ASSE 6030 study materials
ASSE 6030 study resources

ASSE 6030: Backflow Prevention Assemblies and Devices

ASSE 6030 · Work through your exam, one topic at a time.

All guide sections

Backflow Prevention Assemblies and Devices

The device family

Know each device, its mechanism, and its approved use.

  • Air gap: physical separation between supply and receiving vessel. Highest protection; protects against both mechanisms; requires no testing but needs inspection.
  • Reduced-pressure principle assembly (RP): two independently acting check valves plus a hydraulically operated differential relief valve. Protects against backsiphonage and backpressure; health-hazard rated.
  • Double check assembly (DC): two check valves, no relief. Protects against backpressure and backsiphonage for non-health hazards only.
  • Pressure vacuum breaker (PVB): one check plus an air inlet, for backsiphonage only, non-health and some health uses per local code; cannot be used under continuous pressure or where backpressure is possible.
  • Atmospheric vacuum breaker (AVB): air inlet only, no check, no downstream shutoff, no continuous pressure, backsiphonage only.
  • Spill-resistant vacuum breaker (SVB): like a PVB but the air inlet stays closed during normal flow, reducing discharge; backsiphonage only.
  • Hose bibb vacuum breaker and laboratory faucet vacuum breaker: small, point-of-use, backsiphonage only.

Traps

  • Assuming an RP and a DC differ only in test procedure; the relief valve is the defining difference.
  • Placing a DC on a health hazard.
  • Using a PVB or AVB where backpressure can occur.
  • Forgetting that AVBs cannot have downstream shutoff valves.

Rule of thumb

Health hazard plus backpressure possible = RP or air gap. Health hazard plus backsiphonage only = PVB or SVB (per code). Non-health hazard with backpressure = DC. Point-of-use, backsiphonage only = hose bibb or faucet vacuum breaker.

Worked example

A carbonator in a restaurant is fed potable water and can push CO₂-laden water back under pressure. That is a health hazard with backpressure, so an RP assembly or air gap is required, not a DC.