ASSE 6040 study materials
ASSE 6040 study resources

ASSE 6040 cheat sheet

ASSE 6040 · Keep the key ideas within reach.

Quick reference

Cross-Connection Control Concepts and Terminology

  • Cross-connection: any actual or potential connection between a potable water system and any source of contamination or pollution.

  • Backflow is reverse flow of water, caused by either backsiphonage (supply-side pressure drop) or backpressure (downstream pressure exceeding supply pressure).

  • Backsiphonage occurs when supply pressure drops below atmospheric, creating a partial vacuum that draws nonpotable liquid into the piping.

  • Backpressure occurs when a downstream pressure, such as from a pump or elevated tank, exceeds the pressure of the potable supply.

  • Contamination is a substance that creates an actual hazard to public health; pollution degrades quality but does not create a health hazard.

  • An air gap is the vertical unobstructed distance between the lowest opening of a supply pipe and the flood-level rim of a receiving vessel.

  • The cross-connection control hierarchy: air gap, reduced pressure principle assembly, double check valve assembly, then vacuum breakers and check valves.

  • A cross-connection control program is the administrative and physical system used by a water supplier to protect the public water system from contamination.

Quick reference

Public Health Significance of Cross-Connections

  • A single cross-connection event can contaminate an entire distribution main serving thousands of people.

  • Backflow incidents cause gastrointestinal illness, chemical poisoning, and in some cases death from pathogens or toxic substances.

  • Common high-risk hazards include sewage, chemicals, pesticides, hospital waste, and industrial process water.

  • The 1933 Chicago World's Fair amoebiasis outbreak, linked to a cross-connection, sickened thousands and is a historic public health case.

  • Health risk is assessed by toxicity, pathogen content, and the likelihood and duration of exposure.

  • Pollution degrades water quality and aesthetics, whereas contamination can cause illness or injury.

  • Public notification and boil-water advisories are required when a contamination event is confirmed or suspected.

  • The safe drinking water framework treats cross-connection control as a critical barrier against intentional and accidental contamination.

Quick reference

Backflow Prevention Assemblies and Devices

  • An air gap is the only absolute protection against backflow; it requires no testing but must be physically maintained.

  • A reduced pressure principle assembly (RP) uses two spring-loaded check valves and a differential-pressure relief valve; the relief valve discharges when the differential drops below about 5 psi.

  • A double check valve assembly (DC) has two check valves and is used for non-health hazards only.

  • A pressure vacuum breaker (PVB) has a loaded check valve and an air inlet; it cannot be used where backpressure exists.

  • An atmospheric vacuum breaker (AVB) must be installed downstream of the last control valve and cannot be subject to continuous pressure.

  • A spill-resistant vacuum breaker (SVB) can withstand continuous pressure and is used on systems such as boiler feed lines.

  • A hose-bibb vacuum breaker is a small device for hose connections; it must remain installed and be checked periodically.

  • A dual check with intermediate vent (DuCV) is a device for low-hazard protection at the service connection.

  • An RP assembly must be installed with adequate drainage and a minimum clearance above flood level for the relief valve discharge.

Quick reference

Codes, Standards, and Regulations

  • ASSE 1001 covers atmospheric vacuum breakers; ASSE 1002 covers dual check with intermediate vent; ASSE 1011 covers hose-bibb vacuum breakers.

  • ASSE 1012 covers pressure vacuum breakers; ASSE 1013 covers reduced pressure principle assemblies; ASSE 1015 covers double check valve assemblies.

  • ASSE 1020 covers pressure-type vacuum breakers for use on boiler feed lines; ASSE 1047 covers spill-resistant vacuum breakers.

  • ASSE 5110 is the professional qualification standard for cross-connection control surveyors; ASSE 5120 covers backflow prevention assembly testers.

  • The Safe Drinking Water Act and EPA regulations require public water systems to protect against cross-connections.

  • State and local plumbing codes and water supplier regulations establish testing intervals and installation requirements.

  • ASSE 6040 is the professional qualification standard for cross-connection control program administrators.

  • NFPA 13 and local fire codes govern backflow protection on fire sprinkler systems and standpipes.

Quick reference

Program Development and Administration

  • A program includes authority, inspection, hazard assessment, device installation, testing, recordkeeping, and enforcement.

  • The water supplier must have legal authority to require cross-connection control through ordinance, rule, or service contract.

  • A cross-connection control program should identify all service connections and classify them by hazard level.

  • Program staffing includes a program administrator, surveyors, and certified testers.

  • The program should maintain a written policy, a hazard classification list, and a testing schedule.

  • Public education and outreach reduce accidental cross-connections and improve compliance.

  • Enforcement tools include notices, re-test orders, and service termination for noncompliance.

  • The program should be reviewed annually and updated when regulations or hazards change.

Quick reference

Premises Isolation and Hazard Assessment

  • Premises isolation protects the public water system at the service connection; internal isolation protects the building's own plumbing.

  • Hazard assessment determines whether a connection is a health hazard, a non-health hazard, or no hazard.

  • Health hazards require an air gap or reduced pressure principle assembly; non-health hazards may use a double check valve assembly.

  • A survey should inspect all fixtures, equipment, and processes that could create a cross-connection.

  • Typical high-hazard premises include hospitals, mortuaries, car washes, chemical plants, and irrigation systems.

  • Typical low-hazard premises include office buildings and retail stores with no process water.

  • The surveyor should document each hazard and recommend the appropriate protection method.

  • Premises isolation is required when internal protection cannot adequately protect the public system.

Quick reference

Field Testing, Inspection, and Maintenance

  • Reduced pressure principle assemblies are tested with a differential pressure gauge and must hold a minimum 5 psi differential across the first check.

  • The RP relief valve must open at a differential of at least 2 psi and close at a differential of at least 5 psi.

  • A double check valve assembly is tested by checking that each check valve holds a minimum of 1 psi.

  • A pressure vacuum breaker is tested for the check valve closing and the air inlet opening.

  • Test results must be recorded on a standard test report form with gauge readings and pass/fail status.

  • Devices must be tested at installation, after repair, and at intervals set by the authority, commonly annually.

  • Annual inspection includes checking for leaks, corrosion, debris, and proper installation height.

  • A failed assembly must be repaired or replaced and retested before being returned to service.

Quick reference

Records, Reporting, and Program Evaluation

  • Each device record should include location, type, size, make, model, serial number, and test history.

  • Test reports must be submitted to the water supplier within the time frame set by regulation.

  • Records should be retained for the period required by the authority, often at least five years.

  • Program evaluation metrics include the number of devices, test compliance rate, and number of violations.

  • A tracking system should flag devices due for testing and send reminders to property owners.

  • Trend analysis of test failures helps identify problem installations and prioritize inspections.

  • Annual reports to the governing body summarize program performance and recommend improvements.

  • Accurate records support enforcement actions and demonstrate due diligence in protecting public health.