and the flood level rim of the vessel it fills. It is the only absolute form of backflow protection.

Related: Flood level rim, Critical level
Flood level rim

The edge or rim of a receptacle or fixture over which water would spill. It serves as the reference point for setting a required air gap or a vacuum breaker's critical level.

Related: Air gap, Critical level
Critical level

A marking established by the manufacturer showing the minimum elevation at which a vacuum breaker must be installed relative to the flood level rim of the fixture or piping it protects.

Related: Flood level rim, Pressure vacuum breaker (PVB)
Health hazard

A cross-connection condition in which the contaminant could cause illness or death, such as sewage, toxic chemicals, or radioactive material. It requires the highest degree of protection available.

Related: Non-health hazard, Degree of hazard, Reduced pressure principle assembly (RP)
Non-health hazard

A cross-connection condition in which the contaminant would only degrade the taste, odor, or appearance of drinking water and is not expected to cause illness, such as a food-grade dye.

Related: Health hazard, Degree of hazard, Double check valve assembly (DCVA)
Degree of hazard

A rating that combines the toxicity of the potential contaminant with the likelihood that backflow will occur, and that determines which type of backflow prevention assembly must be installed.

Related: Health hazard, Non-health hazard
Premises isolation (containment)

Protection installed on the service line, usually just downstream of the water meter, so the customer's entire plumbing system cannot backflow into the public water main.

Related: Internal isolation (point-of-use), Authority having jurisdiction (AHJ)
Internal isolation (point-of-use)

Protection installed at an individual fixture, appliance, or process connection to keep a local hazard from contaminating the building's own drinking water distribution system.

Related: Premises isolation (containment), Cross-connection
Authority having jurisdiction (AHJ)

The health department, building department, water utility, or other body that adopts the cross-connection control ordinance, approves assemblies, issues permits, and enforces testing and reporting requirements.

Related: Annual testing requirement, Test report and tag
Certified backflow prevention assembly tester

A person who has completed an approved training course, passed written and practical examinations, and keeps certification current in order to legally test and report on backflow prevention assemblies.

Related: Annual testing requirement, Test report and tag
Annual testing requirement

A program rule found in most cross-connection ordinances requiring each testable assembly to be field tested at least once every twelve months, with the results filed with the authority.

Related: Certified backflow prevention assembly tester, Authority having jurisdiction (AHJ)
Reduced pressure principle assembly (RP)

A testable assembly with two spring-loaded check valves and a differential relief valve between them. The relief valve discharges to atmosphere if a check leaks, giving protection against both backsiphonage and backpressure for health hazards.

Related: Differential relief valve, Double check valve assembly (DCVA), Differential pressure
Double check valve assembly (DCVA)

A testable assembly of two independent spring-loaded check valves with test cocks and shutoff valves. It is approved only for non-health hazards because it provides no relief against backpressure.

Related: Double check detector assembly (DCDA), Check valve, Non-health hazard
Double check detector assembly (DCDA)

A double check valve assembly fitted with a parallel bypass line containing a water meter and a smaller double check, used on fire sprinkler systems so that low and domestic-type flows still register.

Related: Double check valve assembly (DCVA), Premises isolation (containment)
Pressure vacuum breaker (PVB)

A testable assembly with a spring-loaded check valve and an air inlet that opens when supply pressure drops. It protects against backsiphonage only and must be installed above all downstream piping.

Related: Critical level, Spill-resistant vacuum breaker (SVB), Continuous pressure
Spill-resistant vacuum breaker (SVB)

A vacuum breaker whose air inlet is held closed by a check valve so it does not spill water during normal flow, permitting continuous pressure service. It protects against backsiphonage only.

Related: Pressure vacuum breaker (PVB), Continuous pressure, Atmospheric vacuum breaker (AVB)
Atmospheric vacuum breaker (AVB)

A simple non-testable device whose air inlet opens at atmospheric pressure and seals when water flows. It cannot be installed under continuous pressure or downstream of a shutoff valve.

Related: Continuous pressure, Hose connection vacuum breaker
Hose connection vacuum breaker

A non-testable device with hose threads that screws onto a sillcock to prevent backsiphonage through a garden hose or portable equipment. It must be removed where freezing occurs.

Related: Atmospheric vacuum breaker (AVB), Freezing damage
Barometric loop

A length of pipe formed into an inverted U at least 35 feet high, where the standing column of water prevents backsiphonage. It offers no protection against backpressure.

Related: Backsiphonage, Air gap
Check valve

A valve that permits flow in one direction only and closes automatically when flow reverses. In testable backflow assemblies the checks are spring loaded and operate independently of each other.

Related: Differential pressure, Double check valve assembly (DCVA)
Differential relief valve

The hydraulically operated valve located between the checks of a reduced pressure assembly. It opens to atmosphere when the pressure differential across the first check falls below its set value, preventing backpressure and backsiphonage.

Related: Reduced pressure principle assembly (RP), Differential pressure
Shutoff valve

The full-port valves immediately upstream and downstream of an assembly that allow a tester to isolate and depressurize it for testing or repair without shutting down the entire building.

Related: Test cock, Hold test
Continuous pressure

A condition in which a device is subjected to water pressure for more than twelve continuous hours. Devices rated for this service must include a check valve to prevent spilling or discharge.

Related: Pressure vacuum breaker (PVB), Spill-resistant vacuum breaker (SVB)
Test cock

A small quarter-turn valve with a screwdriver slot located on a backflow assembly, used to attach test hoses, bleed air, and read pressure at a specific point during field testing.

Related: Purging test cocks, Differential pressure
Differential pressure

The difference between the pressure at the assembly inlet and the pressure between the checks, or across a single check. Assemblies must hold a minimum differential to pass a field test.

Related: Hold test, Reduced pressure principle assembly (RP)
Test gauge calibration

Checking a field test gauge against a certified reference and documenting the result, usually once a year. A gauge found out of tolerance makes every test performed with it invalid.

Related: Differential pressure, Test report and tag
Purging test cocks

Briefly opening and closing test cocks to push air and debris out of the gauge hoses so pressure readings settle quickly and reflect true conditions in the assembly.

Related: Test cock, Debris fouling
Hold test

Watching a gauge for a specified period with flow shut off to confirm that a check valve or relief valve keeps its required pressure difference or opening point without drifting.

Related: Differential pressure, Shutoff valve
Test report and tag

The form recording assembly location, make, model, size, serial number, gauge readings, and pass or fail result, filed with the authority with a copy left on site for the owner.

Related: Authority having jurisdiction (AHJ), Certified backflow prevention assembly tester
Thermal expansion

Pressure buildup in a closed piping system when heated water has nowhere to expand, which can damage an assembly or cause repeated discharge from a relief valve.

Related: Differential relief valve, Water hammer
Water hammer

A sharp pressure surge caused by a sudden stop or change in flow velocity, capable of cracking seats, loosening check valves, and producing false gauge readings during a test.

Related: Thermal expansion, Check valve
Debris fouling

Sand, scale, or pipe chips caught on a seat, disc, or relief valve so it cannot seal tightly. It is a leading reason an assembly fails its test and must be disassembled and cleaned.

Related: Rubber goods, Purging test cocks
Rubber goods

The elastomeric parts of an assembly, including seat discs, O-rings, diaphragms, and gaskets, which harden, swell, or tear with age and are replaced during routine repair.

Related: Debris fouling, Freezing damage
Freezing damage

Cracks or splits in the body, bonnet, or relief valve caused by water expanding as it freezes. It is avoided by installing assemblies in protected, drainable locations.

Related: Hose connection vacuum breaker, Rubber goods