Electrical theory and fundamentals

  • Ohm's law: V = I × R; I = V/R; R = V/I for resistive circuits.

  • Power: P = V × I = I²R = V²/R; single-phase real power P = V I cosφ.

  • Three-phase balanced load: P = √3 × V_L × I_L × cosφ; apparent power S = √3 × V_L × I_L.

  • Impedance Z = √(R² + X²); X_L = 2πfL; X_C = 1/(2πfC).

  • Series circuit: same current through all components; R_total = R1 + R2 + ...

  • Parallel circuit: same voltage across branches; 1/R_total = 1/R1 + 1/R2 + ...

  • Australian LV supply is nominally 230 V phase-to-neutral, 400 V phase-to-phase, 50 Hz.

  • Power factor = cosφ = P/S; lagging power factor can be corrected with capacitors.

Quick reference

Wiring Rules and installation standards (AS/NZS 3000)

  • AS/NZS 3000 (Wiring Rules) sets minimum requirements for design, selection, installation, verification and maintenance of electrical installations.

  • MEN system: neutral and protective earth are connected at the point of supply only; earth bar and neutral link remain separate at switchboards.

  • Protective earthing must connect exposed conductive parts to the earthing system; equipotential bonding is required for metallic services.

  • RCDs with 30 mA maximum residual current are required for socket-outlet and lighting final subcircuits in specified locations; check current edition exceptions.

  • Voltage drop from the point of supply to any point generally must not exceed 5% of nominal voltage for LV installations.

  • Cable cross-sectional area is selected for current-carrying capacity, voltage drop, protective device coordination and installation conditions.

  • Maximum demand is calculated using diversity and AS/NZS 3000 methods, not simply by adding all connected loads.

  • Segregation of electrical, communications and data cables is required to prevent interference and unsafe contact.

  • IP rating: first digit indicates protection against solids and dust (0-6); second digit indicates protection against water (0-9K).

Quick reference

Queensland electrical safety legislation and regulatory requirements

  • Electrical Safety Act 2002 (Qld) imposes duties to ensure electrical safety and to eliminate or minimise electrical risks so far as reasonably practicable.

  • Electrical Safety Regulation 2013 (Qld) supports the Act, covers licensing and safety requirements, and calls up AS/NZS 3000.

  • The Electrical Safety Office (ESO) administers Queensland electrical safety laws, licensing, investigations and compliance.

  • Electrical work must be carried out by a licensed electrical worker; an electrical contractor licence is required for electrical contracting.

  • Apprentices and trainees must be supervised according to their competency and licence conditions.

  • Work health and safety duties also arise under the Work Health and Safety Act 2011 (Qld).

  • Serious electrical incidents and dangerous events must be notified to the Electrical Safety Office or WorkSafe Queensland as required.

  • Licence classes define the scope of electrical work that may legally be performed.

Quick reference

Installation practice, testing and verification

  • Visual inspection before testing: check connections, enclosures, labels, damage, IP integrity and earthing.

  • Test sequence: protective earthing continuity, insulation resistance, polarity, earth fault loop impedance, RCD operation, then energise.

  • Insulation resistance test at 500 V DC with installation isolated; LV circuits should generally achieve at least 1 MΩ.

  • Continuity of protective earthing: low-resistance path from earth bar to exposed conductive parts, tested with a low-resistance ohmmeter.

  • Polarity: active conductors switched and connected correctly; neutrals not switched; socket outlets wired to correct terminals.

  • Earth fault loop impedance must be low enough for the protective device to operate within the required disconnection time.

  • RCD test: confirm the device trips at its rated residual current and within the required time.

  • Use calibrated instruments and prove the voltage tester before and after testing for dead.

  • After testing, record results, complete required certification, and restore covers and labels.

Quick reference

Electrical safety, risk control and safe work practices

  • Hierarchy of control: eliminate, substitute, engineering controls, administrative controls, then PPE as the last resort.

  • Isolate, lock out, tag out and test for dead before work; prove the tester on a known live source.

  • Treat all conductors as live until tested and isolated; maintain safe approach distances.

  • Use a SWMS or JSA for high-risk electrical work, identifying hazards, controls and responsibilities.

  • PPE may include insulated gloves, arc-rated clothing, safety glasses and hearing protection as risk assessment requires.

  • Arc flash risk: isolate upstream, use remote operation and keep clear of energised equipment; avoid solo live work.

  • Electric shock response: isolate supply, call emergency services, start CPR and use a defibrillator if trained.

  • Report hazards, incidents and near misses; isolate damaged equipment and tag it out.

  • Test instruments must be rated for the category and voltage and inspected before use.