ASSE 6030 study materials
ASSE 6030 study resources

ASSE 6030 flashcards

ASSE 6030 · Build recall with a focused review session.

33 cards. Read the term and the definition here. The deck at the top of this page is optional.

Cross-connection
Any actual or potential physical connection between a potable water supply and a source of nonpotable fluid or substance, allowing contamination to enter the drinking water system.
Backflow
The reverse flow of water or other substances into the distribution system of a public water supply from any source, caused by backsiphonage or backpressure.
Backsiphonage
Reverse flow caused by negative or subatmospheric pressure in the supply piping, which draws nonpotable fluid into the potable system through a cross-connection.
Backpressure
Reverse flow caused when downstream pressure exceeds the supply pressure, forcing nonpotable fluid back into the potable water system.
Containment isolation
Protection installed at the service connection to isolate an entire premises from the public water main, preventing backflow from the whole facility.
Pollution versus contamination
A pollution hazard degrades water quality without a health risk; a contamination hazard creates a health risk and requires the highest level of protection.
Pressure and head formula
Pressure in psi equals head in feet multiplied by 0.433, based on water weighing 62.4 pounds per cubic foot at standard conditions.
Absolute pressure
Absolute pressure equals gauge pressure plus atmospheric pressure, which is about 14.7 psi at sea level.
Maximum theoretical lift
A perfect vacuum equals 0 psia, so the maximum theoretical backsiphonage lift at sea level is about 33.9 feet of water.
Static versus residual pressure
Static pressure is measured with no flow; residual pressure is the pressure remaining while water is flowing through the system.
Water hammer
A pressure surge caused by a rapid change in water velocity, reduced by arrestors, slow-closing valves, and proper piping design.
Air gap
A physical separation between a potable outlet and the flood-level rim; it is the only non-mechanical method and provides the highest protection.
Reduced-pressure assembly
An assembly with two independently acting check valves and a hydraulically operating differential relief valve between them, used for health hazards.
Double check valve assembly
An assembly with two independently acting check valves and test cocks, used only for non-health hazards where backpressure is possible.
Pressure vacuum breaker
A device with a loaded check valve and loaded air inlet valve, installed above downstream piping and not subject to backpressure.
Atmospheric vacuum breaker
A device with an unloaded air inlet valve, limited to low-hazard applications not under continuous pressure, with no test cocks.
Spill-resistant vacuum breaker
A pressure vacuum breaker variant with a check valve that prevents spillage during normal operation and permits installation in pits with drainage.
ASSE 1013
The standard covering reduced-pressure principle backflow prevention assemblies, including requirements for design, performance, and testing.
ASSE 1015
The standard covering double check valve backflow prevention assemblies, used for non-health hazard applications where backpressure may occur.
ASSE 1020
The standard covering pressure vacuum breaker assemblies, which protect against backsiphonage only and must be installed above downstream piping.
AWWA C511
The AWWA standard covering reduced-pressure principle backflow prevention assemblies, complementing ASSE standards for water utility applications.
Safe Drinking Water Act
Federal law requiring public water systems to protect the distribution system from contamination, supported by regulations such as 40 CFR Part 141.
Health hazard protection
A health hazard requires an air gap or a reduced-pressure assembly, because these provide the highest level of protection against contamination.
Non-health hazard protection
A non-health hazard may be protected by a double check valve assembly, pressure vacuum breaker, or other approved device depending on conditions.
Detector assembly use
Detector assemblies on fire sprinkler systems detect unauthorized water use while protecting the supply from backflow.
Air gap height rule
The potable outlet must be at least twice the effective opening diameter above the flood-level rim, and never less than one inch.
PVB installation height
A pressure vacuum breaker must be installed at least 12 inches above the highest downstream piping or fixture, with local code governing exact height.
AVB installation limits
An atmospheric vacuum breaker must be installed at least 6 inches above the highest downstream piping and must not be under continuous pressure.
RP assembly installation
A reduced-pressure assembly must be installed horizontally with clearance for testing and repair, and must not be placed in a pit without drainage and access.
RP test sequence
Record supply pressure, check check valve one tightness, check relief valve opening point, check check valve two tightness, and record final readings.
Relief valve opening point
The relief valve must open at least 2 psi below the supply pressure, and the assembly must maintain the required differential between zones.
Test gauge calibration
Test gauges must be calibrated within the accuracy tolerance specified by the jurisdiction, and calibration dates must be recorded on test reports.
Program records
Records should include device location, make, model, size, serial number, installation date, test results, and tester identification for each assembly.