ASSE 6030 key terms
ASSE 6030 · Get comfortable with the vocabulary.
- Cross-connection
- Related: Backflow, Backsiphonage, Backpressure
Any actual or potential physical link between a potable water supply and a source of contamination or pollution. Such a link allows unwanted material to enter the drinking water system if pressure conditions reverse.
- Backflow
- Related: Cross-connection, Backsiphonage, Backpressure
The unwanted reverse flow of water, liquids, gases, or other substances into the potable water distribution system. It occurs whenever downstream pressure exceeds supply pressure or a negative pressure develops.
- Backsiphonage
- Related: Backpressure, Cross-connection, Vacuum breaker
Backflow caused by a negative or sub-atmospheric pressure in the supply piping, which draws nonpotable material into the system. Common causes include main breaks, heavy demand, and nearby firefighting.
- Backpressure
- Related: Backsiphonage, Cross-connection, Reduced pressure principle assembly
Backflow resulting from downstream pressure that is higher than the supply pressure in the potable system. Pumps, boilers, elevated tanks, and thermal expansion commonly create this condition.
- Pollution
- Related: Contamination, Hazard classification, Air gap
A condition that degrades water quality but does not create an actual health hazard. Examples include taste, odor, or color changes that make water unappealing without causing illness.
- Contamination
- Related: Pollution, Hazard classification, Reduced pressure principle assembly
Any impairment of water quality that creates an actual health hazard to consumers. It implies the presence of disease-causing organisms, toxic chemicals, or other harmful substances in the supply.
- Air gap
- Related: Flood-level rim, Backflow preventer, Pollution
A physical separation between the free-flowing discharge end of a supply pipe and the flood-level rim of a receiving vessel. It is the highest level of backflow protection available.
- Reduced pressure principle assembly
- Related: Check valve, Relief valve, Field test kit
A testable backflow prevention assembly containing two independently acting check valves and a hydraulically operated differential relief valve. It protects against both backsiphonage and backpressure at high hazard levels.
- Double check valve assembly
- Related: Reduced pressure principle assembly, Check valve, Hazard classification
A testable assembly with two independently acting check valves in series. It protects against backpressure and backsiphonage where the hazard is pollution rather than contamination.
- Pressure vacuum breaker
- Related: Vacuum breaker, Backsiphonage, Spill-resistant vacuum breaker
A testable assembly with one or two check valves plus an air inlet that opens at low supply pressure. It protects against backsiphonage only and must be installed above the highest downstream outlet.
- Spill-resistant vacuum breaker
- Related: Pressure vacuum breaker, Vacuum breaker, Air inlet
A vacuum breaker designed so the air inlet stays closed under normal supply pressure and opens only during backsiphonage. It may be installed in pits where ordinary vacuum breakers would spill water.
- Atmospheric vacuum breaker
- Related: Vacuum breaker, Air inlet, Backsiphonage
A non-testable device with an air inlet that opens when flow stops or pressure drops, admitting air to break a siphon. It must be installed at least six inches above the highest downstream outlet.
- Check valve
- Related: Double check valve assembly, Reduced pressure principle assembly, Relief valve
A valve that permits flow in only one direction and closes automatically when flow reverses. In backflow assemblies, check valves are spring-loaded or resilient-seated to hold tight against reverse pressure.
- Relief valve
- Related: Reduced pressure principle assembly, Check valve, Field test kit
The differential pressure relief component of a reduced pressure principle assembly. It discharges water to atmosphere when the pressure differential between the zones falls below the design threshold.
- Air inlet
- Related: Vacuum breaker, Atmospheric vacuum breaker, Spill-resistant vacuum breaker
A port on a vacuum breaker that opens to atmosphere to admit air and break a vacuum. Its proper opening and closing are checked during field testing of the device.
- Hazard classification
- Related: Contamination, Pollution, Air gap
The process of rating a cross-connection by the degree of risk it poses, usually as high (contamination) or low (pollution). The rating determines which type of backflow protection is required.
- Degree of hazard
- Related: Hazard classification, Contamination, Pollution
A measure of the seriousness of the potential harm from a cross-connection, considering the toxicity, pathogen content, and concentration of the contaminant. It drives selection of the appropriate protective device.
- Flood-level rim
- Related: Air gap, Atmospheric vacuum breaker, Critical level
The edge of a receiving vessel or fixture where water would overflow onto the floor. It is the reference point for setting the minimum air gap or vacuum breaker elevation.
- Critical level
- Related: Flood-level rim, Air gap, Pressure vacuum breaker
The marked elevation on a backflow device that establishes the minimum height above a flood-level rim or outlet. Installation below this mark can render the device ineffective and is a common inspection failure.
- Thermal expansion
- Related: Backpressure, Relief valve, Closed system
The increase in water volume as it is heated in a closed system, which raises pressure and can cause backpressure or relief valve discharge. Expansion tanks or thermal relief devices are common remedies.
- Closed system
- Related: Thermal expansion, Backpressure, Check valve
A piping arrangement with no open outlet that allows water to expand freely, such as a system with a check valve or backflow preventer at the service. It requires thermal expansion control.
- Water hammer
- Related: Relief valve, Shutoff valve, Field test kit
A pressure surge caused by the sudden stop of flowing water, producing a shock wave in the piping. It can damage backflow assemblies and cause nuisance relief valve discharges.
- Pressure differential
- Related: Field test kit, Relief valve, Check valve
The difference in pressure between two points in a system, such as across a check valve or between the zones of a reduced pressure assembly. Field tests measure it to confirm proper operation.
- Field test kit
- Related: Pressure differential, Reduced pressure principle assembly, Test cock
A set of calibrated gauges, hoses, and fittings used to verify the performance of a backflow assembly. It typically includes high- and low-pressure gauges and a differential pressure gauge.
- Test cock
- Related: Field test kit, Check valve, Relief valve
A small valved port on a backflow assembly used to attach test equipment and observe pressure at specific points. Opening the wrong test cock during testing can cause water damage or injury.
- Shutoff valve
- Related: Field test kit, Water hammer, Test cock
A valve used to stop flow to a backflow assembly for testing or repair. Both upstream and downstream shutoffs must hold tight for a valid field test.
- Containment protection
- Related: Isolation protection, Hazard classification, Cross-connection control program
Backflow protection installed at the service connection or property line to isolate the entire premises from the public main. It is the water purveyor's primary defense against customer-side hazards.
- Isolation protection
- Related: Containment protection, Air gap, Hazard classification
Backflow protection installed at each individual point of use or fixture within a building. It supplements containment by protecting occupants and the building's internal piping from localized hazards.
- Cross-connection control program
- Related: Containment protection, Tester certification, Records management
An organized effort by a water purveyor to identify hazards, require appropriate backflow protection, test assemblies, and maintain records. It typically includes surveys, permits, and enforcement procedures.
- Tester certification
- Related: Field test kit, Records management, Cross-connection control program
Formal credentialing that verifies a person has the training and skill to test backflow assemblies. Many jurisdictions require certification and periodic recertification before accepting test reports.
- Records management
- Related: Tester certification, Cross-connection control program, Field test kit
The systematic retention and tracking of test reports, permits, survey results, and repair records for backflow assemblies. Accurate records support enforcement, audits, and compliance reporting.
- Vacuum breaker
- Related: Atmospheric vacuum breaker, Pressure vacuum breaker, Air inlet
A device that admits air into piping when pressure drops, preventing a siphon from forming. Types include atmospheric, pressure, and spill-resistant models, each with specific installation limits.
- Backflow preventer
- Related: Air gap, Reduced pressure principle assembly, Double check valve assembly
A general term for any device or assembly installed to stop reverse flow, including air gaps, vacuum breakers, double check assemblies, and reduced pressure assemblies. Selection depends on hazard level.
- Premises isolation
- Related: Containment protection, Cross-connection control program, Hazard classification
A synonym for containment protection, referring to protection at the point where a customer's piping connects to the public water main. It shields the distribution system from on-site hazards.
- Nuisance discharge
- Related: Relief valve, Thermal expansion, Water hammer
Unwanted water released from a relief valve or air inlet, often from thermal expansion, pressure fluctuations, or debris. It signals a problem and can create slip hazards or water damage.
- Freeze protection
- Related: Installation elevation, Nuisance discharge, Shutoff valve
Measures taken to keep backflow assemblies and piping from freezing, such as insulation, heat tape, or draining. Frozen assemblies can crack and fail, causing contamination and flooding.
- Installation elevation
- Related: Critical level, Freeze protection, Air gap
The required height of a backflow device above the surrounding grade or flood level. Correct elevation ensures drainage, prevents submersion, and keeps the air inlet or relief port functional.
- Drainage
- Related: Nuisance discharge, Installation elevation, Relief valve
Adequate floor drains or discharge paths that carry away relief valve discharge and test water. Poor drainage can submerge assemblies, cause flooding, and create health or safety hazards.