Cross-connection
Any actual or potential connection between a potable water system and a source of contamination or pollution that could allow backflow into the potable system.
Backflow
The reverse flow of water or other substances through a piping system, caused by backsiphonage or backpressure, that can contaminate the potable supply.
Backsiphonage
Reverse flow caused by a drop in supply pressure below atmospheric, creating a partial vacuum that draws nonpotable liquid into the potable piping.
Backpressure
Reverse flow caused when downstream pressure exceeds the pressure of the potable supply, pushing nonpotable water back into the potable system.
Contamination
The introduction of a substance that creates an actual hazard to public health when it enters the potable water system.
Pollution
The introduction of a substance that degrades water quality or appearance but does not create a health hazard to consumers.
Health hazard
A cross-connection condition that could cause illness or injury if backflow occurs, requiring the highest level of protection.
Non-health hazard
A cross-connection condition that degrades water quality but does not pose a health risk, allowing lower-level protection such as a double check valve.
Air gap
The vertical unobstructed distance between the lowest opening of a supply pipe and the flood-level rim of a receiving vessel; the only absolute backflow protection.
Reduced pressure principle assembly
A testable assembly with two spring-loaded check valves and a differential-pressure relief valve that discharges when the differential falls below about 5 psi.
Double check valve assembly
A testable assembly with two check valves used for non-health hazards where backpressure or backsiphonage could occur.
Pressure vacuum breaker
A testable device with a loaded check valve and an air inlet that opens on backsiphonage; it cannot be used where backpressure exists.
Atmospheric vacuum breaker
A non-testable device with a float check and air inlet that must be installed downstream of the last control valve and cannot be under continuous pressure.
Spill-resistant vacuum breaker
A testable device with a check valve and air inlet that can withstand continuous pressure and is used on systems such as boiler feed lines.
Hose-bibb vacuum breaker
A small device installed on hose connections to prevent backsiphonage; it must remain installed and be inspected periodically.
Dual check with intermediate vent
A device with two check valves and an intermediate vent used for low-hazard protection at a service connection.
ASSE 1013
The product standard covering reduced pressure principle assemblies, including performance and testing requirements for the assembly.
ASSE 1015
The product standard covering double check valve assemblies, specifying performance and testing requirements for the assembly.
ASSE 5110
The professional qualification standard for cross-connection control surveyors who inspect premises for cross-connections and hazards.
ASSE 5120
The professional qualification standard for backflow prevention assembly testers who test and maintain devices in the field.
ASSE 6040
The professional qualification standard for cross-connection control program administrators who manage program operations and compliance.
Safe Drinking Water Act
Federal law requiring public water systems to protect drinking water quality, including protection against cross-connection contamination.
Program authority
The legal basis, through ordinance, rule, or service contract, that allows a water supplier to require cross-connection control.
Hazard classification
The process of categorizing each service connection as a health hazard, non-health hazard, or no hazard to determine required protection.
Premises isolation
Protection installed at the service connection to prevent backflow from a customer's premises into the public water system.
Internal isolation
Protection installed inside a building to prevent backflow from a specific fixture or process into the building's own plumbing.
Differential pressure gauge
A field test instrument used to measure pressure differences across check valves and the relief valve of a reduced pressure principle assembly.
Relief valve opening point
The differential pressure at which the relief valve of a reduced pressure principle assembly opens, typically at least 2 psi.
Check valve hold test
A field test confirming that a check valve holds a specified minimum pressure, commonly 1 psi for double check assemblies.
Annual testing
The required periodic field test of backflow prevention assemblies, commonly performed once per year as set by the authority.
Device record
A file entry containing location, type, size, make, model, serial number, and test history for each backflow prevention assembly.
Test compliance rate
A program metric calculated as the number of assemblies tested on schedule divided by the total number of assemblies in the program.