BTEB Electrician (EIM) Exam · Put your knowledge to work in context.

All case studies

Cable Sizing for a Workshop Submain

A workshop is fed from a distribution board 38 m away by a three-core armoured cable clipped direct to a wall for 22 m, then in thermal insulation for 8 m, then in free air for 8 m. The load is a 400 V three-phase motor circuit drawing 45 A at full load with a starting current of six times full load for 8 seconds. The supply is TN-S with a prospective fault current of 4.5 kA at the origin. Ambient temperature is 35 °C. The client has specified a 63 A BS 88-2 fuse and a 10 mm² copper conductor because 'it fits the gland'.

1. Assess whether the client's 10 mm² proposal is defensible. Show the reasoning steps you would use, stating any assumptions.

Read the worked answer

Work through the standard design sequence rather than accepting the gland argument.

  1. Design current Ib = 45 A.
  2. Protective device In = 63 A, so Ib ≤ In is satisfied.
  3. Correction factors: ambient 35 °C gives roughly 0.94 for XLPE or 0.87 for PVC; grouping not stated, assume 1.0. The 8 m in thermal insulation is the problem: for a cable totally surrounded, derating can be around 0.5, and for one side in contact with insulation roughly 0.75. A partly enclosed run of 8 m is significant relative to the 38 m total.
  4. Required tabulated capacity It ≥ In / (Ca × Ci). With Ca 0.87 and Ci 0.75, It ≥ 63 / 0.65 ≈ 97 A.
  5. A 10 mm² three-core armoured cable clipped direct is typically around 60–70 A, well below 97 A. Even ignoring the insulation factor it is marginal at 63 A.

Conclusion: 10 mm² is not defensible; a larger conductor (likely 25 mm²) or rerouting the insulated section is needed. Verify against the actual cable manufacturer's tables before committing.

2. The motor starts at six times full load for 8 seconds. Explain how this affects fuse selection and whether the 63 A BS 88-2 fuse is suitable.

Read the worked answer

A BS 88-2 fuse must ride through the start without nuisance operation but still protect the cable. The starting current is 6 × 45 = 270 A for 8 s. A 63 A BS 88-2 fuse will typically carry several times its rating for a short period; at 270 A (about 4.3 × In) the pre-arcing time is normally well over 8 s, so the fuse should hold on start. That part is acceptable.

However, fuse suitability is only one of two checks. The cable must still be protected: the fuse's disconnection time at the relevant overcurrent must not damage the conductor, and the tabulated current-carrying capacity after correction must be at least In. Since the corrected capacity of 10 mm² fails that test, the fuse choice does not rescue the cable. Also check the adiabatic withstand k²S² ≥ I²t for the fault current, and verify earth-fault loop impedance gives disconnection within the required time (0.4 s for TN final circuits, 5 s for distribution circuits). Recommend a motor-rated device (e.g. an aM fuse or MPCB) coordinated with the starter rather than a general-purpose fuse if starting is frequent.