Air Gap vs. RPZ at a Bottling Plant with Dual Supply

ASSE 6040 · Put your knowledge to work in context.

All case studies

Air Gap vs. RPZ at a Bottling Plant with Dual Supply

A beverage bottling plant has two water sources: a municipal service line at 60 psi and a private well pump that can deliver 85 psi. The two supplies are piped together downstream of check valves, and the blended water feeds a carbonation system where CO2 is injected at 90 psi. The plant engineer proposes replacing the existing reduced-pressure principle (RPZ) assembly on the municipal line with a simple dual-check valve because the well pump 'backs up' the city pressure. The municipal cross-connection inspector notes the well has a history of iron bacteria and that a hose bib with a submerged garden hose sits 4 feet from the carbonator. The plant wants to avoid a 12-inch air gap because of floor-space constraints and the need to boost pressure to the carbonator. The RPZ currently discharges from its relief port several times per shift. Describe what the inspector should require and why.

1. Evaluate the engineer's proposal to substitute a dual-check valve for the RPZ. Identify the hazard level and the applicable protection principle, and explain why the dual check is inadequate.

Read the worked answer

The proposal fails on two independent grounds.

First, hazard classification. The well water carries iron bacteria, a microbiological contaminant, and the carbonation loop injects CO2 at 90 psi, well above the 60 psi municipal supply. Any loss of city pressure creates a backsiphonage path from a system containing bacteria and dissolved gas. That is a health hazard (high hazard), not a non-health hazard. High hazards require an air gap or a reduced-pressure principle assembly; a double check valve is rated only for non-health hazards.

Second, the dual-check design. Two check valves are not testable for differential pressure relief and provide no mechanical means to dump water when upstream pressure drops. The RPZ's relief valve opens when the differential across the first check falls below about 5 psi, protecting against both backpressure and backsiphonage. The dual check has no relief port, so a pressure reversal simply seats the checks and traps contaminated water against the city main until the checks leak.

The recurring RPZ discharge is a symptom, not a reason to downgrade protection. It likely reflects thermal expansion or pressure fluctuations from the well pump cycling. The correct response is to diagnose the relief discharge (install a properly sized thermal expansion tank, verify the relief valve setting, confirm the first-check differential) and keep the RPZ. If the plant cannot tolerate discharge, an air gap with a collection/repump system is the alternative - not a check valve.

2. The plant argues floor space rules out a 12-inch air gap. What design options preserve high-hazard protection while addressing the space and pressure constraints?

Read the worked answer

Several compliant options exist; the inspector should present them rather than accept a downgrade.

  1. Air gap with a break tank and booster pump. A smaller receiving tank can be set below the carbonator feed, with the gap sized to the maximum discharge rate. A booster pump then raises pressure to the 90 psi injection point. This satisfies the air gap requirement and solves the pressure problem, at the cost of a tank and pump.

  2. Relocate the RPZ. The assembly can be installed at a different point on the municipal service - for example, immediately after the meter in a mechanical room - as long as it is accessible for testing and the discharge is piped to a drain. The 4-foot hose bib and carbonator remain protected because they are downstream of the assembly.

  3. Separate the systems entirely. If the well is the primary source for process water and the city is only a backup, an air gap between the two supplies (or a physical disconnect with a transfer switch) eliminates the blending that creates the cross-connection.

  4. Fix the hose bib. The submerged garden hose is itself an uncontrolled cross-connection; it needs a vacuum breaker or a hose-bibb vacuum breaker regardless of which assembly is chosen.

Any option must keep the assembly testable, drainable, and protected from freezing and backpressure. The inspector should document the hazard rating and require the chosen option in writing before approving the installation.