High Risk Work Licence - Standard Boiler (BS) study plan
High Risk Work Licence - Standard Boiler (BS) · Give each week a clear focus.
8 weeks · About 7 hours per week
Boiler construction, types and terminology & Boiler fittings, valves, gauges and safety devices
Sketch and label the main pressure parts of a shell boiler (shell, furnace, tube plates, firetubes, crown and girder stays) from memory, naming each part's function
Distinguish firetube from watertube construction and list three operating consequences of each arrangement
Explain the purpose of at least eight boiler fittings (safety valve, main steam stop, feed check, feed isolating, blowdown, water gauge glass, pressure gauge, low-water cut-out) and where each sits in the steam/water circuit
Define the terminology set: working pressure, design pressure, MAWP, saturation temperature, priming, foaming, carry-over, and stay pitch
Your checkpoint
A hand-drawn, fully labelled boiler cross-section with a one-line function note for every fitting shown, self-marked against the study notes with corrections listed
Boiler fittings, valves, gauges and safety devices & Feedwater systems, pumps, injectors and water level control
Describe how a safety valve is set, tested and sealed, and state why it must never be gagged or isolated from the boiler
Sequence the correct water-level test procedure for a gauge glass, including blowing through, and explain how a low-water cut-out is proven
Compare feed pump types (centrifugal, reciprocating, injector) by principle of operation and typical application
Trace the feedwater path from storage through treatment, pump, economiser and feed check valve into the boiler
Your checkpoint
A written step-by-step procedure card (10-15 steps) for proving gauge glass and low-water cut-out correct, with the consequence of each step being skipped noted beside it
Combustion, fuels, burners and Draft systems & Start-up, shutdown and normal operating procedures
Explain the combustion triangle and the three T's, and relate excess air to stack loss and CO formation
Identify burner components (register, swirler, pilot, flame scanner, fuel control valve) and describe a safe light-up sequence including purge and proving time
Differentiate natural, forced, induced and balanced draft and state how each is achieved
Write the normal start-up sequence from cold for a standard boiler, from pre-start checks through to putting on load
Your checkpoint
A one-page cold start-up checklist in correct order, cross-checked against the light-up sequence so no purge, scanner-prove or warm-through step is missing
Boiler water chemistry, treatment and blowdown & Start-up, shutdown and normal operating procedures
Interpret the key water chemistry parameters (pH, total dissolved solids, alkalinity, hardness, dissolved oxygen, conductivity) and state the corrosion or scaling risk each controls
Explain the difference between bottom blowdown and surface (scum) blowdown and when each is used
Describe continuous and intermittent feedwater control and the operator's role in maintaining level within the normal band
Explain why a boiler is warmed through slowly and what thermal stress does to tube plates and stays
Your checkpoint
A timed 30-question self-test covering domains 1-6, scored, with every wrong answer rewritten as a corrected fact
Abnormal conditions, emergencies and accident prevention & Boiler fittings, valves, gauges and safety devices
List the immediate actions for low water, high water, and a gauge glass that shows a false level, and justify why the low-water response is not to add feed in an unproven condition
Describe the correct response to a tube leak, a safety valve lifting below set pressure, and a burner flame failure
Explain how priming and foaming are recognised, their causes, and the corrective actions
Distinguish an emergency shutdown from a normal shutdown and list the conditions that force an emergency stop
Your checkpoint
A decision-tree diagram for abnormal water level (low, high, false indication) showing the check, the action and the escalation point at each branch
Abnormal conditions, emergencies and accident prevention & Combustion, fuels, burners and Draft systems
Outline the actions for a furnace explosion or puff-back and the conditions that precede it
Describe fuel supply isolation, purge and leak-test requirements before relighting after a trip
Explain draft loss, high stack temperature and CO readings as early warning signs of poor combustion
State the reporting and isolation duties after any protective device operates
Your checkpoint
A written emergency response drill write-up for one scenario (furnace puff-back or flame failure), covering detection, immediate action, isolation, notification and return-to-service conditions
Inspection, maintenance, testing and record keeping & Legislative and duty-of-care responsibilities for boiler operation
List the inspections and tests due on a standard boiler (internal and external inspection, safety valve test, pressure gauge and cut-out checks) and the typical interval for each
Describe what records must be kept, why they matter evidentially, and how to complete a shift log accurately
Explain the operator's duty of care, the concept of competent person, and the obligation to stop and report unsafe conditions
Identify the licence class obligations and the consequences of operating outside them
Your checkpoint
A completed sample shift log and maintenance register for one week, plus a short written statement of the operator's reporting duties when a defect is found
Boiler construction, types and terminology & Boiler fittings, valves, gauges and safety devices & Feedwater systems, pumps, injectors and water level control & Combustion, fuels, burners and Draft systems & Boiler water chemistry, treatment and blowdown & Start-up, shutdown and normal operating procedures & Abnormal conditions, emergencies and accident prevention & Inspection, maintenance, testing and record keeping & Legislative and duty-of-care responsibilities for boiler operation
Revise every domain using the corrected facts gathered in weeks 1-7, prioritising the domains with the lowest practice scores
Complete two full-length timed practice papers under exam conditions
Explain aloud, without notes, the safety valve, gauge glass and low-water cut-out procedures
Review all decision trees and procedure cards and close any remaining gaps
Your checkpoint
Two scored practice papers with a one-page 'weak points' summary and a dated plan for the final 48 hours before the exam
Milestones
Week 2: Can name and locate every fitting on a boiler diagram and explain the gauge glass prove procedure without notes
Week 4: Scores at least 75% on the 30-question self-test across domains 1-6 and has rewritten every incorrect answer as a corrected fact
Week 6: Can state the low-water, flame failure and puff-back responses in the correct order, with escalation points, unaided
Week 8: Scores 85% or better on both full-length timed papers and has no unresolved gaps on the weak-points summary