Cert III Air Conditioning & Refrigeration study materials
Cert III Air Conditioning & Refrigeration study resources

Cert III Air Conditioning & Refrigeration cheat sheet

Cert III Air Conditioning & Refrigeration · Keep the key ideas within reach.

Quick reference

Work Health and Safety and Environmental Compliance

  • WHS duty holders: PCBUs must ensure health and safety so far as reasonably practicable; workers must take reasonable care and follow controls; officers exercise due diligence.

  • Hierarchy of control, highest to lowest: eliminate, substitute, engineering controls, administrative controls, PPE - PPE is the last line of defence only.

  • Refrigerant exposure: use oxygen-depletion and refrigerant monitors in plant rooms; ozone-depleting and high-GWP refrigerants require leak detection, logbook records and recovery, never venting.

  • Recovery targets: recover refrigerant before opening any circuit; recycled refrigerant may be reused only in equipment owned by the same owner; reclaimed refrigerant must meet purity standards.

  • Oxygen-fuel gas (oxy-acetylene) brazing: flashback arrestors on both regulators, cylinders upright and secured, hoses inspected, fire watch during and after hot work.

  • Electrical safety: tag-out/lock-out before work on control circuits; test for dead with a proven tester; RCDs on portable tools; safe isolation confirmed at the point of work.

  • Personal exposure limits: assess noise (85 dB(A) 8-hour action level), heat, and refrigerant exposure; record atmospheric tests before entering confined plant spaces.

  • Pressure hazards: never trap liquid refrigerant between closed valves; fit pressure relief devices; hydrostatic test with nitrogen, not air or oxygen, and never exceed test pressure.

  • Environmental records: refrigerant purchase, use, recovery and disposal must be documented; leak checks are more frequent for larger charge systems.

Quick reference

Refrigeration and Air Conditioning Fundamentals (Thermodynamics, Pressure-Temperature, Refrigerants)

  • Vapour-compression cycle sequence: evaporator absorbs heat, compressor raises pressure and temperature, condenser rejects heat, expansion device drops pressure and temperature.

  • Sensible heat changes temperature with no phase change; latent heat changes phase at constant temperature (latent heat of vaporisation is the dominant load in an evaporator).

  • Superheat = suction temperature minus evaporating (saturation) temperature; subcooling = condensing temperature minus liquid line temperature.

  • Pressure-temperature relationship: for a given refrigerant, saturation pressure fixes saturation temperature; use the PT chart for the specific refrigerant, never a substitute.

  • Refrigerant glide: zeotropic blends (e.g. R-407C) have a temperature glide, so use dew point for superheat and bubble point for subcooling calculations.

  • Common refrigerants: R-134a (medium temperature, GWP 1430), R-410A (high pressure, GWP 2088), R-32 (lower GWP alternative), R-744 (CO2, very high pressure, transcritical operation).

  • Compression ratio = absolute discharge pressure ÷ absolute suction pressure; high ratios raise discharge temperature and reduce volumetric efficiency.

  • Air properties: dry-bulb is sensible temperature, wet-bulb reflects evaporative cooling, dew point is where condensation begins; relative humidity is the ratio of actual to saturation vapour pressure.

Quick reference

Electrical and Control Systems for Refrigeration and Air Conditioning

  • Ohm's law V = I × R; power P = V × I for resistive loads; for AC use power factor: P = V × I × PF.

  • Single-phase motor start methods: permanent split capacitor (run capacitor only), capacitor-start capacitor-run, and positive temperature coefficient (PTC) start devices.

  • Three-phase supply: 400 V line-to-line, 230 V line-to-neutral in Australia; phase rotation must be correct for scroll and screw compressors or damage results.

  • Contactor and overload: thermal overload protects the motor; check trip class and reset; control circuit fuses protect the coil circuit, not the compressor.

  • Thermostat and pressure switch logic: low-pressure switch cuts out on low suction, high-pressure switch cuts out on high discharge; both are safety devices, not operating controls.

  • Defrost controls: time-initiated, temperature- or pressure-terminated; defrost termination sensor must be positioned to sense coil temperature, not air temperature.

  • Superheat control with thermostatic expansion valve: bulb clamped to suction line, insulated, and charged with the same refrigerant family as the system.

  • Electrical fault finding: measure voltage drop across contacts, resistance to earth, and insulation resistance (megger) before energising; compare readings to nameplate values.

Quick reference

Installation and Commissioning of Refrigeration and Air Conditioning Systems

  • Pipe sizing: suction lines sized for low pressure drop to protect capacity; liquid lines sized to avoid flashing; hot gas lines sized for velocity to carry oil.

  • Brazing: purge with dry nitrogen while brazing to prevent internal oxidation (scale); use silver-phosphor alloy for copper-to-copper joints.

  • Evacuation: triple evacuation with nitrogen breaks to below 500 microns (about 66 Pa) and hold to confirm no moisture or leaks.

  • Pressure testing: dry nitrogen test at the design test pressure, hold and record; never use oxygen or air on a refrigerant circuit.

  • Refrigerant charging: charge by weight where possible; for blends charge as liquid to avoid fractionation; verify superheat and subcooling after charging.

  • Airflow commissioning: measure static pressure, fan speed and air quantity; balance to design airflow; check filter pressure drop and coil face velocity.

  • Electrical commissioning: check supply voltage and phase sequence, motor rotation, control interlocks, and safety switch operation before full load.

  • Documentation at handover: as-installed drawings, commissioning records, refrigerant charge and type, and operating instructions.

Quick reference

Fault Finding, Diagnosis and Repair

  • Systematic diagnosis: gather symptoms, check the simplest causes first, confirm with measured superheat, subcooling, pressures and current draw before replacing parts.

  • High superheat with low suction pressure suggests undercharge, restricted liquid line, or a blocked/underfeeding expansion valve.

  • Low superheat with high suction pressure suggests overcharge or an overfeeding expansion valve; liquid floodback risks compressor damage.

  • High discharge pressure causes: poor condenser airflow, fouled coil, non-condensables in the circuit, or high ambient temperature.

  • Low discharge pressure with normal suction suggests compressor valve wear or low load; confirm with amp draw against nameplate.

  • Moisture indicators: sight glass colour change indicates moisture; acid test indicates oil breakdown; both point to evacuation or burnout issues.

  • Electrical faults: open winding, shorted winding, capacitor failure, or contactor pitting; isolate, prove dead, then test with a meter.

  • Repair verification: after repair, re-evacuate, recharge, and record superheat, subcooling and amp draw to confirm the fault is cleared.

Quick reference

Maintenance, Service and Decommissioning

  • Preventive maintenance scope: clean coils and filters, check refrigerant charge, inspect electrical connections, test safeties, lubricate moving parts, record readings.

  • Leak testing methods: electronic detector, soap bubbles, pressure decay, and UV dye; confirm the leak location and repair before recharging.

  • Refrigerant recovery: use recovery machines rated for the refrigerant; evacuate to the required vacuum; never mix refrigerant types in a recovery cylinder.

  • Decommissioning sequence: isolate electrical supply, recover refrigerant, purge with nitrogen, cap and label lines, remove oil and dispose of it as regulated waste.

  • Oil management: check oil level and colour; acidic or dark oil indicates overheating or moisture; oil type must match the compressor specification.

  • Compressor service: check winding resistance and insulation resistance, capacitor condition, and running current; record before and after values.

  • Records: maintenance logs, refrigerant usage records and service reports must be retained and available for audit.

  • Disposal: refrigerant cylinders, oil and contaminated components are regulated waste; use licensed contractors and record disposal.

Quick reference

Communication, Documentation and Customer Service

  • Job documentation: record site, equipment model and serial, refrigerant type and charge, readings, work performed, parts used and follow-up required.

  • Refrigerant records must show quantity purchased, used, recovered and disposed of, with dates and equipment identifiers.

  • Customer communication: explain the fault in plain language, state the options (repair, replace, monitor), and confirm the scope and cost before starting work.

  • Safety communication: advise the customer of hazards (electrical, refrigerant, hot work) and required isolation before work begins.

  • Warranty and compliance: document that work meets the relevant standard and manufacturer instructions; keep records for the warranty period.

  • Handover: provide operating instructions, maintenance schedule and emergency contact; confirm the customer understands the controls.

Quick reference

Workplace Practice, Teamwork and Industry Compliance

  • Licensing: refrigerant handling requires the appropriate national refrigerant handling licence; electrical work requires a licensed electrician.

  • Standards and codes: work to AS/NZS 1677 (refrigerating systems), AS/NZS 5141 (air conditioning), and the relevant electrical wiring rules.

  • Environmental obligations: ozone-depleting substances and synthetic greenhouse gases are regulated; venting is prohibited and leak reporting thresholds apply.

  • Teamwork: use clear handover, tag-out coordination, and permit systems when multiple trades work on the same plant.

  • Housekeeping: keep work areas clear, store cylinders upright and secured, and label all containers and lines.

  • Incident reporting: report hazards, near misses and injuries through the site system; participate in toolbox talks and risk assessments.

  • Continuous improvement: review procedures after incidents, update SWMS (safe work method statements) and share lessons with the team.