ASSE 6010: Cross-Connection Control Principles and Backflow Theory

ASSE 6010 · Work through your exam, one topic at a time.

All guide sections

Cross-Connection Control Principles and Backflow Theory

Two ingredients, every time

Backflow is flow opposite to the intended direction. Every backflow event requires both a cross-connection (any actual or potential link between potable water and a nonpotable source) and a pressure reversal. Exam items love to offer a cross-connection under normal pressure and ask whether backflow is happening; it is not. The hazard exists, but flow has not reversed. Saying otherwise is the most common distractor.

Backsiphonage versus backpressure

Backsiphonage results from sub-atmospheric pressure in the supply - a main break, a nearby fire hydrant draft, high-flow demand, or a partial vacuum in a tall building's riser. Backpressure results when downstream pressure exceeds supply pressure - a booster pump, boiler, elevated tank, or thermal expansion. Questions frequently describe a pump and expect "backpressure," then describe a broken main and expect "backsiphonage." Do not confuse them.

Hazard categories

Contamination is a health hazard (toxic, infectious, radioactive); pollution is a non-health, aesthetic hazard (taste, odor, color). Hazard level drives device selection later, so classify deliberately.

Traps to expect

  • A single check valve is never accepted as a backflow assembly - it is not testable and not approved.
  • The critical level is the flood level rim of the receiving vessel, not its bottom.
  • A barometric loop protects against backsiphonage only, and only up to roughly 33–35 ft.
  • An air gap is the only absolute protection; mechanical devices can fail.

Rule of thumb

One psi supports a column of water 2.31 ft high (one foot of head equals 0.433 psi). A 12 psi vacuum can therefore lift a contaminant about 27 ft. Worked example: a submerged inlet sits 9 ft below the main. If the main pressure falls to zero, the head at the inlet is 9 × 0.433 ≈ 3.9 psi of back-siphon pressure - plenty to pull process water into the pipe.