ASSE 6030: Field Testing Procedures and Troubleshooting

ASSE 6030 · Work through your exam, one topic at a time.

All guide sections

Field Testing Procedures and Troubleshooting

Test fundamentals

Testing verifies that check valves hold and that the relief valve opens at the correct differential. Use a calibrated differential test kit, record gauge readings, and follow the manufacturer's procedure. The three classic checks on an RP are: check valve 1 holds against reverse flow, check valve 2 holds, and the relief valve opens when the differential across check 1 falls to the specified threshold (commonly around 2 psi, but confirm the listing).

Typical sequence

  1. Flush and stabilize flow.
  2. Test check 1 for tightness.
  3. Test check 2 for tightness.
  4. Test relief valve opening point.
  5. Record all readings, device make, model, size, serial number, and tester certification.

Troubleshooting

  • Relief valve drips continuously: debris on check 1 seat, failed check 1, or thermal expansion.
  • Relief discharges during test only: normal if within specification; if outside, check 1 is leaking.
  • Check 2 fails: debris or worn seat; disassemble and clean, replace parts as needed.
  • Gauge readings erratic: air in the line, faulty gauge, or unstable supply pressure.

Traps

  • Passing a device without testing all three functions.
  • Using an uncalibrated gauge.
  • Confusing a normal relief discharge during testing with a failure.
  • Failing to record serial numbers, which invalidates the report.

Rule of thumb

Test in order, record everything, and never sign off on a device you could not fully exercise. A report without readings and serial numbers is not a valid test report.

Worked example

An RP relief valve drips at rest. The tester isolates the device and finds check 1 does not hold. The fix is to clean or replace check 1, not to adjust the relief valve spring.