High Risk Work Licence - Standard Boiler (BS) flashcards
High Risk Work Licence - Standard Boiler (BS) · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Fire-tube boiler
- A boiler in which hot combustion gases pass through tubes surrounded by water. It is limited to lower pressures and smaller capacities than a water-tube boiler.
- Water-tube boiler
- A boiler where water circulates inside tubes that are heated externally by combustion gases. It suits high pressure and large steam output because small tubes withstand pressure well.
- Boiler heating surface
- The gas-side area of the boiler exposed to products of combustion, measured in square metres. It largely determines the evaporative capacity of the boiler.
- Equivalent evaporation
- The steam output expressed as evaporation of feedwater from and at 100 degrees Celsius. It allows boilers of different operating conditions to be compared fairly.
- Low-water fuel cutout
- A safety device that shuts off fuel to the burner when the water level falls below a safe limit. It must be tested regularly by evaporation or drain test.
- Safety valve accumulation test
- A test confirming that with the safety valve fully open, boiler pressure does not rise more than ten percent above the valve set pressure at maximum firing.
- Gauge glass blowdown
- Opening the gauge glass drain and connections to clear sludge and confirm that the indicated water level is true. It is done at least once per shift.
- Non-return feed valve
- A check valve between the feed pump and the boiler that allows feedwater in but prevents boiler water and steam from flowing back into the feed line.
- Injector principle
- Steam expands through a nozzle and condenses in the feedwater, transferring momentum and creating a pressure high enough to force water into the boiler.
- Normal water level
- The water level at the centre of the gauge glass during normal operation, with the lowest visible level safely above the highest heated surface.
- Modulating level control
- A control system that continuously adjusts the feedwater valve to hold water level within a narrow band as steam demand changes, avoiding cycling.
- Excess air
- Air supplied above the theoretical amount needed for complete combustion. Too little produces carbon monoxide and smoke; too much wastes heat up the stack.
- Balanced draft
- A combination of forced-draft and induced-draft fans that keeps the furnace slightly negative, preventing flame escape while drawing gases through the boiler.
- Furnace pre-purge
- Passing air through the furnace before ignition to clear any accumulated combustible gases, typically at least four furnace volume changes, preventing explosion.
- Flame failure protection
- A system that proves the flame with a scanner and shuts off fuel within seconds if the flame is lost, preventing unburnt fuel from accumulating.
- Scale formation
- Deposits of calcium and magnesium salts on heating surfaces. Scale insulates the metal, raises metal temperature and can cause tube overheating and failure.
- Dissolved oxygen corrosion
- Pitting of boiler metal caused by oxygen in the feedwater. It is controlled by deaeration and by chemical oxygen scavengers such as sodium sulphite.
- Total dissolved solids
- The concentration of dissolved salts in boiler water. It is controlled by blowdown to prevent foaming, priming and carryover into the steam system.
- Bottom blowdown
- Opening the valve at the lowest point of the boiler to remove sludge and sediment from the mud drum. It is done with the boiler at the correct water level.
- Surface blowdown
- A continuous or intermittent draw-off from the water surface that removes dissolved solids and scum, helping to control total dissolved solids and foaming.
- Cold start warming
- Bringing a cold boiler up to pressure slowly, with air vents open, to limit thermal stress on the shell, tubes and seams and avoid differential expansion damage.
- Paralleling a boiler
- Bringing a boiler on line by raising its pressure slightly above header pressure, draining the connecting line, then opening the stop valve slowly.
- Low-water emergency action
- If water is not visible in the gauge glass, shut off fuel immediately and do not feed water. Allow the boiler to cool before inspection to avoid a violent failure.
- Foaming and priming
- Foaming is a frothy water surface; priming is carryover of water droplets into the steam line. Causes include high dissolved solids, alkalinity, oil and overloading.
- Water hammer
- A sharp pressure shock caused by condensate slugs or trapped steam in a line. It is prevented by warming and draining lines before admitting steam.
- Furnace explosion
- Ignition of accumulated combustible gases in the furnace or flue. Prevention relies on pre-purge, proven flame scanner, correct fuel-air ratio and interlocked fuel valves.
- Hydraulic test
- A pressure test, usually at 1.25 to 1.5 times maximum allowable working pressure, with the boiler isolated and safety valves removed or gagged, to prove strength.
- Internal inspection
- An examination of the boiler interior, including shell, tubes, tubesheets, crown sheet, stays and mud drum, carried out at statutory intervals and recorded.
- Boiler log book
- A record of water level, steam pressure, feedwater temperature, blowdown, chemical tests and abnormal conditions, signed by the operator on each shift.
- High-risk work licence
- A statutory licence authorising the holder to operate a boiler of a specified class. Operating outside the scope of the licence is an offence.
- Primary duty of care
- The duty on a person conducting a business or undertaking to ensure health and safety so far as reasonably practicable, including safe plant and systems of work.
- Hierarchy of risk control
- The order of controls: eliminate the hazard, substitute, isolate, engineer, then administrative controls, with personal protective equipment as the last line.